THE OKONITE COMPANY
Product Data
Section 5: Sheet
43

printer friendly version (PDF)


Okonite® FMR-N® X-Olene® FMR®
600 Volt Instrumentation Cable
Pairs or Triads - Overall Shield Type P-OS 90°C Rating
For Class 1E Nuclear Plant Use
 



A
  Stranded Tinned Copper Conductors

B  Okonite FMR-N Insulation

C  Twisted Pair/Triad

D  Polyester Tape (as needed)

E  Tinned Copper Drain Wire

F  Copper/Polyester/Nomex Shield Tape

G  Rip Cord

H  X-Olene FMR Jacket


Insulation
Okonite FMR-N is Okonite’s trade name for its heat, moisture, flame and chemically resistant, mechanically rugged nuclear plant qualified ethylene-propylene insulation compound. Its physical properties and flame retardency permit its use without a jacket on the single conductors.
The properties of Okonite FMR-N insulation substantially enhance the well known features of ethylene propylene rubber insulations.
Nuclear qualified Okonite FMR-N cables meet IEEE Standard - 383 LOCA and flame test criteria.

Overall Jacket
The overall jacket is a cross-linked polyethylene compound. This combination construction assures circuit security because of its high mechanical strength and excellent resistance to moisture, ozone, oil and many chemicals.

Applications
Okonite FMR-N Instrumentation Cables are recommended for use in power generating plants and in substations; designed especially for critical circuits where continuity of service is of prime importance. This premium quality instrumentation cable is recommended for wet or dry, ac or dc service at conductor temperatures to 90°C. They may be installed in conduits, ducts, cable troughs, trays, messenger supported, or directly buried in the earth.

Specifications
Conductors: Tinned copper per ASTM B-33, Class B stranded per ASTM B-8.

Insulation: Okonite FMR-N meets or exceeds the electrical and physical requirements of ICEA S-73-532.

Conductor Identification: Pigmented black and white in pairs, black, white and red in triads; white conductor numerically printed for group identification.

Assembly: Pairs or triads assembled with left-hand lay. Flame-retardant, non-wicking fillers included where required to provide a round cable.

Cable Shield: Copper/Polyester/Nomex tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, same size as conductor.

Overall Jacket: The X-Olene FMR compound meets or exceeds the requirements of thermoset jackets given in ICEA S-73-532. 

Product Features

  • Qualified as Class 1E cable.
  • Flame retardant - passes the IEEE 383 and 1202 flame test requirements.
  • Quality Assurance traceability.
  • 90°C rated control cable, factory assembled for indoor or outdoor installation in cable trays, in raceways, direct burial in the earth, or supported by messenger wire.
  • Mechanically rugged.
  • Color coded conductors.
  • Resistant to water, oil and many chemicals.
  • Thermally stable at elevated temperatures.
  • High insulation resistance, even at elevated temperatures.
  • Small diameter, lightweight.

1-Catalog Number
2-Size AWG Strands
3-Number of Pairs
4-Number of Triads
5-Jacket Thickness - mils
6-Nominal Cable O.D. - In.
7-Cross-Sectional Area (sq. in.)
8-Approx Net Weight (lbs/1000’)
9-Approx Ship Weight (lbs/1000’)

 
Okonite FMR-N Insulation—25 mils
1 2 3 4 5 6 7 8 9

267-16-2301
267-16-2302

18 (7x) 

1
2

 

45
45

0.31
0.42

0.08
0.14

49
98

60
121

267-16-2304
267-16-2308
267-16-2312

4
8
12

 

60
60
80

0.60
0.73
0.87

0.28
0.42
0.59

152
275
380

176
313
443

267-16-2316
267-16-2320
267-16-2324

16
20
24

 

80
80
80

0.98
1.09
1.17

0.75
0.93
1.08

469
585
722

533
664
802

267-17-2301
267-17-2302
267-17-2304

 

1
2
4

45
45
60

0.32
0.45
0.66

0.08
0.16
0.34

60
127
223

71
150
262

267-17-2308
267-17-2312
267-17-2316

 

8
12
16

60
80
80

0.86
1.08
1.20

0.58
0.92
1.13

352
527
654

416
607
734

267-17-2320
267-17-2324

 

20
24

80
80

1.33
1.46

1.39
1.67

826
1014

932
1120

267-16-2401
267-16-2402
267-16-2404

16 (7x) 

1
2
4

 

45
45
60

0.33
0.44
0.58

0.09
0.15
0.26

62
125
208

73
148
232

267-16-2408
267-16-2412
267-16-2416

8
12
16

 

60
80
80

0.77
0.97
1.05

0.47
0.74
0.87

335
492
608

374
556
688

267-16-2421
267-16-2424

20
24

 

80
80

1.18
1.29

1.09
1.31

774
960

854
1065

267-17-2401
267-17-2402
267-17-2404

 

1
2
4

45
60
60

0.35
0.63
0.73

0.10
0.31
0.42

77
194
281

88
218
319

267-17-2408
267-17-2412
267-17-2416

 

8
12
16

80
80
80

0.98
1.19
1.32

0.75
1.11
1.37

503
698
870

567
778
976

267-17-2420
267-17-2424

 

20
24

80
80

1.47
1.62

1.70
2.06

1098
1355

1204
1497

 


ELECTRICAL CHARACTERISTICS 
Conductor Resistance, nominal ohms/1000 ft. @20°C 
18 AWG...........................................6.92 
16 AWG...........................................4.35 
Insulation Resistance Constant                                      
@60°F, minimum................20,000 Megohms-1000 ft. 
Loop Resistance, nominal (2 conductor)                       
ohms-1000 ft @20°C                                                   
18 AWG...........................................14.0 
16 AWG.............................................8.7 
Mutual Capacitance (PF/ft.), nominal                            
1 Pr #18 AWG....................................25 
1 Pr #16 AWG....................................29 

 

A\06100543
BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS