A Bare Stranded Copper
Conductor
B X-olene Insulation
C Tinned Stranded Copper group
Drain Wire
D Aluminum/Polyester Tape
E Twisted Shielded Pairs/Triads
F Communication Wire
G Aluminum/Polyester Tape
H Tinned Stranded Copper Drain
Wire
J Rip Cord
K Inner Black Okoseal Jacket
L Impervious, Continuous Corrugated
Aluminum C-L-X Sheath
M Outer Black Okoseal Jacket
Specifications
Conductors: Bare soft annealed copper, Class B, 7-strand concentric
per ASTM B-8.
Insulation: X-Olene (XLP) per UL 13 and UL Standard 2250, 15 mils
nominal thickness, 90°C temperature
rating.
Conductor Identification: Pigmented black and white in pairs,
black, red and white in triads; white conductor numerically printed for
group identification.
Group Shield: Aluminum/Polyester tape overlapped to provide 100%
coverage, and a 7-strand tinned copper drain wire, two sizes smaller than
the conductor. All group shields are completely isolated from each other.
Communications Wire: 20 AWG, solid bare copper conductor, 15 mils
nominal X-Olene insulation, 90°C
temperature rating.
Assembly: Pairs or triads assembled with left-hand lay. Fillers
included where required to provide a round cable.
Cable Shield: Aluminum/Polyester tape overlapped to provide 100%
coverage, and a 7-strand tinned copper drain wire, same size as the
conductor.
Inner Jacket: Black, flame-retardant, low temperature Okoseal (PVC)
per UL 13 and UL Standard 2250. A rip cord is laid longitudinally under
the jacket to facilitate removal.
C-L-X Sheath: A close-fitting, impervious, continuously welded and
corrugated aluminum sheath provides complete protection against moisture,
liquids, and gases, has excellent mechanical strength and provides
equipment grounding through the sheath.
Outer Jacket: Black, flame-retardant, low temperature Okoseal per
UL 13 and UL Standard 2250.
Classifications
UL Listed as ITC/PLTC Instrument Tray Cable/Power Limited Tray Cable for
use in accordance with Article 727 and Article 725 of the National
Electrical Code.
These cables comply with UL Standard 2250 and UL 13 for PLTC, CL2 and CL3.
Applications
Okonite Type C-L-X SP-OS (Pair/Triad - Individual and Overall
Shield) instrumentation cables are designed for use as instrumentation,
process control, and computer cables in ITC non-classified or labeled
circuits up to 150 volts and 5 amps (750VA) and in Class 2 or 3
Power-Limited circuits where maximum shielding against external
interference is required, as well as shielding among groups, particularly
where the cable may be subject to abnormally high current or voltage
interference; indoors or outdoors; in wet or dry locations; in cable
trays; in raceways; supported by a messenger wire; under raised floors;
for direct burial. Suitable Class I, Division 2, Class II, Division 2, or
Class III, Division 2 and Class I, Zone 2 hazardous locations. Also for use as Power-Limited
fire protective signaling cable (FPL) per NEC Code 760. The C-L-X sheath
provides physical protection against mechanical damage. It maybe installed
in both exposed and concealed work, secured to supports not greater than 6
feet apart.
Product Features
- Passes the UL 1581, IEEE 383-1974, & IEEE 1202-1991 vertical tray
flame tests.
- Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520
and the 210,000 BTU/hr corner configuration test.
- Recommended for dc applications in wet environments.
- UL listed for direct burial.
- C-L-X enclosure permits installation in cable tray containing light
and power cables without a barrier separator.
- Impervious, continuous sheath excludes moisture, gasses and liquids.
- C-L-X sheath exceeds equipment grounding conductor requirements of
NEC Article 250.
- Excellent compression and impact resistance.
- Meets API Standards 14F and 14FZ.
- Lower installed system cost than conduit or EMT systems.
- UL listed as Marine Shipboard cable.
- Listed by American Bureau of Shipping (ABS) as CWCMC-PLTC and
CWCMC-ITC.
- Recognized by US Coast Guard as Type MC or CWCMC.
- Suitable for low temperature installation to -40°C.
|