A Solid Thermocouple Alloy
Conductor
B Okoseal Insulation
C Tinned Stranded Copper Group
Drain Wire
D Aluminum/Synthetic Polymer
Tape
E Twisted Shielded Pairs
F Communication Wire
G Aluminum/Synthetic Polymer
Tape
H Tinned Stranded Copper Group
Drain Wire
J Rip Cord
K Inner Okoseal Jacket
L Galvanized Steel Interlocking
Loxarmor
M Outer Okoseal Jacket
Specifications
Conductors: Solid alloys per ANSI MC 96.1.
Insulation: Flame-retardant Okoseal®
(PVC) per UL Standard 13 and 2250, 15 mils nominal thickness, 105°C
temperature rating.
Conductor Identification: Pigmented insulation on individual
conductors, negative conductor numerically printed for group
identification.
Group Shield: Aluminum/synthetic polymer taped overlapped to
provide 100% coverage, and a tinned copper drain wire, two sizes smaller
than the conductor. All group shields are completely isolated from each
other.
Communications Wire: 22 AWG solid 12 mils nominal flame-retardant
Okoseal insulation, 105°C temperature
rating.
Assembly: Pairs assembled with left-hand lay. Flame-retardant,
non-wicking fillers included where required to provide a round cable.
Cable Shield: Aluminum/Polyester tape overlapped to provide 100%
coverage, and a 7-strand tinned copper drain wire, same size as the
conductor.
Inner Jacket: Color-coded, flame-retardant Okoseal per UL Standard
13 and 2250. A rip cord is laid longitudinally under the jacket to
facilitate removal.
Loxarmor Sheath: An interlocking galvanized steel armor provides
mechanical protection against cut-through and crushing. All four sides of
the steel tape are galvanized to prevent corrosion.
Outer Jacket: Color-coded, flame-retardant, low temperature Okoseal
per UL Standard 13 and 2250.
Classification: UL Listed as Type ITC/PLTC - Instrumentation Tray
Cable/Power Limited Tray Cable for use in accordance with Article 725 and
727 of the National Electrical Code.
The cables comply with UL 2250 and UL13 for CL2 and CL3.
Applications
Okonite Loxarmor Type SP-OS (Pair - Individual and Overall
Shield) thermocouple extension cables are designed for use as
instrumentation and process control cables in ITC non-classified or
labeled circuits up to 150 volts and 5 amps (750VA) and in Class 2 or 3
Power-Limited
circuits where maximum shielding against external interference is
required, as well as shielding among groups, particularly where the cable
may be subject to abnormally high current or voltage interference; indoors
or outdoors; in wet or dry locations with a conductor operating
temperatures up to 105°C; in cable
trays; in raceways; supported by a messenger wire; under raised floors;
for direct burial. Suitable Class I, Division 2, Class II, Division 2, or
Class III, Division 2 hazardous locations. Also for use as Power-Limited
fire protective signaling cable (FPL) per NEC Code 760. The Loxarmor
(interlocked steel) sheath provides the physical protection against
mechanical damage as required in NEC Section 727-4. It may be installed in
both exposed and concealed work, secured to supports not greater than 6
feet apart.
Product Features
- Passes the UL 1581 & IEEE 383-1974 vertical tray flame tests.
- Passes the IEEE 1202-1991 vertical tray flame test (8 pair and
larger).
- Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520
and the 210,000 BTU/hr corner configuration test.
- UL listed as sunlight resistant.
- UL listed for direct burial (2 pr #20 AWG and larger).
- Complete pre-packaged, factory-tested wiring system-color coded.
- Loxarmor cables are quality control inspected to meet or exceed
applicable UL Standards.
- Loxarmor enclosure permits installation in cable tray containing
light and power cables without a barrier separator.
- Individual pairs are numbered and color-coded for simplified
hook-up.
- Individual pairs or triads are completely isolated.
- Maximum noise rejection.
- Impervious, continuous sheath excludes moisture, gases and liquids.
- Excellent compression and impact resistance.
- Lower installed system cost than conduit or EMT systems.
- OSHA Acceptable.
- Also available in aluminum.
- Suitable for installation at low temperature to -40°C.
|