THE OKONITE COMPANY Product Data
Section 3: Sheet 4
X-Olene®
Type RHH or RHW-2, or USE-2
600V Power and Control
Copper Conductor/90°C Wet or Dry
Sunlight Resistant - For Direct Burial
UL *
A Bare, Solid or Stranded Copper Conductor

B X-Olene Insulation


Insulation

X-Olene is Okonite's trade name for its chemically cross-linked polyethylene insulating compound with outstanding electrical and physical properties. Its excellent chemical physical resistance permits X-Olene's use in areas exposed to alcohol, ketones and dilute acids and bases, without additional coverings.

Applications
X-Olene Type RHH or RHW-2 or USE-2 600 Volt Power and Control Cables are recommended for general low voltage power and control applications. Where the National Electrical Code applies, Type RHH or RHW-2 or USE-2 may be used up to 90°C in dry or wet locations. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, directly buried in the earth, or lashed to a messenger for aerial installation.

Specifications
Conductor: Bare, solid or stranded copper per ASTM B-3 or B-8.

Insulation: Meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70, and UL Standards 44 and 854.

Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2 or USE-2.

CSA* rated RW90.

* On Special Request.

Product Features
  • Outstanding heat resistance.
  • Rated 90°C wet or dry.
  • Mechanically rugged.
  • Stable electrical properties.
  • Low moisture absorption.
  • Highly resistant to weather and most chemicals.
  • UL Listed.

1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Number of Strands
4-Insulation Thickness - mils
5-Insulation Thickness - mm
6-Approx.O.D. - Inches
07-Approx.O.D. - mm
08-Approx. Net Weight lbs./1000'
09-Approx. Ship Weight lbs./1000'
10-90°C Wet(1) NEC Ampacity
11-75°C Wet(1) NEC Ampacity
12-ICEA Ampacity(2)
1 2 3 4 5 6 7 8 9 10 11 12

112-32-3061
112-32-3071
112-32-3101

14
14
12

1
7
1

45
45
45

1.14
1.14
1.14

.16
.17
.19

4.06
4.32
4.57

21
25
29

23
27
31

15
15
20

15
15
20

24
24
30

112-32-3111
112-32-3141
112-32-3151

12
10
10

7
1
7

45
45
45

1.14
1.14
1.14

.20
.20
.21

4.83
5.08
5.33

34
43
45

36
45
47

20
30
30

20
30
30

30
42
42

112-32-3231
112-32-3271
112-32-3311

8
6
4

7
7
7

60
60
60

1.52
1.52
1.52

.27
.31
.35

6.86
7.87
9.14

71
105
158

78
115
168

55
75
95

30
65
85

55
75
97

112-32-3371
112-32-3401
112-32-3421

2
1
1/0

7
19
19

60
80
80

1.52
2.03
2.03

.41
.49
.53

10.67
12.45
13.46

240
312
384

254
328
414

130
150
170

115
130
150

130
156
179

112-32-3441
112-32-3461
112-32-3481

2/0
3/0
4/0

19
19
19

80
80
80

2.03
2.03
2.03

.58
.63
.68

14.73
16.00
17.53

475
588
730

507
631
773

195
225
260

175
200
230

204
242
278

112-32-3511
112-32-3521
112-32-3541

250
300
350

37
37
37

95
95
95

2.41
2.41
2.41

.76
.81
.86

19.56
20.83
22.10

872
1032
1195

912
1107
1270

290
320
350

255
285
310

317
351
384

112-32-3581
112-32-3641
112-32-3701

500
750
1000

37
61
61

95
110
110

2.41
2.79
2.79

.92
1.20
1.35

25.40
31.00
34.80

1620
2499
3292

1728
2644
3437

430
535
615

380
475
545

477
598
689

Minimum Manufacturing Quantity: 50,000 ft.
To order a color other than black, change the last digit of the catalog number as follows:
White 2
Red 3
Green 4
Orange 5
Blue 6
Yellow 7
Example: To order #14/SOL - Red, the catalog number would be 112-32-3063.
Ampacities

(1) Ampacities are based on Table 310-16 of the National Electrical Code for these 90°C rated conductors at an ambient temperature of 30°C. The 75°C wet column is provided for additional information.

The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within a raceway is in accordance with Note 8 to NEC Tables 310-16 through 310-19.

(2) Based on three (3) conductors in a single enclosed or exposed conduit. Capacities based on 40°C air ambient using ICEA methods. For 30°C ambient multiply values by 1.10; for 50°C multiply by .90. For other ambients or installation conditions refer to Engineering Data Book EHB-90.

The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 318-11.

C/01050304
BACK TO DATA SHEET INDEX