A Bare Stranded Copper Conductor
B Okoseal Insulation
C Twisted Pairs/Triads
D Communication Wire
E Aluminum/Polyester Tape
F Tinned Stranded Copper Drain
Wire
G Rip Cord
H Black Okoseal Jacket
Specifications
Conductors: Bare soft annealed copper, Class B, 7-strand concentric
per ASTM B-8.
Insulation: Flame-retardant Okoseal (PVC) per UL 13 and 2250, 15
mils nominal thickness, 105°C
temperature rating.
Conductor Identification: Pigmented black and white in pairs,
black, red and white in triads; white conductor numerically printed for
group identification.
Conductor Identification: Pigmented black and white in Paris,
black, red and white in triads white conductor numerically printed for
group identification.
Communications Wire: 22 AWG, solid, bare copper conductor, 12 mils
nominal flame-retardant Okoseal insulation, 105°C
rating.
Assembly: Pairs or triads assembled with left-hand lay.
Flame-retardant, non-wicking fillers included where required to provide a
round cable.
Cable Shield: Aluminum/Polyester tape overlapped to provide 100%
coverage, and a 7-strand tinned copper drain wire, same size as conductor.
Jacket: Black, flame-retardant, low temperature Okoseal per UL 13
and 2250. A rip cord is laid longitudinally under the jacket to facilitate
removal.
Classifications: UL Listed as ITC/PLTC - Instrument Tray
Cable/Power Limited Tray Cable for use in accordance with Article 727 and
Article 725 of the National Electrical Code.
Cables comply with UL 2250 and UL 13 for PLTC, CL2 and CL3.
Applications
Okonite Type P-OS (Pairs/triads - Overall Shield) instrumentation
cables are designed for use as instrumentation, process control in ITC
non-classified or labeled circuits up to 150 volts and 5 amps (750VA) and
in Class 2 or 3 Power-Limited circuits where shielding against external
interference is required, but shielding against interference among groups
is not required; indoors or outdoors in wet or dry locations with
conductor operating temperatures up to 105°C;
in cable trays; in raceways; supported by a messenger wire; under raised
floors; for direct burial. Suitable Class I, Division 2, Class II,
Division 2, or Class III, Division 2 hazardous locations. Also for use as
Power-Limited fire protective signaling cable (FPL) per NEC Code 7760.
The overall shield eliminates most of the static interference from the
electric field radiated by power cables and other electrical equipment.
For dc service in wet locations X-Olene®
insulation is recommended.
Product Features
- Passes the UL 1581 and IEEE 383-1974 vertical tray flame tests.
- Passes IEEE 1202-1991 vertical tray flame test (2 Pr #18 & larger).
- Sunlight & oil resistant.
- UL listed for direct burial (4/C #20 AWG or 2/C #18 and larger).
- Individual pairs or triads are numbered and color coded for
simplified hook-up.
- Good external noise rejection.
- Excellent weathering characteristics.
- OSHA Acceptable.
- Flexible, easy to handle, splice and terminate.
- 100% shield coverage for reduced electromagnetic noise pick-up.
- Communication wire included in each cable for voice communication
during installation or instrument calibration.
- Suitable for low temperature installation of -40°C.
|