Shielding should be considered for non-metallic covered cables
operating at a circuit voltage above 2000 volts for single conductor cables and 5000 volts
for assembled conductors with a common overall jacket.
Definition of shielding
Shielding of an electric power cable is the
practice of confining the electric field of the cable to the insulation of the conductor
or conductors. It is accomplished by means of strand and insulation shields.
Functions of Shielding
A strand shield is employed to preclude
excessive voltage stress on voids between conductor and insulation. To be effective, it
must adhere to or remain in intimate contact with the insulation under all conditions.
An insulation shield has a number of
functions:
(a) To confine the electric field within the cable.
(b) To obtain symmetrical radial distribution of voltage stress within the dielectric,
thereby minimizing the possibility of surface discharges by precluding excessive
tangential and longitudinal stresses.
(c) To protect cable connected to overhead lines or otherwise subject to induced
potentials.
(d) To limit radio interference.
(e) To reduce the hazard of shock. If not grounded, the hazard of shock may be increased.
Use of Insulation Shielding
The use of shielding involves consideration
of installation and operating conditions. Definite rules cannot be established on a
practical basis for all cases, but the following features should be considered as a
working basis for the use of shielding.
Where there is no metallic covering or
shield over the insulation, the electric field will be partly in the insulation and partly
in whatever lies between the insulation and ground. The external field, if sufficiently
intense in air, will generate surface discharge and convert atmospheric oxygen into ozone
which may be destructive to rubber insulations and to protective jackets. If the surface
of the cable is separated from ground by a thin layer of air and the air gap is subjected
to a voltage stress which exceeds the dielectric strength of air, a discharge will occur,
causing ozone formation.
The ground may be either a metallic conduit,
a damp non-metallic conduit or a metallic binding tape or rings on an aerial cable, a
loose metallic sheath, etc. Likewise, damage to non-shielded cable may result when the
surface of the cable is moist, or covered with soot, soapy grease or other conducting film
and the external field is partly confined by such conducting film so that the charging
current is carried by the film to some spot where it can discharge to ground. The
resultant intensity of discharge may be sufficient to cause burning of the insulation or
jacket.
Where nonshielded nonmetallic jacketed
cables are used in underground ducts containing several circuits which must be worked on
independently, the external field if sufficiently intense can cause shocks to those who
handle or contact energized cable. In cases of this kind, it may be advisable to use
shielded cable. Shielding used to reduce hazards of shock should have a resistance low
enough to operate protective equipment in case of fault. In some cases, the efficiency of
protective equipment may require proper size ground wires as a supplement to shielding.
The same considerations apply to exposed installations where cables may be handled by
personnel who may not be acquainted with the hazards involved.
Operating
voltage limits kV, above
which insulation shielding is required
|
60 HERTZ POWER CABLE -
100 AND 133% INSULATION LEVEL |
1. Single and multiple conductor
cables with
metallic sheath or armor |
5kV |
2. Multiple conductor cables with common
overall discharge resisting jacket |
5kV |
| 3. Single conductor cables |
2kV* |
*Exception: Specially designed single conductor cables
for specific applications |
8kV |
Grounding Shielded Cable
When installing shielded cable, metallic
shielding must be solidly grounded. Where conductors are individually shielded, each must
have its shielding grounded and the shielding of each conductor should be carried across
every joint to assure positive continuity of a shielding from one end of the cable to the
other. Where grounding conductors are part of the cable assembly, they must be connected
with the shielding at both ends of the cable.
For safe and effective operation, the
shielding should be grounded at each end of the cable and at each splice. For short
lengths or where special bonding arrangements are used, grounding at one point only may be
satisfactory.
All grounding connections should be made to
the cable shield in such a way as to provide a permanent low resistance bond. Soldering
the connection to the cable shield in usually preferable to a mechanical clamp, as there
is less danger of a poor connection, loosening, or injury to the cable. The area of
contact should be ample to prevent the current from heating the connection and melting the
solder.
For additional security, a mechanical
device, such as a nut and bolt, may be used to fasten the ends of the connection together.
This combination of a soldered and mechanical connection provides permanent low resistance
which will maintain contact even though the solder melts.
The wire or strap used to connect the cable
shield ground connection to the permanent ground must be of ample size to carry fault
currents.
