THE OKONITE COMPANY
Product Data
Section 5: Sheet 3
C-L-X® Type P-OS
Type ITC/PLTC Armored Instrumentation Cable
Single Pair or Triad - Overall Shield
300 Volts - 105°C Rating
For Cable Tray Use

UL 


A
Bare Stranded Copper Conductor

B  Okoseal Insulation

C  Twisted Pair/Triad

D  Aluminum/Polyester Tape

E  Tinned Stranded Copper Drain Wire

F  Rip Cord

G  Inner Black Okoseal Jacket

H  Impervious, Continuous Corrugated Aluminum C-L-X Sheath

J  Outer Black Okoseal Jacket


Specifications
Conductors: Bare soft annealed copper, Class B, 7-strand concentric per ASTM B-8.

Insulation: Flame-retardant Okoseal (PVC) per UL Standard 13 and UL 2250, 15 mils nominal thickness, 105°C temperature rating.

Conductor Identification: Pigmented black and white in pairs,
black, red and white in triads.

Assembly: Pair or triad assembled with left-hand lay.

Cable Shield: Aluminum/Polyester tape overlapped to provide 100% coverage, and a 7 strand tinned copper drain wire, same size as conductor.

Inner Jacket: Black, flame-retardant Okoseal per UL 13 and UL Standard 2250. A rip cord is laid longitudinally under the jacket to facilitate removal.

C-L-X Sheath: A close-fitting, impervious, continuously welded and corrugated aluminum sheath provides complete protection against moisture, liquids, and gases, has excellent mechanical strength and provides equipment grounding through the sheath.

Outer Jacket: Black, flame-retardant Okoseal per UL 13 and UL Standard 2250.

Classifications

UL Listed as ITC/PLTC Instrument Tray Cable/Power Limited Tray Cable for use in accordance with Article 727 and Article 725 of the National Electrical Code.

These cables comply with UL 2250 and UL 13 for PLTC, CL2 and CL3.

Applications
Okonite Type C-L-X P-OS (Pair/Triad - Overall Shield) instrumentation cables are designed for use as instrumentation, process control, and computer cables in ITC non-classified or labeled circuits up to 150 volts and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits where shielding against external interference is required, but shielding against interference among groups is not required; indoors or outdoors; in wet or dry locations with conductor operating temperatures up to 105°C; in cable trays; in raceways; supported by a messenger wire; under raised floors; for direct burial. Suitable Class I, Division 2, Class II, Division 2, or Class III, Division 2 and Class I, Zone 2 hazardous locations. Also for use as Power-Limited fire protective signaling cable (FPL) per NEC Code 760. The C-L-X sheath provides physical protection against mechanical damage. It may be installed in both exposed and concealed work, secured to supports not greater than 6 feet apart.

The overall shield eliminates most of the static interference from the electric field radiated by power cables and other electrical equipment.

For dc service in wet locations, X-Olene insulation is recommended.

Product Features

  • Passes the UL 1581, IEEE 383-1974, and IEEE 1202-1991 vertical tray flame tests.
  • Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520 and the 210,000 BTU/hr corner configuration test.
  • UL listed as sunlight resistant.
  • UL listed for direct burial.
  • Complete pre-packaged, factory-tested wiring system-color coded.
  • C-L-X enclosure permits installation in cable tray containing light and power cables without a barrier separator.
  • Individual pairs or triads are color coded for simplified hook-up.
  • Maximum noise rejection.
  • Impervious, continuous sheath excludes moisture, gases and liquids.
  • C-L-X sheath exceeds equipment grounding conductor requirements of NEC Article 250.
  • Excellent compression and impact resistance.
  • Lower installed system cost than conduit or EMT systems.
  • OSHA Acceptable.
  • UL listed as Marine Shipboard cable.
  • Listed by American Bureau of Shipping (ABS) as CWCMC-PLTC and CWCMC-ITC.
  • Meets API Standards 14F and 14FZ.
  • Recognized by US Coast Guard as Type MC (CWCMC).
  • Suitable for low temperature installation of -40°C.
     

Okoseal Insulation: 15 mils
 1-Catalog Number
 2-Number of Pairs
 3-Number of Triads
 4-Inner Jacket Thickness-mils
 5-Inner Jacket Nominal O.D.-Inches
 6-Outer Jacket-(mils)
  7-C-L-X O.D.-Inches
  8-Nominal Cable O.D.-Inches
  9-Cross-Sectional area (sq in)
10-Approx.Net Weight (lbs/1000')
11-Approx.Ship Weight (lbs/1000')
1 2 3 4 5 6 7 8 9 10 11

564-10-3401
564-15-3401

1


1

35
35

.26
.28

50
50

.43
.43

.54
.54

.25
.25

134
155

173
194

Authorized stock item. Available from our Customer Service Centers.

Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 392.9

Jackets:  Optional jacket types available - consult local sales office.

Length Tolerance:
Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ±15%.

Copper or bronze C-L-X available on special order.

To order C-L-X Type P-OS without the outer Okoseal jacket, change the sixth digit of the catalog number from 3 to 1, for example to order 1 pr. 16 AWG with a bare aluminum C-L-X, the catalog number would be 564-10-1401.

C-L-X products manufactured in the United States under license granted by Kabelmetal of Hanover, Germany.


ELECTRICAL SPECIFICATIONS
Per UL Standard 13 & 2250
Conductor Resistance, nominal.................ohms/1000 ft. @20°C
16 AWG....................................................................4.1
Insulation Test Voltage (spark test)......................5000 Volts ac
Dielectric Test Voltage.............................................1500 Volts
Insulation Resistance Constant @60°F minimum                          
(natural material typical value)...............2000 Megohms-1000 ft.
Loop Resistance, nominal (2 conductor) ohms-1000 ft @20°C  
16 AWG..................................................................8.2
Mutual Capacitance, typical.........................................76 PF/ft
 
C/04050503

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS