THE OKONITE COMPANY
Product Data 
Section 5: Sheet 10

C-L-X® Type P-OS
Type ITC/PLTC Armored Instrumentation Cable
Multiple Pairs or Triads - Overall Shield
300 Volts - 105°C Rating
For Cable Tray Use
UL 

 A  Bare Stranded Copper Conductor

 B  Okoseal Insulation

 C  Twisted Pairs/Triads

 D  Communication Wire

 E  Aluminum/Polyester Tape

 F  Tinned Stranded Copper Drain Wire

 G  Rip Cord

 H  Inner Black Okoseal Jacket

 J  Impervious, Continuous, Corrugated Aluminum C-L-X Sheath

 K Outer Black Okoseal Jacket



Specifications

Conductors: Bare soft annealed copper, Class B, 7-strand concentric per ASTM B-8.

Insulation: Flame-retardant Okoseal (PVC) per UL 13 and 2250, 15 mils nominal thickness, 105°C temperature rating.

Conductor Identification: Pigmented black and white in pairs, black, red and white in triads; white conductor numerically printed for group identification.

Communication Wire: 22 AWG, solid bare copper conductor, 12 mils nominal flame-retardant Okoseal insulation, 105°C temperature rating.

Assembly: Pairs or triads assembled with left-hand lay. Flame-retardant, non-wicking fillers included where required to provide a round cable.

Cable Shield: Aluminum/Polyester tape overlapped to provide 100% coverage, and a 7-strand tinned copper drain wire, same size as conductor.

Inner Jacket: Black, flame-retardant, low temperature Okoseal per UL 13 and 2250. A rip cord is laid longitudinally under the jacket to facilitate removal.

C-L-X Sheath: A close fitting, impervious, continuously welded and corrugated aluminum sheath provides complete protection against moisture, liquids, and gases, has excellent mechanical strength and provides equipment grounding through the sheath.

Outer Jacket: Black, flame-retardant, low temperature Okoseal per UL 13 and 2250.

Classifications: UL Listed as ITC/PLTC - Instrument Tray Cable/Power Limited Tray Cable for use in accordance with Article 727 and Article 725 of the National Electrical Code.

Cables comply with UL 2250 and UL 13 for PLTC, CL2 and CL3.

Applications
Okonite Type C-L-X P-OS (Pairs/triads - Overall Shield) instrumentation cables are designed for use in instrumentation, process control in ITC non-classified or labeled circuits up to 150 volts and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits where shielding
against external interference is required, but shielding against interference among groups is not required; indoors or outdoors; in wet or dry locations with conductor operating temperatures up to 150°C; in cable trays; in raceways; supported by a messenger wire; under raised floors; for direct burial. Suitable Class I, Division 2, Class II, Division 2, or Class III, Division 2 and Class I, Zone 2 hazardous locations. Also for use as power-Limited fire protective signaling cable (FPL) per NEC Code 760. The C-L-X sheath provides physical protection against mechanical damage. It may be installed in both exposed and concealed work, secured to supports not greater than 6 feet apart.

The overall shield eliminates most of the static interference from the electric field radiated by power cables and other electrical equipment.

For dc service in wet locations, X-Olene® insulation s recommended.

Product Features

  • Passes the UL 1581 & IEEE 383-1974 vertical tray flame tests.
  • Passes the IEEE 1202-1991 vertical tray flame test (2 Pr #18 AWG and larger).
  • Passes the 210,000 BTU/hr vertical tray flame test per ICEA T-29-520 and the 210,000 BTU/hr corner configuration test.
  • UL listed as sunlight resistant.
  • UL listed for direct burial (2 PR #20 AWG and larger).
  • Complete prepackaged, factory-tested wiring system-color coded.
  • C-L-X cables are quality control inspected to meet or exceed applicable UL Standards.
  • C-L-X enclosure permits installation in cable tray containing light and power cables without a barrier separator.
  • Individual pairs or triads are numbered and color coded for simplified hook-up.
  • Excellent noise rejection.
  • Impervious, continuous sheath excludes moisture, gases and liquids.
  • C-L-X sheath exceeds equipment grounding conductor requirements of NEC Section 250.
  • Excellent compression and impact resistance.
  • Lower installed system cost than conduit or EMT systems.
  • OSHA acceptable.
  • Meets API Standards 14F and 14FZ.
  • UL listed as Marine Shipboard cable.
  • American Bureau of Shipping listed as CWCMC Type PLTC and CWCMC-ITC.
  • Recognized by US Coast Guard as Type MC or CWCMC.
  • Suitable for low temperature installation to -40°C.

 1-Catalog Number
 2-Strand Size (AWG)
 3-Number of Pairs
 4-Number of Triads
 5-Inner Jacket Thickness-mils
 6-Nominal Core O.D. - Inches
  7-C-L-X O.D. - Inches
  8-Outer Jacket - mils
  9-Nominal Cable O.D. - Inches
10-Cross-Sectional Area (sq in)
11-Approx Net Weight (lbs/1000’)
12-Approx Ship Weight (lbs/1000’)
1 2 3 4 5 6 7 8 9 10 11 12

564-10-3202
564-10-3204
564-10-3206

20(7X)

2
4
6


 

40
40
50

0.35
0.39
0.45

0.58
0.58
0.66

50
50
50

0.69
0.69
0.77

0.37
0.37
0.47

171
194
245

210
233
325

564-10-3208
564-10-3210
564-10-3212

8
10
12

 

50
50
50

0.49
0.56
0.58

0.71
0.80
0.80

50
50
50

0.83
0.91
0.91

0.53
0.65
0.65

277
324
346

357
404
426

564-10-3216
564-10-3220
564-10-3224

16
20
24

 

60
60
60

0.66
0.72
0.77

0.89
0.97
1.02

50
50
50

1.00
1.08
1.13

0.78
0.92
1.00

424
490
545

504
570
625

564-10-3236
564-10-3250

36
50

 

60
70

0.87
1.02

1.11
1.29

50
50

1.22
1.40

1.51
1.54

697
930

803
1036

564-15-3204
564-15-3208
564-15-3212

 

4
8
12

50
50
50

0.43
0.51
0.61

0.66
0.75
0.84

50
50
50

0.77
0.86
0.95

0.46
0.58
0.71

242
329
419

322
409
499

564-15-3216
564-15-3224
564-15-3236

 

16
24
36

60
60
70

0.69
0.81
0.93

0.93
1.06
1.19

50
50
50

1.04
1.17
1.30

0.85
1.08
1.33

518
680
936

598
760
1026

564-10-3302
564-10-3304
564-10-3306

18(7X)

2
4
6

 

50
50
50

0.41
0.46
0.50

0.62
0.66
0.71

50
50
50

0.73
0.77
0.82

0.42
0.46
0.53

202
244
288

282
324
368

564-10-3308
564-10-3310
564-10-3312

8
10
12

 

50
60
60

0.55
0.65
0.68

0.80
0.87
0.93

50
50
50

0.91
1.00
1.04

0.65
0.78
0.85

330
409
440

410
489
520

564-10-3316
564-10-3320
564-10-3324

16
20
24

 

60
60
60

0.73
0.81
0.86

0.97
1.06
1.11

50
50
50

1.08
1.17
1.22

0.92
1.07
1.17

525
611
684

605
691
790

564-10-3336
564-10-3350

36
50

 

70
70

1.00
1.15

1.29
1.46

50
50

1.40
1.57

1.54
1.93

946
1255

1052
1398

564-15-3304
564-15-3308
564-15-3312

 

4
8
12

50
50
60

0.49
0.57
0.71

0.71
0.80
0.93

50
50
50

0.82
0.91
1.04

0.53
0.65
0.85

285
401
543

365
481
623

564-15-3316
564-15-3324
564-15-3336

 

16
24
36

60
70
70

0.78
0.92
1.04

1.02
1.19
1.34

50
50
50

1.13
1.30
1.45

1.00
1.33
1.65

658
918
1231

738
1008
1337

564-10-3402
564-10-3404
564-10-3406

16(7X)

2
4
6

 

50
50
50

0.46
0.51
0.56

0.66
0.75
0.80

50
50
50

0.77
0.86
0.91

0.46
0.58
0.65

234
290
359

314
370
439

564-10-3408
564-10-3410
564-10-3412

8
10
12

 

50
60
60

0.62
0.73
0.76

0.84
0.97
1.02

50
50
50

0.95
1.08
1.13

0.71
0.92
1.00

416
512
559

496
592
639

564-10-3416
564-10-3420
564-10-3424

16
20
24

 

60
70
70

0.82
0.93
1.00

1.06
1.19
1.29

50
50
50

1.17
1.30
1.40

1.07
1.33
1.54

674
832
937

754
922
1027

564-10-3436
564-10-3450

36
50

 

70
80

1.11
1.32

1.42
1.64

50
60

1.53
1.78

1.84
2.49

1258
1751

1401
1915

564-15-3404
564-15-3408
564-15-3412

 

4
8
12

50
60
60

0.53
0.66
0.79

0.75
0.89
1.06

50
50
50

0.86
1.00
1.17

0.58
0.78
1.07

346
529
713

426
609
793

564-15-3416
564-15-3424
564-15-3436

 

16
24
36

70
70
70

0.89
1.04
1.18

1.15
1.34
1.51

50
50
60

1.26
1.45
1.65

1.25
1.65
2.14

904
1229
1757

984
1335
1900

Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 392.9

Jackets:  Optional jacket types available - consult local sales office.

Copper or bronze  C-L-X available on special order.

To order C-L-X Type P-OS without the outer Okoseal jacket, change the sixth digit of the catalog number from 3 to 1. For example, to order 1 pr. 20 AWG with a bare aluminum C-L-X, the catalog number would be 564-10-1212.

C-L-X products manufactured in the United States under license granted by Kabelmetal of Hanover, Germany.

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ±15%.


ELECTRICAL SPECIFICATIONS
Per UL Standard 13 & 2250
Conductor Resistance, nominal..................ohms/1000 ft. @20°C
20 AWG...............................................................10.4
18 AWG..................................................................6.5
16 AWG..................................................................4.1
Insulation Test Voltage (spark test).......................5000 Volts ac
Dielectric Test Voltage........................1500 Volts ac for 15 sec.
Shield Isolation Test                                                                     
Pair to Cable Shield..........exceeds 100M ohms/1000 ft.
Insulation Resistance Constant @60°F, minimum                          
(natural material typical value) 2,000 Megohms-1000 ft.
Loop Resistance, nominal (2 conductor)....ohms-1000 ft @20°C
20 AWG...............................................................20.8
18 AWG................................................................13.0
16 AWG..................................................................8.2
Mutual Capacitance (PF/ft.)*                                                         
#20..........................................................................37
#18...........................................................................41
#16...........................................................................44
*Typical Value                                                                               
C/04050510