Effect of Grounding Metallic Shield
The metallic coverings of cables must be
grounded to provide satisfactory operating and safety conditions. As the method of
grounding may affect the current carrying capacity, formulas for calculating losses and
correcting the current carrying capacity for those losses may be found on pages 19 and 20
of Okonite's Engineering HandBook.
Installations of shielded single conductor
cables must be studied to determine the best method of grounding. This is necessary as
voltage is induced in the shield of a single conductor cable carrying alternating current
due to the mutual induction between its shield and any other conductors in its vicinity.
This induced voltage can result in two conditions:
1. Metal shields bonded or grounded at more
than one point have circulating currents flowing in them, the magnitude of which depends
on the mutual inductance to the other cables, the current in these conductors, and the
resistance of the shield. This circulating current does not depend on the length of the
cables nor the number of bonds, providing there are bonds at each end. The only effect of
this circulating current is to heat the shield and thereby reduce the effective current
carrying capacity of the cable. If the shield loss exceeds 5 percent or the copper loss,
the current carrying capacity should be reduced.
2. Shields bonded or grounded at only one
point will have a voltage built up along the shield. The magnitude depends on the mutual
inductance to other cables, the current in all the conductors, and the distance to the
grounded point. This voltage may cause discharge or create an unsafe condition for
workmen. The usual safe potential is about 25 volts for cables having nonmetallic covering
over the shield.
Multi-Grounded Shields
If operating conditions permit, it is
desirable to bond and ground cable shields at more than one point, to improve the
reliability and safety of the circuit. This decreases the reactance to fault currents and
increases the human safety factor.
Some general recommendations may be made,
but it must be remembered that variations in insulation thickness, conductivity of sheath,
spacing of conductors, and the current being carried all affect these recommendations. It
is impossible to cover all these variations.
The following single conductor cables
carrying alternating currents may, in general, be operated with multisheath grounds.
1. Shielded cables up to and including 250
kcmil with phases in separate ducts.
Cables in ac circuits should not be
installed with each phase in separate magnetic conduits under any circumstances due to the
high inductance under such conditions. Cables in a-c circuits should not be installed with
each phase in separate metallic non-magnetic conduit when their size exceeds 4/0 unless
the conduit is insulated to prevent circulating currents.
2. Shielded cables installed with all three
phases in the same duct.
3. Cables of any size may be installed with
multi-shield grounds, provided allowance is made for heating due to current induced in the
shield. Cables carrying direct current may always be solidly grounded at more than one
point, except where insulating joints are required to isolate earth currents or to permit
cathodic protection.
Shields Grounded at One Point
Shields of single conductor cable carrying
alternating current will have a potential buildup if grounded at only one point. The
table below gives the maximum lengths which should be allowed
between insulating joints in order to keep this potential below the maximum safe value of
25 volts.
They apply to cables operating at any 60 Hz
a-c voltage. Many conditions will permit longer lengths between insulating joints, as for
example, where cables are operating at less than full load.
The lengths given are from the grounded
point to the insulating joint. If the mid-point of the section is grounded, the total
length between insulating joints may be twice the length given.
Induced Shield Voltages, Currents and
Losses
The Okonite Engineering Handbook gives
formulas for calculating the induced voltage and shield loss for single conductor cables.
These formulas neglect proximity loss, but are accurate enough for practical purposes.
It is assumed that the cables are carrying
balanced currents.
For cables installed three per conduit use
arrangement II. The spacing S in this case will be equal to the outside diameter of the
cable increased by 20 percent to allow for random spacing in the conduit.
Maximum lengths for single conductor
cables with shields insulated at joints and terminals and grounded at end of each section
only.
These lengths are based on cables spaced on
7.5 centers operating at 75% load factor with ampacities given here for 15kV rated cables
for 1/C per duct and for ampacities given here for 3 x 1/C cables
per duct.
Size
Conductor |
One Phase
per duct (ft) |
Three Phases
per duct (ft) |
1/0......
4/0......
350......
500......
750......
1,000......
2,000...... |
1465......
1055......
820......
695......
595......
565......
420...... |
4965.......
3530.......
2610.......
2200.......
1800.......
.........
......... |
|