THE OKONITE COMPANY
Product Data
Section 5: Sheet
42
C-L-X® Okoseal-N® SP-OS
Type MC-HL Armored Class 1 Instrumentation Cable
Multiple Shielded Pairs or Triads - Individual and Overall Shield
600 Volts 90°C Rating,
For Cable Tray Use-Sunlight Resistant-For Direct Burial
UL 

A  Bare Stranded Copper Conductor

B  Okoseal Insulation/Nylon Jacket

C  Tinned Stranded Copper Group Drain Wire

D  Aluminum/Polyester Tape

E  Twisted, Shielded Pairs/Triads

F  Tinned Stranded Copper Drain Wire

G  Aluminum/Polyester Tape

H  Rip Cord

Inner Black Okoseal Jacket

K  Impervious, Continuous, Corrugated Aluminum C-L-X Sheath

L  Outer Black Okoseal Jacket


Specifications
Conductors: Bare soft annealed copper, Class B, 7-strand concentric per ASTM B-8.

Insulation: Flame-retardant Okoseal (PVC) per UL 83, 15 mils nominal thickness, 90°C temperature rating.

Insulation Jacket: Nylon per UL 83, 4 mils nominal thickness.

Conductor Identification: Pigmented black and white in pairs, black, white and red in triads.

Group Shield: Aluminum polyester tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, two sizes smaller than the conductor. All group shields are completely isolated from each other.

Assembly: Pairs or triads assembled with left-hand lay. Non-wicking fillers included where required to provide a round cable.

Cable Shield: Aluminum/polyester tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, same size as conductor.

Inner Jacket: Black, flame-retardant Okoseal per UL Standard 1569. A rip cord is laid longitudinally under the jacket to facilitate removal.

C-L-X Sheath: A close-fitting, impervious, continuously welded and corrugated, aluminum sheath meeting UL 1569 provides complete protection against moisture, liquids, and gases, has excellent mechanical strength, and provides equipment grounding through the sheath.

Outer Jacket: Black, flame-retardant Okoseal per UL Standard 1569.

Classifications: UL Listed as Type MC-HL Articles 501, 502, and 503 of the National Electrical Code.

Applications
Okonite C-L-X type SP-OS (shielded pairs or triads - overall shield) instrumentation cables are designed for use on Class 1 Remote-Control Signaling circuits or where a 600V cable is desired, as instrumentation, process control, or computer cable transmitting signals at levels above 100 mili-volts in circuits where maximum noise protection is required. Protection from interference among groups as well as external sources is provided by individual group shields as well as an overall cable shield. For use indoors or outdoors; wet or dry locations; in cable trays’ in raceways; supported by a messenger wire; for direct burial; in Classes I, II, and III, Divisions 1 and 2 and Class I, Zone 1 and 2 hazardous locations per NEC Articles 501, 502,503 and 505. For use as non-power limited fire protective signaling cable (NPLF) per NEC Code 760.
The isolated individual shields over each pair, when properly grounded, prevent crosstalk or capacitive coupling between adjacent pairs which occurs with ac signals, particularly the pulse type.
The overall shield eliminates most of the static interference from the electric field radiated by power cables and other electrical equipment.
The C-L-X sheath provides physical protection against mechanical damage as required in NEC Section 725-8 as well as complete protection against moisture or gases entering the cable.
For dc service in wet locations, X-Olene insulation is recommended.

Product Features

  • UL listed for cable tray use, direct burial and sunlight resistant.
  • Passes the IEEE 383-1974 and IEEE 1202-1991 vertical tray flame tests.
  • Passes the 210,000 BTU Vertical Tray Flame Test utilizing the corner configuration and the ICEA T-29-520 Vertical Tray Flame Test.
  • C-L-X enclosure permits installation in cable tray containing light and power cables without a barrier separator.
  • Individual pairs or triads are numbered and color coded for simplified hook-up.
  • Individual units are completely isolated for maximum noise rejection.
  • Impervious, continuous sheath excludes moisture, gases and liquids.
  • C-L-X sheath exceeds equipment grounding conductor requirements of NEC Article 250.
  • Excellent compression and impact resistance.
  • Lower installed system cost than conduit or EMT systems.
  • OSHA Acceptable.
  • Complies with NEC Articles 501, 502 & 503 for hazardous locations.
  • UL listed as Type MC-HL and Marine Shipboard cable.
  • American Bureau of Shipping listed as CWCMC Type MC-HL.
  • Recognized by US Coast Guard as Type MC and CWCMC.
  • Suitable for low temperature installation to -40°C.
  • Meets API Standards 14 F and 14FZ.

#16 AWG - Multi Pair & Triad (SP-OS) Type MC-HL
 1-Catalog Number
 2-Number of Pairs
 3-Number of Triads
 4-Inner Jacket Thickness - mils
 5-Core O.D. Nominal - Inches
 6-C-L-X O.D. - Inches
  7-Outer Jacket mils
  8-Nominal Cable O.D. - Inches
  9-Cross-Sectional Area * Sq. In.
 10-Net Weight Lbs./1000’
 11-Ship Weight Lbs./1000’
1 2 3 4 5 6 7 8 9 10 11

561-60-3402
561-60-3404
561-60-3406

2
4
6

 

50
50
50

.45
.56
.66

.67
.80
.89

50
50
50

.78
.91
1.00

0.48
0.65
0.79

234
335
421

314
415
501

561-60-3408
561-60-3410
561-60-3412

8
10
12

 

50
50
50

.70
.79
.85

.93
1.06
1.11

50
50
50

1.04
1.17
1.22

 0.85
1.08
1.17

492
601
674

572
681
780

561-60-3416
561-60-3420
561-60-3424

16
20
24

 

50
50
50

.98
1.06
1.12

1.23
1.34
1.42

50
50
50

1.40
1.45
1.53

1.54
1.65
1.84

842
977
1118

948
1120
1261

561-60-3436
561-60-3450

36
50

 

60
60

1.37
1.57

1.64
1.92

60
60

1.82
2.05

2.60
3.30

1586
2124

1773
2416 

561-65-3404
561-65-3408
561-65-3412

 

4
8
12

50
50
50

.61
.82
.98

.84
1.06
1.24

50
50
50

.95
1.17
1.35

0.71
1.08
1.54

395
637
863

475
717
969

561-65-3416
561-65-3424
561-65-3436

 

16
24
36

50
50
50

1.10
1.30
1.58

1.37
1.60
1.96

50
60
60

1.48
1.73
2.09

1.72
2.35
3.43

1058
1485
2141

1201
1672
2426

Authorized Stock Item: Available from our Customer Service Centers.

* Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 392.9.

Jackets:  Optional jacket types available - consult local sales office.

Copper or bronze  C-L-X available on special order.

To order C-L-X Type SP-OS without the outer Okoseal jacket (not “HL” listed), change the sixth digit of the catalog number from 3 to 1, for example to order 1 pr. 20 AWG with a bare aluminum C-L-X, the catalog number would be 564-10-1212.

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ±15%.


ELECTRICAL SPECIFICATIONS 

Conductor Resistance, nominal..............................ohms/1000 ft. @20°C 
16 AWG......................................................................4.1                   
Insulation Test Voltage (spark test)...................................6000 Volts ac   
Dielectric Test Voltage...................................2000 Volts ac for 60 sec.    
Insulation Resistance Constant @60°F minimum                                        
(natural material typical value).....2000 Megohms-1000 ft.                     
Loop Resistance, nominal (2 conductor)..............ohms-1000 ft @20°C     
16 AWG....................................................................8.2                     
Mutual Capacitance (PF/ft.)*                                                                     
#16..............................................................................60                     
*Typical Value                                                                                           
E/08010542
BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |