THE OKONITE COMPANY
Product Data
Section 5: Sheet
26

C-L-X® Type SP-OS
Type ITC/PLTC Thermocouple Extension Cable
Multiple Pair - Overall Shield
105°C Rating
For Cable Tray Use
UL 

A  Solid Thermocouple Alloy Conductor

B  Okoseal Insulation

C  Tinned Stranded Copper Group Drain Wire

D  Aluminum/Polyester Tape

E  Twisted Shielded Pairs

F  Communication Wire

G  Aluminum/Polyester Tape

H  Tinned Stranded Copper Group Drain Wire

J  Rip Cord

K  Inner Okoseal Jacket

L  Impervious, Continuous, Corrugated Aluminum C-L-X Sheath

M  Outer Okoseal Jacket


Specifications
Conductors: Solid alloys per ANSI MC 96.1.

Insulation: Flame-retardant Okoseal® (PVC) per UL Standard 13 and 2250, 15 mils nominal thickness, 105°C temperature rating.

Conductor Identification: Pigmented insulation on individual conductors, negative conductor numerically printed for group identification.

Group Shield: Aluminum/polyester taped overlapped to provide 100% coverage, and a tinned copper drain wire, two sizes smaller than the conductor. All group shields are completely isolated from each other.

Communications Wire: 22 AWG bare copper conductor, 12 mils nominal flame-retardant Okoseal insulation, 105°C temperature rating.

Assembly: Pairs assembled with left-hand lay. Flame-retardant, non-wicking fillers included where required to provide a round cable.

Cable Shield: Aluminum/polyester tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, same size as the conductor.

Inner Jacket: Color-coded, flame-retardant, low temperature, Okoseal per UL Standard 13 and 2250. A rip cord is laid longitudinally under the jacket to facilitate removal.

C-L-X Sheath: A close-fitting, impervious, continuously welded and corrugated aluminum sheath provides complete protection against moisture, liquids, and gases, has excellent mechanical strength, and provides equipment grounding through the sheath.

Outer Jacket: Color-coded, flame-retardant, low temperature, Okoseal per UL Standard 13 and 2250.

Classification: UL Listed as Type ITC/PLTC - Instrumentation Tray Cable/Power Limited Tray Cable for use in accordance with Article 725 and 727 of the National Electrical Code.

The cables comply with UL 2250 and UL 13 for PLTC, CL2 and CL3.

Applications
Okonite Type C-L-X SP-OS (Pair - Individual and Overall Shield) thermocouple extension cables are designed for use as instrumentation and process control cables in ITC non-classified or labeled circuits and in Class 2 or 3 Power-Limited circuits where maximum shielding against external interference is required, as well as shielding among groups, particularly where the cable may be subject to abnormally high current or voltage interference; indoors or outdoors; in wet or dry locations with conductor operating temperatures up to 105°C; in cable trays; in raceways; supported by a messenger wire; under raised floors; for direct burial. Suitable Class I, Division 2, Class II, Division 2, or Class III, Division 2 and Class I, Zone 2 hazardous locations. Also for use as Power-Limited fire protective signaling cable (FPL) per NEC Code 760. The C-L-X sheath provides physical protection against mechanical damage. It may be installed in both exposed and concealed work, secured to supports not greater than 6 feet apart.

Product Features

  • Passes the UL 1581 & IEEE 383-1974 vertical tray flame tests.
  • Passes the IEEE 1202-1991 vertical tray flame test (2 pair #18 AWG and larger).
  • Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520 and the 210,000 BTU/hr corner configuration test.
  • UL listed as sunlight resistant.
  • UL listed for direct burial (2 pr #20 AWG and larger).
  • Complete pre-packaged, factory-tested wiring system-color coded.
  • C-L-X cables are quality inspected to meet or exceed applicable UL Standards.
  • C-L-X enclosure permits installation in cable tray containing light and power cables without a barrier separator.
  • Individual pairs are numbered and color coded for simplified hook-up.
  • Individual pairs are completely isolated for maximum noise rejection.
  • Impervious, continuous sheath excludes moisture, gases and liquids.
  • C-L-X sheath exceeds equipment grounding conductor requirements of NEC Section 250.
  • Excellent compression and impact resistance.
  • Lower installed system cost than conduit or EMT systems.
  • OSHA Acceptable.
  • UL listed as Marine Shipboard cable.
  • American Bureau of Shipping listed as CWCMC-PLTC and CWCMC-ITC.
  • Recognized by US Coast Guard as Type MC or CWCMC.
  • Suitable for low temperature installation to -40°C.

Conductors: 20 AWG - Okoseal Insulation: 15 mils
 1-ASA/ISA Type
 2-Catalog Number
 3-Number of Pairs
 4-Inner Jacket Thickness - mils
 5-Inner Jacket Nominal O.D. - (In.)
 6-C-L-X O.D. - Inches
  7-Outer Jacket - mils
  8-Nominal Cable O.D. - (In.)
  9-Cross-Sectional Area (sq in)
 10-Approx Net Weight (lbs/1000’)
 11-Approx Ship Weight (lbs/1000’)
1 2 3 4 5 6 7 8 9 10 11

EX

584-10-1204
584-10-1208
584-10-1210

4
8
10

50
50
60

.45
.56
.64

.66
.80
.89

50
50
50

.77
.91
1.00

.47
.65
.78

230
307
380

310
387
460

584-10-1212
584-10-1216
584-10-1220

12
16
20

60
60
60

.70
.77
.81
.93
1.02
1.06

50
50
50

1.04
1.13
1.17
.85
1.00
1.07
409
484
560
489
564
640

584-10-1224
584-10-1236
584-10-1250

24
36
50

70
70
70

.97
1.09
1.19

1.24
1.37
1.51

50
50
60

1.35
1.56
1.65

1.43
1.91
2.14

668
860
1177

748
966
1320

JX

584-10-2204
584-10-2208
584-10-2210

4
8
10

50
50
60

.45
.56
.64

.66
.80
.89

50
50
50

.77
.91
1.00

.47
.65
.78

229
305
378

309
385
458

584-10-2212
584-10-2216
584-10-2220

12
16
20

60
60
60

.70
.77
.81

.93
1.02
1.06

50
50
50

1.04
1.13
1.17

.5
1.00
1.07

405
481
556

485
561
636

584-10-2224
584-10-2236
584-10-2250

24
36
50

70
70
70

.97
1.09
1.19

1.24
1.37
1.51

50
50
60

1.35
1.56
1.65

1.43
1.91
2.14

663
853
1167

743
959
1310

KX

584-10-3204
584-10-3208
584-10-3210

4
8
10

50
50
60

.45
.56
.64

.66
.80
.89

50
50
50

.77
.91
1.00

.47
.65
.78

230
307
380

310
387
460

584-10-3212
584-10-3216
584-10-3220

12
16
20

60
60
60

.70
.77
.81

.94
1.02
1.06

50
50
50

1.04
1.13
1.17

.85
1.00
1.07

409
484
560

489
564
640

584-10-3224
584-10-3236
584-10-3250

24
36
50

70
70
70

.97
1.09
1.19

1.24
1.37
1.51

50
50
60

1.35
1.56
1.65

1.43
1.92
2.14

668
860
1177

748
966
1320

TX

584-10-4204
584-10-4208
584-10-4210

4
8
10

50
50
60

.45
.56
.64

.66
.80
.89

50
50
50

.77
.91
1.00

.47
.65
.78

231
309
383

311
389
463

584-10-4212
584-10-4216
584-10-4220

12
16
20

60
60
60

.70
.77
.81

.93
1.02
1.06

50
50
50

1.04
1.13
1.17

.85
1.00
1.07

410
487
564

490
567
644

584-10-4224
584-10-4236
584-10-4250

24
36
50

70
70
70

.97
1.09
1.19

1.24
1.37
1.51

50
50
60

1.35
1.40
1.56

1.43
1.91
2.14

673
867
1187

953
973
1330

ASA/ISA COLOR CODE AND LIMITS OF ERROR

ASA/ISA
Type

Positive Wire

Negative Wire

Outer
Jacket
Color

Temperature
Range°C

Limits of Error

Wire
Size (AWG)

Nom. Loop
Resistance
Per 100’ @ 20°C

Alloy

Color

Alloy

Color

Standard

Special (1)

EX

Chromel

Purple

Constantan

Red

Purple

0 to 200°C

± 1.7°C

± 1.0°C

20

70.7 ohms

JX

Iron

White

Constantan

Red

Black

0 to 200°C

± 2.2°C

± 1.1°C

20

35.7 ohms

KX

Chromel

Yellow

Alumel

Red

Yellow

0 to 200°C

± 2.2°C

± 1.1°C 

20

59.0 ohms

TX

Copper

Blue

Constantan

Red

Blue

-60 to 100°C

± 1.0°C

± 0.5°C

20

29.8 ohms

SX  available upon request.

(1)  Special grade alloy conductors for JX and TX are available on special order.

  Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 392.9

Jackets:  Optional jacket types available - consult local sales office.

Copper or Bronze C-L-X available on special order.

To order C-L-X Type SP-OS without the outer Okoseal jacket, change the sixth digit of the catalog number from 1 to 5 for Ex, 2 to 6 for JX, 3 to & for KX, and 4 to 8 for TX. For example to order 12 pr. 20 AWG Type KX with a bare aluminum C-L-X, the catalog number would be 584-10-7212.

C-L-X products manufactured in the United States under license granted by Kabelmetal of Hanover, Germany.

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ±15%.


ELECTRICAL SPECIFICATIONS
Per UL Standard 2250

Insulation Test Voltage (spark test)...............................5000 Volts ac
Dielectric Test Voltage................................1500 Volts ac for 15 sec.
Insulation Resistance Constant @60°F, minimum                                 
(natural material typical value).............................2000 Ohms-1000 ft.
C/05030526
BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |