THE OKONITE COMPANY Product Data
Section 3: Sheet 5
X-Olene®
Type XHHW-2
600V Power and Control
Copper Conductor/90°C Wet or Dry
UL
A Bare, Solid or Stranded Copper Conductor

B X-Olene Insulation


Insulation

X-Olene is Okonite's trade name for its chemically cross-linked polyethylene insulating compound with outstanding electrical and physical properties. Its excellent chemical physical resistance permits X-Olene's use in areas exposed to alcohol, ketones and dilute acids and bases, without additional coverings.

Applications
X-Olene Type XHHW-2 600 Volt Cables are recommended for general low voltage power and control applications. Where the National Electrical Code applies, Type XHHW-2 may be used up to 90°C in wet or dry locations. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, or lashed to a messenger for aerial installation.

Specifications
Conductor: Bare, solid or stranded copper per ASTM B-3 or B-8.

Insulation: Meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70, and UL Standards.

Listed by Underwriters Laboratories, Inc. as Type XHHW-2.

 

Product Features
  • Small diameter, permits use of smaller conduit or more wires per conduit.
  • Excellent heat resistance.
  • Rated 90°C in wet or dry locations.
  • Mechanically rugged.
  • Stable electrical properties.
  • Low moisture absorption.
  • Highly resistant to weather and most chemicals.
  • UL Listed.

1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Number of Strands
4-Insulation Thickness - mils
5-Insulation Thickness - mm
6-Approx.O.D. - Inches
07-Approx.O.D. - mm
08-Approx. Net Weight lbs./1000'
09-Approx. Ship Weight lbs./1000'
10-90°C Wet(1) NEC Ampacity
11-75°C Wet(1) NEC Ampacity
12-ICEA Ampacity(2)
1 2 3 4 5 6 7 8 9 10 11 12

112-31-3061
112-31-3071
112-31-3101

14
14
12

1
7
1

30
30
30

.76
.76
.76

.13
.14
.15

3.30
3.56
3.81

17
18
25

21
22
29

15
15
20

15
15
20

24
24
30

112-31-3111
112-31-3141
112-31-3151

12
10
10

7
1
7

30
30
30

.76
.76
.76

.15
.17
.18

3.81
4.32
4.57

26
38
40

30
42
44

20
30
30

20
30
30

30
42
42

112-31-3221
112-31-3231
112-31-3271

8
8
6

1
7
7

45
45
45

1.14
1.14
1.14

.24
.24
.28

6.10
6.10
7.11

64
67
100

72
75
108

55
55
75

50
50
65

55
55
75

112-31-3311
112-31-3371
112-31-3401

4
2
1

7
7
19

45
45
55

1.14
1.14
1.40

.32
.38
.44

8.13
9.65
11.2

150
231
294

158
245
328

95
130
150

85
115
130

97
130
156

112-31-3421
112-31-3441
112-31-3461

1/0
2/0
3/0

19
19
19

55
55
55

1.40
.53
.58

.48
.53
.58

12.2
13.5
14.7

365
454
566

382
484
586

170
195
225

150
175
200

179
204
242

112-31-3481
112-31-3511
112-31-3541

4/0
250
350

19
37
37

55
65
65

.64
.71
.81

.63
.70
.81

16.0
17.8
20.6

706
839
1158

749
882
1233

260
290
350

230
255
310

278
317
384

112-31-3581
112-31-3641
112-31-3701

500
750
1000

37
61
61

65
80
80

.94
1.15
1.30

.98
1.14
1.36

24.9
29.0
34.5

1632
2447
3233

1710
2555
3378

430
535
615

380
475
545

477
598
689

Minimum Manufacturing Quantity: 10,000 ft.
To order a color other than black, change the last digit of the catalog number as follows:
White 2
Red 3
Green 4
Orange 5
Blue 6
Yellow 7
Example: To order #14/SOL - Red, the catalog number would be 112-31-3063.
Ampacities

(1) Ampacities are based on Table 310-16 of the National Electrical Code for these 90°C rated conductors at an ambient temperature of 30°C. The 75°C wet column is provided for additional information.

The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within a raceway is in accordance with Note 8 to NEC Tables 310-16 through 310-19.

(2) Based on three (3) conductors in a single enclosed or exposed conduit. Capacities based on 40°C air ambient using ICEA methods. For 30°C ambient multiply values by 1.10; for 50°C multiply by .90. For other ambients or installation conditions refer to Okonite's Engineering Data Book EHB-90.

The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 318-11.

C/01060305