 A
Solid Thermocouple Alloy Conductor
B Okoseal Insulation
C Twisted Pair
D Aluminum/Polyester Tape
E Tinned Stranded Copper Drain
Wire
F Rip Cord
G Inner Okoseal Jacket
H Impervious, Continuous,
Corrugated Aluminum C-L-X Sheath
J Outer Okoseal Jacket
Specifications
Conductors: Solid alloys per ANSI MC 96.1.
Insulation: Flame-retardant Okoseal®
(PVC) per UL Standard 13 and 2250, 15 mils nominal thickness, 105°C
temperature rating.
Conductor Identification: Pigmented insulating on individual
conductors.
Assembly: Pairs assembled with left-hand lay
Cable Shield: Aluminum/Polyester backed tape overlapped to provide
100% coverage, and a 7-strand tinned copper drain wire, same size as the
conductor.
Inner Jacket: Black, flame-retardant, low temperature Okoseal per
UL Standard 13 and 2250. A rip cord is laid longitudinally under the
jacket to facilitate removal.
C-L-X Sheath: Close fitting, impervious, continuously welded and
corrugated aluminum sheath provides complete protection against moisture,
liquids, and gases, has excellent mechanical strength and provides
equipment grounding through the sheath.
Outer Jacket: Flame-retardant, low temperature Okoseal per UL
Standard 13 and 2250.
Classifications: UL Listed as Type ITC/PLTC - Instrumentation Tray
Cable/Power Limited Tray Cable, for use in accordance with Article 727 and
725 of the National Electrical Code.
Cables comply with UL 2250 and UL Subject 13 for PLTC, CL2 and CL3.
Applications
Okonite Type C-L-X P-OS (Pair/triad - Overall Shield) Thermocouple
Extension cables are designed for use as instrumentation and process
control cables in ITC non-classified or labeled circuits up to 150 volts
and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits
where shielding against external interference is required, but shielding
against interference among groups is not required; indoors or outdoors; in
wet or dry location with conductor operating temperatures up to 105°C;
in cable trays; in raceways; supported by a messenger wire; under raised
floors; for direct burial. Suitable Class I, Division 2, Class II,
Division 2, or Class III, Division 2 and Class I, Zone 2 hazardous locations. The C-L-X sheath
provides physical protection against mechanical damage. It may be
installed in both exposed and concealed work, secured to
supports not greater than 6 feet apart.
Product Features
- Passes the UL 1581, IEEE 383-1974, & IEEE 1202-1991 vertical tray
flame tests.
- Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520
and the 210,000 BTU/hr corner configuration test.
- Complete pre-packaged, factory-tested wiring system-color coded.
- C-L-X cables are quality control inspected to meet or exceed
applicable UL Standards.
- C-L-X enclosure permits installation in cable tray containing light
and power cables without a barrier separator.
- Individual pairs or triads are color coded for simplified hook-up.
- Impervious, continuous sheath excludes moisture, gases and liquids.
- C-L-X sheath exceeds equipment grounding conductor requirements of
NEC Section 250.
- Lower installed system cost than conduit or EMT systems.
- Meets API Standards 4F and 14FZ.
- UL listed as Marine Shipboard cable.
- American Bureau of Shipping listed as CWCMC-PLT and CWCMC-ITC.
- Recognized by US Coast Guard as Type MC.
- UL listed for direct burial.
- Suitable for low temperature installation of -40°C.
|