THE OKONITE COMPANY
Product Data
Section 5: Sheet
32

Okozel®-Okozel Type P-OS
Type ITC/PLTC Instrumentation Cable
Single Pair, Triad, or Quad - Overall Shield
300 Volts - 150°C Rating
For Cable Tray Use
UL 

A  Bare Stranded Copper Conductor

B  Okozel Insulation

C  Twisted Pair/Triad/Quad

D  Aluminum-Nylon-Polyester Cable Shield

E  Tinned Stranded Copper Drain Wire

F  Black Okozel Jacket


Insulation and Jacket
Okozel is Okonite's trade name for ETFE Fluoropolymer, a modified Ethylene Tetrafluoroethylene. Okozel is extremely rugged with excellent resistance to cut-through and abrasion. It is chemically inert. Okozel is flame-retardant and non-propagating, passes the IEEE 383 vertical tray flame test, and is rated non-burning under ASTM D635. It is rated for 150°C (302°F) conductor operating temperature for continuous use (90°C within the containment area) and retains all useful physical properties at temperatures down to -100°C (-148°F). Okozel is a radiation resistant dielectric and meets or exceeds all requirements of IEEE Standards 383 and 323.

Specifications
Conductors: Bare soft annealed copper, Class B, 7-strand concentric per ASTM B-8.

Insulation: Flame-retardant, radiation-resistant Okozel, a modified ETFE fluoropolymer. Exceeds requirements for UL Standard 13 and UL 2250.

Conductor Identification: Pigmented black, red, blue and yellow.

Assembly: Conductors assembled with left-hand lay.

Cable Shield: Aluminum-nylon-polyester tape overlapped to provide 100% coverage, and a 7-strand coated copper drain wire, same size as conductor.

Jacket: Black, heavy duty, flame-retardant, radiation, oil, fuel, and chemical-resistant Okozel.
Cable meets or exceeds the requirements of UL Standard 13 and 2250, NEMA HP-100 IEEE Std. 383, Type Test of Class IE Electric Cables for Nuclear Power Generating Stations and is rated non-burning under ASTM D635.

Classification: UL Listed as ITC/PLTC - Instrument Tray Cable/Power Limited Tray Cable for use in accordance with Article 727 and Article 725 of the National Electrical Code.

The cables comply with UL 2250 and UL Standard 13 for PLTC, CL2 and CL3.

Applications
Okonite Okozel Type P-OS (Pair/triad - Overall Shield) instrumentation cables are recommended for use in either nuclear powered or fossil fueled generating stations where continuity of critical control circuits is of primary importance. Designed for use as instrumentation, process control, and computer cables in ITC non-classified or labeled circuits
up to 150 volts and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits where shielding against external interference is required, but shielding against interference among groups is not required; indoors or outdoors; in wet or dry locations with conductor operating temperatures up to 150°C; in cable trays; in raceways; supported by a messenger wire; under raised floors; for direct burial. Suitable Class I, Division 2; Class II, Division 2; or Class III, Division 2 hazardous locations. Also for use as Power-Limited fire protective signaling cable (FPL) per NEC Code 760.

Okozel instrumentation cables are also recommended for high ambient temperature areas up to 150°C (302°F) in industrial applications or for cold weather installations in excess of -65°C
(-85°F).

Product Features

  • 100% shield coverage for reduced electrostatic noise.
  • Twisted to reduce electromagnetic pick-up.
  • Good noise rejection.
  • Outstanding nuclear radiation resistance when exposed to LOCA conditions.
  • Low surface friction provides easier installation.
  • Smaller and lighter diameter permits more cables per tray.
  • 150°C continuous operating temperature, 90°C in containment area.
  • Cold installation temperature in excess of -65°C.
  • Exceptional abrasion resistance will not cut or tear.
  • Flame-retardant and non-propagating. Passes IEEE 383 and UL Vertical Tray Flame Tests.
  • Low smoke emission.
  • Chemically inert - unaffected by typical acids, bases, solvents and cleaning agents, fuels and hydraulic fluids.
  • High dielectric strength.
  • Low dielectric constant.
  • Qualified for nuclear generating stations, Class IE, 90°C rated. See Okonite Sales for heavier walls needed for nuclear qualified cable.

 1-Catalog Number
 2-Conductor Size- AWG (Strands)
 3-Number of Pairs
 
4-Number of Triads
 5-Number of Quads
  6-Insulation Thickness - (mils)
  7-Jacket Thickness-(mils)

  8-Nominal Cable O.D. - (In.)
  9-Approx Net Weight (lbs/1000’)
10-Approx Ship Weight (lbs/1000’)
1 2 3 4 5 6 7 8 9 10

264-40-3301
264-45-3301
264-50-3301

18(7X)

1


1



1

9

15

0.20
0.21
0.23

29
37
46

34
42
51

264-40-4401
264-45-4401
264-50-4401

16(7X)

1


1



1

9

15

0.22
0.24
0.26

40
52
64

45
57
69

264-40-5501
264-45-5501
264-50-5501

14(7X)

1


1



1

12

15

0.25
0.27
0.29

57
74
92

62
79
97

264-40-6601

12(7X)

1

.

.

12

15

0.29

83

88

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ±15%.
 

ELECTRICAL SPECIFICATIONS
Per UL Standards 13 and 2250

Conductor Resistance, maximum..........ohms/1000 ft. @20°C      @25°C
18 AWG.................................................................6.90...........7.04    
16 AWG.................................................................4.34.......... 4.43    
14 AWG.................................................................2.72...........2.78    
12 AWG.................................................................1.71 ..........1.75    
Insulation Test Voltage (spark test)..............5000 volts ac                          
Dielectric Test Voltage.......................1500 volts ac for 15 sec.                  
Insulation Resistance Constant @60°F minimum                                         
(natural material typical value)............50,000 Megohms-1000 ft.                 
Loop Resistance, maximum (2 cdr.)......ohms-1000 ft @20°C      @25°C
18 AWG...............................................................13.80.........14.08   
16 AWG.................................................................8.68...........8.86   
14 AWG.................................................................5.44...........5.56   
12 AWG.................................................................3.42...........3.50   
B/01100532
BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |