THE OKONITE COMPANY
Product Data
Section 5: Sheet
44

printer friendly version (PDF)


Okonite® FMR-N® X-Olene® FMR®
600 Volt Instrumentation Cable
Shielded Pairs or Triads - Overall Shield Type SP-OS 90°C Rating
For Class 1E Nuclear Plant Use
 


A
  Stranded Tinned Copper Conductors

B  Okonite FMR-N Insulation

C  Tinned Copper Drain Wire

D  Copper/Polyester Shield Tape

E  Polyester Tape (as needed)

F  Tinned Copper Drain Wire

G  Copper/Polyester/Nomex Shield Tape

H  Rip Cord

J   X-Olene FMR Jacket


Insulation
Okonite FMR-N is Okonite’s trade name for its heat, moisture, flame and chemically resistant, mechanically rugged nuclear plant qualified ethylene-propylene insulation compound. Its physical properties and flame retardency permit its use without a jacket on the single conductors.
The properties of Okonite FMR-N insulation substantially enhance the well known features of ethylene propylene rubber insulations.
Nuclear qualified Okonite FMR-N cables meet IEEE Standard - 383 LOCA and flame test criteria.

Overall Jacket
The overall jacket is a cross-linked polyethylene compound. This combination construction assures circuit security because of its high mechanical strength and excellent resistance to moisture, ozone, oil and many chemicals.

Applications
Okonite FMR-N Instrumentation Cables are recommended for use in power generating plants and in substations; designed especially for critical circuits where continuity of service is of prime importance. This premium quality instrumentation cable is recommended for wet or dry, ac or dc service at conductor temperatures to 90°C. They may be installed in conduits, ducts, cable troughs, trays, messenger supported, or directly buried in the earth.

Specifications
Conductors: Tinned copper per ASTM B-33, Class B stranded per ASTM B-8.

Insulation: Okonite FMR-N meets or exceeds the electrical and physical requirements of ICEA S-73-532.

Conductor Identification: Pigmented black and white in pairs, black, white and red in triads; white conductor numerically printed for group identification.

Group Shield: Copper/polyester tape overlapped to provide 100% coverage, and a 7-strand tin coated copper drain wire, two sizes smaller than the conductor. All group shields are completely isolated from each other.

Assembly: Pairs or triads assembled with left-hand lay. Flame-retardant, non-wicking fillers included where required to provide a round cable.

Cable Shield: Copper/Polyester/Nomex tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, same size as conductor.

Overall Jacket: The X-Olene FMR compound meets or exceeds the requirements of thermoset jackets given in ICEA S-73-532.

Product Features

  • Qualified as Class 1E cable.
  • Flame retardant - passes the IEEE 383 and 1202 flame test requirements.
  • Quality Assurance traceability.
  • 90°C rated control cable, factory assembled for indoor or outdoor installation in cable trays, in raceways, direct burial in the earth, or supported by messenger wire.
  • Individual units are completely isolated for maximum noise rejection.
  • Mechanically rugged.
  • Color coded conductors.
  • Resistant to water, oil and many chemicals.
  • Thermally stable at elevated temperatures.
  • High insulation resistance, even at elevated temperatures.
  • Small diameter, lightweight.

1-Catalog Number
2-Size AWG Strands
3-Number of Pairs
4-Number of Triads
5-Jacket Thickness - mils
6-Nominal Cable O.D. - In.
7-Cross-Sectional Area (sq. in.)
8-Approx Net Weight (lbs/1000’)
9-Approx Ship Weight (lbs/1000’)

 
Okonite FMR-N Insulation—25 mils
1 2 3 4 5 6 7 8 9

268-16-2302

18 (7x)

2

 

45

0.48

0.18

128

151

268-16-2304
268-16-2308
268-16-2312

4
8
12

 

60
60
80

0.67
0.80
0.95

0.35
0.50
0.71

192
330
486

231
369
550

268-16-2316
268-16-2320
268-16-2324

16
20
24

 

80
80
80

1.08
1.18
1.42

0.92
1.09
1.58

608
721
954

688
801
1097

268-17-2302
268-17-2304

 

2
4

45
60

0.54
0.70

0.23
0.38

153
260

177
299

268-17-2308
268-17-2312
268-17-2316

 

8
12
16

80
80
80

0.90
1.09
1.12

0.64
0.93
0.99

453
625
770

517
705
850

268-17-2320
268-17-2324

 

20
24

80
80

1.25
1.49

1.23
1.74

975
1217

1081
1360

268-16-2402
268-16-2404

16 (7x)

2
4

 

45
60

0.53
0.66

0.22
0.34

152
253

175
292

268-16-2408
 268-16-2412
268-16-2416

8
12
16

 

60
80
80

0.84
1.05
1.21

0.55
0.87
1.15

410
609
772

474
673
852

268-16-2420
268-16-2424

20
24

 

80
80

1.30
1.37

1.33
1.47

966
1175 

1072
1281

268-17-2402
268-17-2404

 

2
4

60
60

0.61
0.72

0.29
0.41

208
348

232
387

268-17-2408
268-17-2412
268-17-2416

 

8
12
16

80
80
80

1.01
1.20
1.34

0.80
1.13
1.41

574
801
1011

638
881
1117

268-17-2420
268-17-2424

 

20
24

80
80

1.47
1.58

1.70
1.96

1269
1549

1412
1692

 


ELECTRICAL CHARACTERISTICS 
Conductor Resistance, nominal ohms/1000 ft. @20°C 
18 AWG...........................................6.92 
16 AWG...........................................4.35 
Insulation Resistance Constant                                      
@60°F, minimum................20,000 Megohms-1000 ft. 
Loop Resistance, nominal (2 conductor)                       
ohms-1000 ft @20°C                                                   
18 AWG...........................................14.0 
16 AWG.............................................8.7 
Mutual Capacitance (PF/ft.), nominal                            
1 Pr #18 AWG....................................25 
1 Pr #16 AWG....................................29 

 

A\06100544