To determine effective 60-Hertz ac resistance, multiply dc resistance values
corrected for proper temperature, by the ac/dc resistance ratio given below.
These
apply to the following specific conditions.
Use Columns 1 and 2 for:
(a) Single-conductor non-metallic sheathed cables in air or non-metallic
conduit.
(b) Single-conductor metallic-sheathed cables with sheaths insulated
in air or
separate non-metallic conduits.
(c) Multiple-conductor non-metallic
sheathed cables in air or non-metallic
conduits.
Note: Columns 1 and 2 include skin effect only. For close spacing such
as
multi-conductor cables or several cables in the same conduit, there
will be an
additional apparent resistance due to proximity loss. This varies
with spacing
(insulation thickness) but for most purposes can be neglected without serious
error.
Use Column 3 for:
(a) Multiple-conductor metallic-sheathed cable.
(b) Multiple-conductor non-metallic
sheathed cables in metal conduit.
(c) Two or more single-conductor non-metallic
sheathed cables in same metallic
conduit.
|