Voltage Rating
The selection of the cable insulation level to be used in a
particular installation shall be made on the basis of the applicable phase to phase
voltage and the general system category as outlined below:
100 Percent Level - Cables in this category may be
applied where system is provided with relay protection such that ground faults will be
cleared as rapidly as possible, but in any case within 1 minute. While these cables are
applicable to the great majority of cable installations which are on grounded systems,
they may be used also on other systems for which the application of cables is acceptable
**provided the above clearing requirements are met in completely de-energizing the faulted
section.
133 Percent Level - This insulation level
corresponds to that formerly designated for ungrounded systems. Cables in this category
may be applied in those situations where the clearing time requirements of the 100 percent
level category cannot be met, and yet there is adequate assurance that the faulted section
will be de-energized in a time not exceeding 1 hour. Also they may be used when additional
insulation strength over the 100 percent level category is desirable.
173 Percent Level - Cables in this category should
be applied on systems where the time required to de-energize a grounded section is
indefinite. Their use is recommended also for resonant grounded systems. Consult the
manufacturer for insulation thickness.
**In common with other electrical equipment, the use of
cables is not recommended on systems where the ratio of the zero to positive phase
reactance of the system at the point of cable application lies between -1 and -40 since
excessively high voltages may be encountered in the case of ground faults.
Electrical
formulas for determining amperes,
horsepower, kilowatts and kilovolt-amperes
|
DESIRED
DATA |
ALTERNATING
CURRENT |
DIRECT
CURRENT |
Single-Phase |
Two-Phase*
Four-Wire |
Three-Phase |
Amperes when
kva is shown |
kva
x 1000
E |
kva
x 1000
2 x E |
kva x 1000
1.73 x E |
kva x 1000
E |
Amperes when
kilowatts are shown |
kw x 1000
E x pf |
kw x 1000
2 x E x pf |
kw x
1000
1.73 x E x pf |
kw x 1000
E |
Amperes when
horsepower is shown |
hp x
746
E x %Eff x pf |
hp x 746
2 x E x %Eff x pf |
hp x 746
1.73 x E x %Eff x pf |
hp x 746
E x %Eff |
Kilovolt-Amperes |
I x E
1000 |
I x E x 2
1000 |
I x E x 1.73
1000 |
I x E
1000 |
Kilowatts |
I x E x pf
1000 |
I x E x 2 pf
1000 |
I x E x 1.73 x
pf
1000 |
I x E
1000 |
Horsepower |
I x E x %Eff x
pf
746 |
I x E x 2 x %Eff
x pf
746 |
I x E x 1.73 x
%Eff x pf
746 |
I x E x %Eff
746 |
*In three-wire, two phase balanced circuits,
the current in the common conductor is 1.41 times that in either of the other conductors.
E = volts Ø-Ø; I = amperes; % Eff = percent efficiency in
decimals; pf = power factor in decimals;
kva = kilovolt-ampere; hp = horsepower; kw = kilowatts
|