THE OKONITE COMPANY Product Data
Section 4: Sheet 10

P-45
1000V Control Cable

Multiple Conductors/75°C Rating

 
A Bare Stranded Copper Conductor

B Insulation - Okolene - 30 mils

C Conductor Jacket - Okoseal - 150 mils

D Binder Tape

E Outer Jacket - Okoseal


Insulation
Okolene® is Okonite's trade name for its natural polyethylene insulation with outstanding dielectric strength. The insulation thickness is 30 mils.

Jackets and Finishes
The 15 mil Okoseal® (PVC) jacket over the individual conductors provides additional mechanical strength. The color coding used in these cables is in accordance with ICEA Standard S-73-532, Table E-1. The six, standard, solid-base colors, in order are: black, white, red, green, orange and blue, followed by permanent tracer colors, black, white, red, and green, to code a total of 21 conductors. The Okoseal (PVC) outer jacket supplied with these cables has excellent resistance to oil and most chemicals.

Applications
P-45 control cables are recommended as economical, high quality, general purpose low voltage control cables, for use in wet or dry locations, ac or dc service, in conduit, duct, troughs, or direct burial installations.

Specifications
Conductors: Class "B" stranded bare copper, per ASTM B-8 (except #9 AWG which is Class "C" stranding).
Insulation: Okolene (polyethylene) meets or exceeds applicable requirements of ICEA S-73-532.
Jackets: Meets or exceeds applicable requirements of ICEA S-73-532.
Assembled with fillers where necessary, non-hygroscopic tape and Okoseal jacket overall.

Product Features

  • Color coded for permanent identification.
  • Rated 75°C continuous operating temperature.
  • Small diameter, light weight.
  • Mechanically tough.
  • Excellent moisture and heat resistance.
  • Flexible, easy to handle.
  • Outstanding resistance to most oils, acids and alkalies.
  • High dielectric strength.
  • Excellent electrical properties in wet or dry locations, ac or dc.

 
1-Catalog Number
2-Number of Conductors
3-Size AWG or MCM
4-No. of Strands
5-Outer Jacket Thickness - mils
06-Approx. O.D. - Inches
07-Approx. Net Weight (lbs./1000')

08-Approx. Ship Weight (lbs./1000')
09-Ampacity 75°C (1)

1

2 3 4 5 6 7 8 9

203-84-3301
203-84-3330
203-84-4330

Twin (2)
3
4

12
12
12

7
7
7

45
45
60

.29 x .48
.51
.59

97
138
192

120
161
216

25
25
20

203-84-3305
203-84-3307
203-84-3309

5
7
9

12
12
12

7
7
7

60
60
60

.64
.70
.81

236
302
388

268
334
427

20
18
18

203-84-3312
203-84-3651
203-84-3653

12
Twin (2)
3

12
9
9

7
19
19

80
60
60

.96
.33 x .56
.63

527
150
236

582
173
260

13
42
42

203-84-3654
203-84-3655
203-84-3657

4
5
7

9
9
9

19
19
19

60
60
60

.69
.75
.82

304
371
484

336
410
523

34
34
29

203-84-3659
203-84-3662

9
12

9
9

19
19

80
80

1.00
1.13

664
842

728
922

29
21

 (1) Ampacities are based on 310-16 of the National Electrical Code for XHHW conductors rated 75°C, in a multi-conductor cable, at an ambient temperature of 30°C (86°F). 
The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within the cable is in accordance with NEC Section 310-15.