THE OKONITE COMPANY Product Data
Section 4: Sheet 2

Okonite® - FMR-LCS® Okolon®
600 Volt Shielded Control Cable
Multiple Copper Conductors/90°C Rating
For Central Station Applications

 
A Coated, Stranded Copper Conductors

B Okonite-FMR Insulation

C Marker Strip

D Extruded Fill and Belt

E 5 mil Longitudinal Corrugated Coated Copper Shield

F Okolon Jacket


Insulation
Okonite-FMR is Okonite’s trade name for its heat, moisture, flame and chemically resistant, mechanically rugged ethylene-propylene insulation compound. It is flame retardant and will pass both the 70,000 BTU/hour and 210,000 BTU/hour tray flame test. Its physical properties and flame retardancy permit its use without a jacket on the single conductors thus providing a substantially smaller overall diameter control cable.

The properties of Okonite-FMR insulation substantially enhance the well known features of ethylene propylene rubber insulations.

Nuclear qualified Okonite/FMR cables that meet IEEE Standard - 383 and LOCA criteria are available on special order.


Shield
The shield system consists of a 5 mil copper tape which is longitudinally applied over the extruded belt and fill. The Longitudinal Corrugated Shield (LCS) maintains uniformly low resistance and a low reactance path for optimum shielding against external high frequency interference.

Overall Jacket
The Okolon jacket is a vulcanized chlorosulfonated polyethylene compound. This combination construction assures circuit security because of its high mechanical strength and excellent resistance to moisture, ozone, oil and most chemicals.

Applications
Okonite-FMR Control Cables are recommended for use in either power generating plants and in substations; designed especially for critical circuits where continuity of service is of prime importance. This premium quality control cable is recommended for wet or dry, ac or dc service at conductor temperatures to 90°C where electrostatic shielding is required. They may be installed in conduits, ducts, cable troughs, trays, messenger supported, or directly buried in the earth.

Specifications
Conductors:
Coated copper per ASTM B-33, Class B stranded per ASTM B-8.

Insulation: Okonite-FMR meets or exceeds the electrical and physical requirements of ICEA S-75-532.

Color Coding: Base colors and tracers per ICEA Method 1 Table E-1.  Sequence shown bellow.

Assembly: Conductors cabled using flame and moisture resistant fillers.

Overall Jacket: The Okolon compound meets or exceeds the requirements of ICEA S-75-532

Product Features

  • Flame retardant - passes the IEEE 383 and 1202 flame test requirements. Also passes the ICEA T-29-520 (210,000 BTU/hr) flame test.
  • Quality Assurance traceability available on special order.
  • 90°C rated control cable, factory assembled for indoor or outdoor installation in cable trays, in raceways, direct burial in the earth, or supported by messenger wire.
  • Mechanically rugged.
  • Flexible, easy to install and terminate.
  • Color coded conductors.
  • Resistant to water, oil and most chemicals.
  • Thermally stable at elevated temperatures.
  • High insulation resistance, even at elevated temperatures.
  • Small diameter, light weight.

 
1-Catalog Number
2-Conductor Size - AWG
3-Number of Conductors
4-Insulation Thickness - mils
5-Jacket Thickness - mils
6-Jacket Thickness - mm
07-Approx. O.D. - Inches
08-Approx. O.D. - mm
09-Approx. Net Weight (lbs./1000')
10-Approx. Ship Weight (lbs./1000')
11-90°C Wet or Dry Ampacity (1)
1 2 3 4 5 6 7 8 9 10 11

202-10-6052
202-10-6053
202-10-6054

16 (7x)
1.31 mm2

 

2
3
4

25
0.64 mm

 

60
60
60

1.52
1.52
1.52

0.67
0.67
0.67

17.02
17.02
17.02

262
270
275

294
302
307

18
18
14

202-10-6055
202-10-6057
202-10-6059

5
7
9

60
60
60

1.52
1.52
1.52

0.67
0.67
0.67

17.02
17.02
17.02

279
292
294

311
324
326

14
13
13

202-10-6062
202-10-6069
202-10-6087

12
19
37

60
60
80

1.52
1.52
2.03

0.74
0.83
1.13

18.72
21.11
28.78

356
476
858

411
543
964

9
9
7

202-10-6152
202-10-6153
202-10-6154

14 (7x)
2.08 mm2

2
3
4

30
0.76 mm

60
60
60

1.52
1.52
1.52

0.67
0.67
0.67

17.02
17.02
17.02

262
275
283

294
307
315

25
25
20

202-10-6155
202-10-6157
202-10-6159

5
7
9

60
60
60

1.52
1.52
1.52

0.67
0.68
0.77

17.02
17.27
19.45

289
315
387

321
347
442

20
18
18

202-10-6162
202-10-6169
202-10-6187

12
19
37

60
80
80

1.52
2.03
2.03

0.84
1.00
1.28

21.36
25.35
32.51

468
687
1149

535
754
1292

13
13
10

202-10-6302
202-10-6303
202-10-6304

12 (7x)
3.31 mm2

2
3
4

30
0.76 mm

60
60
60

1.52
1.52
1.52

0.67
0.67
0.67

17.02
17.02
17.02

269
288
303

301
320
335

30
30
24

202-10-6305
202-10-6307
202-10-6309

5
7
9

60
60
60

1.52
1.52
1.52

0.67
0.74
0.83

17.02
18.69
21.10

326
396
487

358
451
554

24
21
21

202-10-6312
202-10-6319
202-10-6337

12
19
37

80
80
80

2.03
2.03
2.03

0.96
1.09
1.43

24.33
27.64
36.42

642
892
1567

709
998
1731

15
15
12

202-10-6452
202-10-6453
202-10-6454

10 (7x)
5.26 mm2

2
3
4

30
0.76 mm

60
60
60

1.52
1.52
1.52

0.67
0.67
0.70

17.02
17.02
17.89

280
310
356

312
342
388

40
40
32

202-10-6455
202-10-6457
202-10-6459
202-10-6462

5
7
9
12

60
60
80
80

1.52
1.52
2.03
2.03

0.75
0.81
0.96
1.06

19.16
20.52
24.36
26.86

416
518
684
851

471
573
751
941

32
28
28
20

202-10-6652
202-10-6653
202-10-6654

9 (7x)
6.63 mm2

2
3
4

30
0.76 mm

60
60
60

1.52
1.52
1.52

0.67
0.69
0.74

17.02
17.02
18.69

288
333
404

320
365
459

50
50
40

202-10-6655
202-10-6657
202-10-6659
202-10-6662

5
7
9
12

60
60
80
80

1.52
1.52
2.03
2.03

0.79
0.89
1.01
1.11

20.05
22.61
25.56
28.24

473
633
787
981

528
700
877
1087

40
35
35
25

Minimum Manufacturing Quantity: For non-stock items - 5000'. Nuclear traceability on special order.

(1) Ampacities are based on 90°C rated conductors at an ambient temperature of 30°C. 

COLOR CODE

No. of
Cond.

Base
Color

Tracer
Color

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

Black
White
Red
Green
Orange
Blue
White
Red
Green
Orange
Blue
Black
Red
Green
Blue
Black
White
Orange
Blue







Black
Black
Black
Black
Black
White
White
White
White
Red
Red
Red
Red


| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |