A Bare Stranded Copper Conductor
B Okoseal Insulation
C Twisted Pairs/Triads
D Aluminum/Synthetic Polymer Backed
Tape
E Tinned Stranded Copper Drain
Wire
F Rip Cord
G Inner Black Okoseal Jacket
H Galvanized Steel Interlocking Armor
(Loxarmor)
J Outer Black Okoseal Jacket
Specifications
Conductors: Bare soft annealed copper, Class B, 7-strand concentric
per ASTM B-8.
Insulation: Flame-retardant Okoseal (PVC) per UL Standard 13 and
2250, 15 mils nominal thickness, 105°C
temperature rating.
Conductor Identification: Pigmented black and white in pairs,
black, red and white in triads; white conductor numerically printed for
group identification.
Assembly: Pairs or triads assembled with left-hand lay.
Flame-retardant, non-wicking fillers included where required to provide a
round cable.
Cable Shield: Aluminum/synthetic polymer tape overlapped to provide
100% coverage, and a 7-strand tinned copper drain wire, same size as
conductor.
Inner Jacket: Black, flame-retardant, low temperature Okoseal per
UL Standard 13 and 2250. A rip cord is laid longitudinally under the
jacket to facilitate removal.
Loxarmor Sheath: An interlocking, galvanized steel armor provides
mechanical protection against cut-through and crushing. All four sides of
the steel tape are galvanized to prevent corrosion.
Outer Jacket: Black, flame-retardant, low temperature Okoseal per
UL Standard 13 and 2250.
Classifications: UL Listed as ITC/PLTC - Instrument Tray
Cable/Power Limited Tray Cable for use in accordance with Article 727 and
Article 725 of the National Electrical Code.
These Cables comply with UL Standard 2250 and UL Standard 13 for PLTC, CL2
and CL3.
Applications
Okonite Loxarmor Type P-OS (Pair/triads - Overall Shield) instrumentation
cables are designed for use as instrumentation, process control in ITC
non-classified or labeled circuits up to 150 volts and 5 amps (750VA) and
in Class 2 or 3 Power-Limited circuits where shielding
against external interference is required, but shielding against
interference among groups is not required; indoors or outdoors; in wet or
dry locations with conductor operating temperatures up to 105°C;
in cable trays; in raceways; supported by a messenger wire; under raised
floors; for direct burial. Suitable in Class I, Division 2, Class II,
Division 2, or Class III, Division 2 hazardous locations. Also for use as
Power-Limited fire protective signaling cable (FPL) per NEC Code 760. The
Loxarmor (interlocked steel) sheath provides physical protection against
mechanical damage. It may be installed in both exposed and concealed work,
secured
to supports not greater than 6 feet apart.
The overall shield eliminates most of the static interference from the
electric field radiated by power cables and other electrical equipment.
For dc service in wet locations X-Olene insulation is recommended.
Product Features
- Passes the UL 13 & IEEE 383-1974 vertical tray flame tests.
- Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520
and the 210,000 BTU/hr corner configuration test.
- UL listed as sunlight resistant.
- Complete pre-packaged, factory-tested wiring system color coded.
- Loxarmor cables are quality control inspected to meet or exceed
applicable UL Standards.
- Loxarmor enclosure permits installation in cable tray containing
light and power cables without a barrier separator.
- Excellent noise rejection.
- Impervious, continuous sheath excludes moisture, gases and liquids.
- Excellent compression and impact resistance.
- Lower installed system cost than conduit or EMT systems.
- OSHA Acceptable.
- Also available in aluminum Loxarmor.
- Suitable for low temperature installation of -40°C.
|