A Nickel Coated Copper Power
Conductors
B Okotherm (Silicone) Thermoset
Insulation
C Fiberglass Braid - Coded per
ICEA
D Glass Fillers
E Flame Retardant Binder Tape
F Impervious, Continuous,
Corrugated, Aluminum C-L-X Sheath
G Black Okoseal Jacket
Cable Description
Nickel coated copper conductors, Okotherm CIC fire resistant thermoset
silicone insulation, color or number coded fiber glass braid, cabled
conductors, optional grounding conductor, fire resistant cable tape,
aluminum CLX sheath, Okoseal (PVC) jacket.
Conductors: Nickel Coated
Copper
Insulation: Okotherm Thermoset Silicone
Color Code: ICEA
Braid: Fiber Glass Braid
Armor-CLX: Continuously Welded and Corrugated Aluminum Outer
Jacket: Black PVC
Applicable Industry Standards:
— UL 1569, 1309, & 2250 — ICEA S-73-532 (NEMA WC 57) — ASTM B-33 & B-355
Flame Tests:
IEC 60331, ICEA T-29-520, IEEE 1202
Applications
Okotherm CIC 600 volt control cables are used in systems where, in the event of
a fire, circuit integrity is required in order to maintain a process or to
safely shut down the process. Fire resistance is determined by compliance to the
IEC 60331 circuit integrity fire test. Okotherm CIC cables maintain circuit
integrity based on qualification to IEC standard 60331, 750°C
for 90 minutes. When exposed to a fire,
the Okotherm CIC insulation becomes an electrically insulating ceramic-like ash
that is capable of maintaining the operating voltage.
Okotherm CIC CLX Type MC cables with the impervious, continuous aluminum
corrugated sheath are recommended as an alternative to a wire conduit system.
These cables may be installed indoors or outdoors, in wet or dry locations, as
open runs of cable secured to supports not more than six feet apart, in cable
tray, as an aerial cable on a messenger, in any approved raceway, direct burial,
or encased in concrete. They are also approved for use in Class I & II, Division
2, Class III, Division 1 and 2 and Class I, Zones 1 & 2 hazardous locations per
NEC Articles 501, 502, 503, and 505. They are listed by the American Bureau of
Shipping (ABS) as CWCMC-CLXM and by UL as marine shipboard cable.
Okotherm CIC CLX Type MC control cables are authorized for use on services,
feeders and branch circuits for power, lighting, control and signaling circuits
in accordance with NEC articles 330 and 725.
Product Features
- UL Listed as Type MC cable and Marine Shipboard Cable, E38916 and
E137931.
- UL Listed for cable tray use, direct burial and sunlight resistant.
- Passes the IEEE 383-1974 and IEEE 1202-1991 vertical tray flame
tests.
- Passes the 210,000 BTU ICEA T-29-520 Vertical Tray Flame Test.
- Complete pre-packaged, factory-tested wiring system — color coded.
- C-L-X cables are quality control inspected to meet or exceed
applicable UL standards.
- 90°C continuous operating temperature in all types of installations.
- 130°C emergency rating.
- 250°C short circuit rating.
- Good EMI shielding characteristics.
- Impervious, continuous metallic sheath excludes moisture, gases and
liquids.
- Reduced sealing fitting requirements in Class I, Division 2 or Zone
2 hazardous locations (NEC Section 501.5(E) or 505.15(C).
- Lower installed system cost than conduit or EMT systems.
- Provides excellent grounding safety.
- Excellent compression and impact resistance.
- Continuous long lengths
- Minimum installation temperature of -40°C or °F.
- American Bureau of Shipping listed as CWCMC Type MC.
- Conforms to applicable requirements of IEEE 1580.
- Fire Resistant - 750°C for 90 minutes
per IEC 60331.
|