THE OKONITE COMPANY Product Data
Section 4: Sheet 9

P-30
600V Control Cable

Multiple and Single Conductors/75°C Rating

 
A Bare Stranded Copper Conductor

B Insulation - Okolene - 20 mils - Multiple Conductors 30 mils - Single Conductor

C Conductor Jacket - Okoseal - 10 mils - Multiple conductors 15 mils - Single Conductor

D Binder Tape

E Outer Jacket - Okoseal


Insulation
Okolene® is Okonite's trade name for its natural polyethylene insulation with outstanding dielectric strength. The insulation thickness is 20 mils.

Jackets and Finishes
The 10 mil Okoseal® (PVC) jacket over the individual conductors provides additional mechanical strength. The color coding used in these cables is in accordance with ICEA Standard S-73-532, Table E-1. The six, standard, solid-base colors, in order are: black, white, red, green, orange and blue, followed by permanent tracer colors, black, white, red, and green, to code a total of 21 conductors. Above 21, the sequence is repeated. The Okoseal (PVC) outer jacket supplied with these cables has excellent resistance to oil and most chemicals.

Applications
P-30 control cables are recommended as economical, high quality, general purpose low voltage control cables, for use in wet or dry locations, ac or dc service, in conduit, duct, troughs, or direct burial installations.

Specifications
Conductors: Class "B" stranded bare copper, per ASTM B-8 (except #9 AWG which is Class "C" stranding).
Insulation: Okolene (polyethylene) meets or exceeds applicable requirements of ICEA S-73-532.
Jackets: Meets or exceeds applicable requirements of ICEA S-73-532.
Assembled with fillers where necessary, non-hygroscopic tape and Okoseal jacket overall.

Product Features

  • Color coded for permanent identification.
  • Rated 75°C continuous operating temperature.
  • Small diameter, light weight.
  • Mechanically tough.
  • Excellent moisture and heat resistance.
  • Flexible, easy to handle.
  • Outstanding resistance to most oils, acids and alkalies.
  • High dielectric strength.
  • Excellent electrical properties in wet or dry locations, ac or dc.

 
1-Catalog Number
2-Number of Conductors
3-Size AWG or MCM
4-No. of Strands
5-Outer Jacket Thickness - mils
06-Approx. O.D. - Inches
07-Approx. Net Weight (lbs./1000')

08-Approx. Ship Weight (lbs./1000')
09-Ampacity 75°C (1)

1

2 3 4 5 6 7 8 9

203-84-2051
203-84-2053
203-84-2054

Twin (2)
3
4

16
16
16

7
7
7

45
45
45

.21 x .33
.34
.37

47
64
79

69
87
102

14
14
11

203-84-2055
203-84-2057
203-84-2059

5
7
9

16
16
16

7
7
7

45
45
45

.41
.44
.51

96
122
156

119
145
179

11
10
10

203-84-2062
203-84-2069
203-84-2151

12
19
Twin (2)

16
16
14

7
7
7

60
60
45

.61
.70
.23 x .37

213
311
64

237
343
86

7
7
20

203-84-2153
203-84-2154
203-84-2155

3
4
5

14
14
14

7
7
7

45
45
45

.40
.44
.48

89
111
136

112
134
159

20
16
16

203-84-2157
203-84-2159
203-84-2162

7
9
12

14
14
14

7
7
7

45
60
60

.52
.63
.71

175
244
306

198
276
338

14
14
10

203-84-2169
203-84-2177

19
27

14
14

7
7

60
80

.83
1.03

453
664

492
720

10
9

203-84-2301
203-84-2303
203-84-2304

Twin (2)
3
4

12
12
12

7
7
7

45
45
45

.25 x .41
.44
.48

84
119
150

106
142
173

25
25
20

203-84-2305
203-84-2307
203-84-2308
203-84-2309

5
7
8
9

12
12
12
12

7
7
7
7

45
60
60
60

.52
.60
.65
.70

185
259
292
331

208
283
325
363

20
18
18
18

203-84-2312
203-84-2319

12
19

12
12

7
7

60
80

.78
.96

420
667

459
722

13
13

203-84-2451
203-84-2452
203-84-2453
203-84-2454

Twin (2)
2
3
4

10
10
10
10

7
7
7
7

45
45
45
60

.28 x .46
.46
.49
.57

114
130
164
229

137
153
187
253

35
35
35
28

203-84-2455
203-84-2457
203-84-2458
203-84-2459

5
7
8
9

10
10
10
10

7
7
7
7

60
60
60
60

.62
.68
.73
.79

279
363
411
466

303
395
450
505

28
25
25
25

203-84-2462
203-84-2651

12
Twin (2)

10
9

7
19

80
45

.93
.29 x .48

632
135

687
158

18
42

203-84-2653
203-84-2654
203-84-2655

3
4
5

9
9
9

19
19
19

45
60
60

.53
.61
.66

195
272
331

218
296
363

42
34
34

203-84-2657
203-84-2659
203-84-2662

7
9
12

9
9
9

19
19
19

60
60
80

.72
.84
.99

434
559
756

473
614
820

29
29
21

(1) Ampacities are based on 310-16 of the National Electrical Code for XHHW conductors rated 75°C, in a multi-conductor cable, at an ambient temperature of 30°C (86°F). The 75°C column is provided for additional information.
The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within the cable is in accordance with NEC Section 310-15.