THE OKONITE COMPANY Product Data
Section 4: Sheet 7

Okonite® - FMR® Okolon®
1000/2000 Volt Control Cable
Multiple Copper Conductors/90°C Rating
For Central Station Applications

 
A Coated, Stranded Copper Conductors

B Okonite-FMR Insulation

C Marker Strip

D Flame and Moisture Resistant Fillers

E Cable Tape

F Okolon Jacket


Insulation
Okonite-FMR is Okonite's trade name for its heat, moisture, flame and chemically resistant, mechanically rugged ethylene-propylene insulation compound. It is flame retardant and will pass both the 70,000 BTU/hour and 210,000 BTU/hour tray flame test. Its physical properties and flame retardency permit its use without a jacket on the single conductors thus providing a substantially smaller overall diameter control cable.

The properties of Okonite-FMR insulation substantially enhance the well known features of ethylene propylene rubber insulations.

Nuclear qualified Okonite/FMR cables that meet IEEE Standard - 383 and LOCA criteria are available on special order.

Overall Jacket
The overall jacket is a vulcanized chlorosulfonated polyethylene compound. This combination construction assures circuit security because of its high mechanical strength and excellent resistance to moisture, ozone, oil and most chemicals.

Applications
Okonite-FMR Control Cables are recommended for use in either power generating plants and in substations; designed especially for critical circuits where continuity of service is of prime importance. This premium quality control cable is recommended for wet or dry, ac or dc service at conductor temperatures to 90°C. They may be installed in conduits, ducts, cable troughs, trays, messenger supported, or directly buried in the earth.

Specifications
Conductors: Coated copper per ASTM B-33, Class B stranded per ASTM B-8.

Insulation: Okonite-FMR meets or exceeds the electrical and physical requirements of ICEA S-73-532.

Color Coding: Base Colors and tracers per ICEA Method 1 Table E-1. Sequence shown bellow.

Assembly: Conductors cabled using flame and moisture resistant fillers.

Overall Jacket: The Okolon compound meets or exceeds the requirements of ICEA S-73-532.

Product Features

  • Flame retardant - passes the IEEE 383 and 1202 flame test requirements. Also passes the ICEA T-29-520 (210,000 BTU/hr) flame test.
  • Quality Assurance traceability available on special order.
  • 90°C rated control cable, factory assembled for indoor or outdoor installation in cable trays, in raceways, direct burial in the earth, or supported by messenger wire.
  •  Mechanically rugged.
  • Flexible, easy to install and terminate.
  • Color coded conductors.
  • Resistant to water, oil and most chemicals.
  • Thermally stable at elevated temperatures.
  • High insulation resistance, even at elevated temperatures.
  • Small diameter, lightweight.

 
1-Catalog Number
2-Conductor Size (AWG)
3-Number of Conductors
4-Insulation Thickness - mils
5-Jacket Thickness - mils
6-Jacket Thickness - mm
07-Approx. O.D. - Inches
08-Approx. O.D. - mm
09-Approx. Net Weight (lbs./1000')

10-Approx. Ship Weight (lbs./1000')
11-90°C Wet or Dry Ampacity 
(1)

1

2 3 4 5 6 7 8 9 10 11

1000V

202-14-2052
202-14-2053
202-14-2054

16 (7x)
1.31 mm2

2
3
4

45
1.14 mm

45
45
45

1.14
1.14
1.14

0.42
0.44
0.48

10.65
11.28
12.30

84
99
125

107
122
148

18
18
14

202-14-2055
202-14-2057
202-14-2059

5
7
9

45
60
60

1.14
1.52
1.52

0.53
0.60
0.70

13.39
15.24
17.76

155
223
278

178
247
310

14
13
13

202-14-2062
202-14-2069
202-14-2087

12
19
37

60
80
80

1.52
2.03
2.03

0.78
0.96
1.27

19.92
24.27
32.26

342
526
910

381
581
1000

9
9
7

2000V

202-14-2152
202-14-2153
202-14-2154

14 (7x)
2.08 mm2

2
3
4

45
1.14 mm

45
45
45

1.14
1.14
1.14

0.45
0.47
0.52

11.36
12.05
13.16

99
120
177

122
143
200

25
25
20

202-14-2155
202-14-2157
202-14-2159

5
7
9

60
60
60

1.52
1.52
1.52

0.60
0.65
0.75

15.16
16.44
19.05

209
277
344

233
309
383

20
18
18

202-14-2162
202-14-2169
202-14-2187

12
19
37

60
80
80

1.52
2.03
2.03

0.84
1.03
1.37

21.39
26.05
34.80

426
657
1161

465
712
1251

13
13
10

202-14-2302
202-14-2303
202-14-2304

12 (7x)
3.33 mm2

2
3
4

45
1.14 mm

45
45
60

1.14
1.14
1.52

0.48
0.51
0.59

12.28
13.03
15.08

163
182
244

186
205
268

30
30
24

202-14-2305
202-14-2307
202-14-2309

5
7
9

60
60
60

1.52
1.52
1.52

0.64
0.70
0.81

16.26
17.82
20.70

298
357
447

330
389
486

24
21
21

202-14-2312
202-14-2319
202-14-2337

12
19
37

80
80
80

2.03
2.03
2.03

0.96
1.12
1.50

24.36
28.33
38.10

604
855
1538

659
935
1681

15
15
12

202-14-2452
202-14-2453
202-14-2454

10 (7x)
5.26 mm2

2
3
4

45
1.14 mm

45
60
60

1.14
1.52
1.52

0.53
0.60
0.65

13.50
15.16
16.55

208
260
322

232
284
354

40
40
32

202-14-2455
202-14-2457
202-14-2459
202-14-2462

5
7
9
12

60
60
80
80

1.52
1.52
2.03
2.03

0.71
0.77
0.94
1.06

18.04
19.65
23.97
26.90

388
478
641
800

420
517
696
867

32
28
28
20

202-14-2652
202-14-2653
202-14-2654

9 (19x)
6.63 mm2

2
3
4

45
1.14 mm

60
60
60

1.52
1.52
1.52

0.59
0.62
0.68

14.97
15.75
17.35

262
298
369

286
322
401

50
50
40

202-14-2655
202-14-2657
202-14-2659
202-14-2662

5
7
9
12

60
60
80
80

1.52
1.52
2.03
2.03

0.74
0.81
0.99
1.11

18.80
20.64
25.16
28.27

452
557
797
940

491
596
852
1020

40
35
35
25

Minimum Manufacturing Quantity is: 2 to 7 conductors - 10,000 ft.: 9 plus conductors - 5000'.

Nuclear Traceability available on special order.

(1) Ampacities are based on 90°C rated conductors at an ambient temperature of 30°C. 

COLOR CODE

No. of
Cond.

Base
Color

Tracer
Color

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

Black
White
Red
Green
Orange
Blue
White
Red
Green
Orange
Blue
Black
Red
Green
Blue
Black
White
Orange
Blue







Black
Black
Black
Black
Black
White
White
White
White
Red
Red
Red
Red