THE OKONITE COMPANY Product Data
Section 4: Sheet 1
3


Okonite® FMR-N® Okolon®
1000/2000 Volt Control Cable
Multiple Copper Conductors/90°C Rating
For Central Station Applications
 

  
A  Stranded Copper Conductors

B  Okonite FMR-N Insulation

C  Marker Strip

D  Flame and Moisture Resistant Fillers (as needed)

E  Cable Tape

F  Okolon Jacket


Insulation
Okonite FMR-N is Okonite’s trade name for its heat, moisture, flame and chemically resistant, mechanically rugged nuclear plant qualified ethylene-propylene insulation compound. Its physical properties and flame retardency permit its use without a jacket on the single conductors.
The properties of Okonite FMR-N insulation substantially enhance the well known features of ethylene propylene rubber insulations.
Nuclear qualified Okonite FMR-N cables meet IEEE Standard - 383 LOCA and flame test criteria.


Overall Jacket

The overall jacket is a vulcanized chlorosulfonated polyethylene compound. This combination construction assures circuit security because of its high mechanical strength and excellent resistance to moisture, ozone, oil and most chemicals.

Applications
Okonite FMR-N Control Cables are recommended for use in either power generating plants and in substations; designed especially for critical circuits where continuity of service is of prime importance. This premium quality control cable is recommended for wet or dry, ac or dc service at conductor temperatures to 90°C. They may be installed in conduits, ducts, cable troughs, trays, messenger supported, or directly buried in the earth.

Specifications
Conductors: Copper per ASTM B-3, Class B stranded per ASTM B-8.

Insulation: Okonite FMR-N meets or exceeds the electrical and physical requirements of ICEA S-73-532.

Color Coding: Base colors and tracers per ICEA Method 1 Table E-1 color sequence shown on reverse of this sheet.

Assembly: Conductors cabled using flame and moisture resistant fillers.

Overall Jacket: The Okolon compound meets or exceeds the requirements of ICEA S-73-532

Product Features

  • Qualified as Class 1E cable.
  • Flame retardant - passes the IEEE 383 and 1202 flame test requirements.
  • Quality Assurance traceability.
  • 90°C rated control cable, factory assembled for indoor or outdoor installation in cable trays, in raceways, direct burial in the earth, or supported by messenger wire.
  • Mechanically rugged.
  • Flexible, easy to install and terminate.
  • Color coded conductors.
  • Resistant to water, oil and most chemicals.
  • Thermally stable at elevated temperatures.
  • High insulation resistance, even at elevated temperatures.
  • Small diameter, lightweight.

1- Catalog Number
2- Conductor Size (AWG)
3- Number of Conductors
4- Insulation Thickness-mils
5- Jacket Thickness - mils
6- Jacket Thickness - mm
  7- Approx O.D. - Inches 
  8- Approx O.D. - mm
  9- Approx Net Weight (lbs/1000’)
10- Approx Ship Weight (lbs/1000’)
11- 90°C Wet or Dry Ampacity (1)
1 2 3 4 5 6 7 8 9 10 11

1000V

202-18-2053
202-18-2054

16 (7x)
1.31 mm2

3
4

45
1.14 mm

45
45

1.14
1.14
0.49
0.53
12.5
13.6
132
164
145
180
16
14

202-18-2055
202-18-2057
202-18-2059

5
7
9

60
60
60

1.52
1.52
1.52
0.61
0.66
0.75
15.6
16.7
19.1
210
248
330
234
280
369
13
10
9

202-18-2062
202-18-2069
202-18-2087

12
19
37

60
80
80

1.52
2.03
2.03
0.84
1.01
1.32
21.3
25.7
33.5
381
562
958
436
622
1048
7
6
4

2000V 

202-18-2152
202-18-2153
202-18-2154

14 (7x)
2.08 mm2

2
3
4

45
1.14 mm

45
45
60

1.14
1.14
1.52
0.50
0.52
0.60
12.6
13.3
15.2
127
155
210
140
171
228
25
21
19

202-18-2155
202-18-2157
202-18-2159

5
7
9

60
60
60

1.52
1.52
1.52
0.65
0.70
0.80
16.5
17.8
20.4
260
297
399
292
336
438
17
14
12

202-18-2162
202-18-2169
202-18-2187

12
19
37

80
80
80

2.03
2.03
2.03
0.94
1.08
1.42
23.9
27.4
36.0
508
703
1217
563
770
1360
10
8
6

202-18-2302
202-18-2303
202-18-2304

12 (7x)
3.33 mm2

2
3
4

45
1.14 mm

45
60
60

1.14
1.52
1.52
0.53
0.60
0.65
13.5
15.2
16.4
159
221
261
175
245
293
32
27
24

202-18-2305
202-18-2307
202-18-2309

5
7
9

60
60
80

1.52
1.52
2.03
0.70
0.76
0.91
17.8
19.2
23.1
321
391
543
360
430
598
22
19
16

202-18-2312
202-18-2319
202-18-2337

12
19
37

80
80
80

2.03
2.03
2.03
1.01
1.17
1.54
25.8
29.7
39.2
638
909
1605
705
989
1748
14
11
8

202-18-2452
202-18-2453
202-18-2454

10 (7x)
5.26 mm2

2
3
4

45
1.14 mm

60
60
60

1.52
1.52
1.52
0.62
0.65
0.71
15.7
16.5
17.9
228
274
332
252
306
371
42
35
32

202-18-2455
202-18-2457
202-18-2459
202-18-2462

5
7
9
12

60
60
80
80

1.52
1.52
2.03
2.03
0.76  0.83
1.00
1.11
19.4
21.0
25.4
28.3
405
507
725
860
444
562
789
940
28
23
20
17

202-18-2652
202-18-2653
202-18-2654

9 (7x)
6.63 mm2

2
3
4

45
1.14 mm

60
60
60

1.52
1.52
1.52
0.64
0.68
0.74
16.3
17.2
18.7
252
307
389
284
339
428
49
40
36

202-18-2655
202-18-2657
202-18-2659
202-18-2662

5
7
9
12

60
80
80
80

1.52
2.03
2.03
2.03
0.80
0.91
1.05
1.17
20.3
23.1
26.5
29.7
464
621
827
986
503
676
891
1066
32
27
23
20
 

(1) Ampacities are based on one cable in conduit in air, 90°C rated conductor & 40° C ambient.

For cables installed in cable tray, see ANSI/ICEA P54-440 (NEMA WC 51-2003).

COLOR CODE 

No. of
Cond. 

Base
Color 

Tracer
Color 

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19 

Black
White
Red
Green
Orange
Blue
White
Red
Green
Orange
Blue
Black
Red
Green
Blue
Black
White
Orange
Blue 







Black
Black
Black
Black
Black
White
White
White
White
Red
Red
Red
Red 


| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |