A Bare Stranded Copper Conductor
B Okoseal Insulation
C Twisted Pair/Triad
D
Aluminum/Polyester Tape
E Tinned Stranded Copper Drain
Wire
F Rip Cord
G Inner Black Okoseal Jacket
H
Impervious, Continuous Corrugated Aluminum C-L-X Sheath
J
Outer Black Okoseal Jacket
Specifications
Conductors: Bare soft annealed copper, Class B, 7-strand concentric
per ASTM B-8.
Insulation: Flame-retardant Okoseal (PVC) per UL Standard 13 and UL
2250, 15 mils nominal thickness, 105°C temperature rating.
Conductor Identification: Pigmented black and white in pairs,
black, red and white in triads.
Assembly: Pair or triad assembled with left-hand lay.
Cable Shield: Aluminum/Polyester tape overlapped to provide 100%
coverage, and a 7 strand tinned copper drain wire, same size as conductor.
Inner Jacket: Black, flame-retardant Okoseal per UL 13 and UL
Standard 2250. A rip cord is laid longitudinally under the jacket to
facilitate removal.
C-L-X Sheath: A close-fitting, impervious, continuously welded and
corrugated aluminum sheath provides complete protection against moisture,
liquids, and gases, has excellent mechanical strength and provides
equipment grounding through the sheath.
Outer Jacket: Black, flame-retardant Okoseal per UL 13 and UL
Standard 2250.
Classifications
UL Listed as ITC/PLTC Instrument Tray Cable/Power Limited Tray Cable for
use in accordance with Article 727 and Article 725 of the National
Electrical Code.
These cables comply with UL 2250 and UL 13 for PLTC, CL2 and CL3.
Applications
Okonite Type C-L-X P-OS (Pair/Triad - Overall Shield) instrumentation
cables are designed for use as instrumentation, process control, and
computer cables in ITC non-classified or labeled circuits up to 150 volts
and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits where
shielding against external interference is required, but shielding against
interference among groups is not required; indoors or outdoors; in wet or
dry locations with conductor operating temperatures up to 105°C;
in cable trays; in raceways; supported by a messenger wire; under raised
floors; for direct burial. Suitable Class I, Division 2, Class II,
Division 2, or Class III, Division 2 and Class I, Zone 2 hazardous locations. Also for use as
Power-Limited fire protective signaling cable (FPL) per NEC Code 760. The
C-L-X sheath provides physical protection against mechanical damage. It
may be installed in both exposed and concealed
work, secured to supports not greater than 6 feet apart.
The overall shield eliminates most of the static interference from the
electric field radiated by power cables and other electrical equipment.
For dc service in wet locations, X-Olene insulation is recommended.
Product Features
- Passes the UL 1581, IEEE 383-1974, and IEEE 1202-1991 vertical tray
flame tests.
- Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520
and the 210,000 BTU/hr corner configuration test.
- UL listed as sunlight resistant.
- UL listed for direct burial.
- Complete pre-packaged, factory-tested wiring system-color coded.
- C-L-X enclosure permits installation in cable tray containing light
and power cables without a barrier separator.
- Individual pairs or triads are color coded for simplified hook-up.
- Maximum noise rejection.
- Impervious, continuous sheath excludes moisture, gases and liquids.
- C-L-X sheath exceeds equipment grounding conductor requirements of
NEC Article 250.
- Excellent compression and impact resistance.
- Lower installed system cost than conduit or EMT systems.
- OSHA Acceptable.
- UL listed as Marine Shipboard cable.
- Listed by American Bureau of Shipping (ABS) as CWCMC-PLTC and
CWCMC-ITC.
- Meets API Standards 14F and 14FZ.
- Recognized by US Coast Guard as Type MC (CWCMC).
- Suitable for low temperature installation of -40°C.
|