THE OKONITE COMPANY
Product Data
Section 5: Sheet 20

Wire Armored Type P-OS
Type ITC/PLTC Armored Thermocouple
Extension Cable

Single Pair - Overall Shield 105°C Rating
For Cable Tray Use
UL 

A  Solid Thermocouple Alloy Conductor

B  Okoseal Insulation

C  Twisted Pair

D  Double Faced Aluminum/Synthetic Polymer Backed Tape

E  Tinned Stranded Copper Drain Wire

F  Rip Cord

G  Inner Okoseal Jacket

H  Galvanized Steel Served Wire Armor

J  Outer Okoseal Jacket


Specifications
Conductors: Solid alloys per ANSI MC 96.1.

Insulation: Flame-retardant Okoseal (PVC) per UL Standards 13 and 2250, 15 mils nominal thickness, 105°C temperature rating.

Conductor Identification: Pigmented insulation on individual conductors

Assembly: Pairs assembled with left-hand lay.

Cable Shield: Aluminum/Polyester tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, same size as the conductor.

Inner Jacket: Flame-retardant Okoseal per UL Standards 13 and 2250. A rip cord is laid longitudinally under the jacket to facilitate removal.

Wire Armor: A serving of soft annealed galvanized steel wires, SWA, applied with a left-hand lay and 90% coverage.

Outer Jacket: Flame-retardant, low temperature Okoseal per UL Standards 13 and 2250.

Classifications: UL Listed as Type ITC/PLTC Instrumentation Tray Cable/Power Limited Tray Cable for use in accordance with Articles 725 and 727 of the National Electrical Code.

These cables comply with UL 2250 and UL 13 for CL2 and CL3.

Applications
Okonite SWA Type P-OS (Pair/triad - Overall Shield) Thermocouple Extension cables are designed for use as instrumentation and process control cables in ITC non-classified or labeled circuit up to 150 volts and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits where shielding against external interference is required, but shielding against interference among groups is not required; indoors or outdoors; in wet or dry locations with conductor operating temperatures up to 105°C; in cable trays; in raceways; supported by a messenger wire; under raised floors; for direct burial. Suitable Class I, Divisions 2, Class II, Division 2, or Class III, Division 2 hazardous locations. Also for use as Power-Limited fire protective signaling cable (FPL) per NEC Code 760.

Product Features

  • Passes the UL 1581 & IEEE 383-1974 vertical tray flame tests.
  • Sunlight & oil resistant.
  • UL listed for direct burial.
  • Individual pairs or triads are color coded for simplified hook-up.
  • Good noise rejection.
  • Excellent weathering characteristics.
  • OSHA Acceptable.
  • Flexible, easy to handle terminate.
  • Twisted with 100% shield coverage to reduce electromagnetic noise.
  • Suitable for low temperature installation of -40°C.

Conductors: 16 AWG
Okoseal Insulation: 15 mils

 1-ASA/ISA Type
 2-Catalog Number
 3-Size AWG
 4-Number of Pairs
 5-Inner Jacket Thickness - mils
 6-Inner Jacket Nominal O.D. - Inches
 7-Armor Wires - No. x SWG

  8-Nominal Armor O.D. - Inches
  9-Outer Jacket - mils
10-Nominal Cable O.D. - (In.)
11-Cross-Sectional Area    (sq in)
12-Approx Net Weight (lbs/1000’)
13-Approx Ship Weight (lbs/1000’)

1 2 3 4 5 6 7 8 9 10 11 12 13

EX
JX
KX
TX

284-20-8181
284-20-8281
284-20-8381
284-20-8481

16
16
16
16

1
1
1
1

35
35
35
35

.25
.25
.25
.25

31 x 24
31 x 24
31 x 24
31 x 24

.30
.30
.30
.30

35
35
35
35

.37
.37
.37
.37

.11
.11
.11
.11

114
114
114
114

125
125
125
125

ASA/ISA COLOR CODE AND LIMITS OF ERROR

ASA/ISA Type Positive Wire Negative Wire Outer
 Jacket
 Color
Temperature
Range°C
Limits of Error Nom. Loop
Resistance
Per 100’ @ 20°C
Alloy Color Alloy Color Standard Special (1)
EX Chromel Purple Constantan Red Purple 0 to 200°C ± 1.7°C   27.8 ohms
JX Iron White Constantan Red Black 0 to 200°C ± 2.2°C ± 1.1°C 13.9 ohms
KX Chromel Yellow Alumel Red Yellow 0 to 200°C ± 2.2°C   23.6 ohms
TX Copper Blue Constantan Red Blue -60 to 100°C ± 1.0°C ± 0.5°C 12.0 ohms

SX available upon request.

(1) Special grade alloy conductors for JX and TX are available on special order.

Minimum Manufacturing Quantity: is 1000 ft.

Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 318-9

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ±15%.


ELECTRICAL SPECIFICATIONS
Per UL Standard 13 and 2250
Insulation Test Voltage (spark test)...........................5000 Volts ac
Dielectric Test Voltage............................1500 Volts ac for 15 sec.
Shield Isolation Test                                                                       
Pair to Cable Shield.......................exceeds 100 Megohms/1000 ft.
Insulation Resistance Constant @60°F minimum                              
(natural material typical value)..........................2000 Ohms-1000 ft. 
B/01100520