THE OKONITE COMPANY
Product Data
Section 5: Sheet
19

C-L-X® Type P-OS
Type ITC/PLTC Armored Thermocouple
Extension Cable

Single Pair - Overall Shield - 105°C Rating
For Cable Tray Use
UL 

 A  Solid Thermocouple Alloy Conductor
 
 B  Okoseal Insulation
 
 C  Twisted Pair
 
 D  Aluminum/Polyester Tape
 
 E  Tinned Stranded Copper Drain Wire
 
 F  Rip Cord
 
 G  Inner Okoseal Jacket
 
 H  Impervious, Continuous, Corrugated Aluminum C-L-X      Sheath
 
 J  Outer Okoseal Jacket


Specifications
Conductors: Solid alloys per ANSI MC 96.1.

Insulation: Flame-retardant Okoseal® (PVC) per UL Standard 13 and 2250, 15 mils nominal thickness, 105°C temperature rating.

Conductor Identification: Pigmented insulating on individual conductors.

Assembly: Pairs assembled with left-hand lay

Cable Shield: Aluminum/Polyester backed tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, same size as the conductor.

Inner Jacket: Black, flame-retardant, low temperature Okoseal per UL Standard 13 and 2250. A rip cord is laid longitudinally under the jacket to facilitate removal.

C-L-X Sheath: Close fitting, impervious, continuously welded and corrugated aluminum sheath provides complete protection against moisture, liquids, and gases, has excellent mechanical strength and provides equipment grounding through the sheath.

Outer Jacket: Flame-retardant, low temperature Okoseal per UL Standard 13 and 2250.

Classifications: UL Listed as Type ITC/PLTC - Instrumentation Tray Cable/Power Limited Tray Cable, for use in accordance with Article 727 and 725 of the National Electrical Code.

Cables comply with UL 2250 and UL Subject 13 for PLTC, CL2 and CL3.

Applications
Okonite Type C-L-X P-OS (Pair/triad - Overall Shield) Thermocouple Extension cables are designed for use as instrumentation and process control cables in ITC non-classified or labeled circuits up to 150 volts and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits
where shielding against external interference is required, but shielding against interference among groups is not required; indoors or outdoors; in wet or dry location with conductor operating temperatures up to 105°C; in cable trays; in raceways; supported by a messenger wire; under raised floors; for direct burial. Suitable Class I, Division 2, Class II, Division 2, or Class III, Division 2 and Class I, Zone 2 hazardous locations. The C-L-X sheath provides physical protection against mechanical damage. It may be installed in both exposed and concealed work, secured to
supports not greater than 6 feet apart.

Product Features

  • Passes the UL 1581, IEEE 383-1974, & IEEE 1202-1991 vertical tray flame tests.
  • Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520 and the 210,000 BTU/hr corner configuration test.
  • Complete pre-packaged, factory-tested wiring system-color coded.
  • C-L-X cables are quality control inspected to meet or exceed applicable UL Standards.
  • C-L-X enclosure permits installation in cable tray containing light and power cables without a barrier separator.
  • Individual pairs or triads are color coded for simplified hook-up.
  • Impervious, continuous sheath excludes moisture, gases and liquids.
  • C-L-X sheath exceeds equipment grounding conductor requirements of NEC Section 250.
  • Lower installed system cost than conduit or EMT systems.
  • Meets API Standards 4F and 14FZ.
  • UL listed as Marine Shipboard cable.
  • American Bureau of Shipping listed as CWCMC-PLT and CWCMC-ITC.
  • Recognized by US Coast Guard as Type MC.
  • UL listed for direct burial.
  • Suitable for low temperature installation of -40°C.

Conductors: 16 AWG
Okoseal Insulation: 15 mils

 1-ASA/ISA Type
 2-Catalog Number
 3-Number of Pairs
 4-Inner Jacket Thickness - mils
 5-Inner Jacket Nominal O.D. - Inches
 6-C-L-X O.D. - Inches

  7-Outer Jacket - mils
  8-Nominal Cable O.D. - (In.)
  9-Cross-Sectional Area   (sq in)
 10-Approx Net Weight (lbs/1000’)
 11-Approx Ship Weight (lbs/1000’)

1 2 3 4 5 6 7 8 9 10 11

EX
JX
KX
TX

584-20-1401
584-20-2401
584-20-3401
584-20-4401

1
1
1
1

35
35
35
35

.25
.25
.25
.25

.43
.43
.43
.43

50
50
50
50

.54
.54
.54
.54

.23
.23
.23
.23

128
128
128
128

167
167
167
167

ASA/ISA COLOR CODE AND LIMITS OF ERROR

ASA/ISA Type Positive Wire Negative Wire Outer
 Jacket
 Color
Temperature
Range°C
Limits of Error Nom. Loop
Resistance
Per 100’ @ 20°C
Alloy Color Alloy Color Standard Special (1)
EX Chromel Purple Constantan Red Purple 0 to 200°C ± 1.7°C   27.8 ohms
JX Iron White Constantan Red Black 0 to 200°C ± 2.2°C ± 1.1°C 13.9 ohms
KX Chromel Yellow Alumel Red Yellow 0 to 200°C ± 2.2°C   23.6 ohms
TX Copper Blue Constantan Red Blue -60 to 100°C ± 1.0°C ± 0.5°C 12.0 ohms

Authorized Stock Item:  Available from our Customer Service Centers.

SX available upon request.

(1) Special grade alloy conductors for JX and TX are available on special order.

Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 392.9

Jackets:  Optional jacket types available - consult local sales office.

Copper or bronze  C-L-X available on special order.

To order C-L-X Type P-OS without the outer Okoseal jacket, change the sixth digit of the catalog number from 1 to 5 for EX, 2 to 6 for JX, 3 to 7 for KX, and 4 to 8 for TX. For example to order 12 pr. 20 AWG Type KX with a bare aluminum C-L-X, the catalog number would be 584-20-7212.

C-L-X products manufactured in the United States under license granted by Kabelmetal of Hanover, Germany.

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ±15%.


ELECTRICAL SPECIFICATIONS
Per UL Standard 2250
Insulation Test Voltage (spark test)...........................5000 Volts ac
Dielectric Test Voltage............................1500 Volts ac for 15 sec.
Shield Isolation Test                                                                       
Pair to Cable Shield..........................exceeds 100M ohms/1000 ft.
Insulation Resistance Constant @60°F minimum                             
(natural material typical value)...................2000 Megohms-1000 ft. 