THE OKONITE COMPANY Product Data
Section 3: Sheet 3
Okonite-FMR®
Type RHH or RHW-2, VW-1
600V Power and Control
Copper Conductor/90°C Wet or Dry
UL
A Coated Copper Conductor

B Okonite-FMR Insulation


Insulation
Okonite-FMR is Okonite's trade name for its heat resistant, mechanically rugged black pigmented ethylene-propylene base insulating compound.

Applications
Okonite-FMR Type RHH or RHW-2 600 Volt Power and Control Cables are recommended for general low voltage power and control applications. Okonite-FMR flame retardant insulated power cables may be used in generating plants, either nuclear or fossil fueled, substations and industrial plants. Type RHH or RHW-2 may be used up to 90°C in dry or wet locations. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, cable tray (size 1/0 AWG and larger per NEC 318-3) or lashed to a messenger for aerial installation.

Specifications
Conductor: Coated copper per ASTM B-33 Class B stranded per ASTM B-8; solid per ASTM B-3.

Insulation: Meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70, IEEE Standard 383, and UL 44.

Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2, VW-1.

Product Features
  • Sizes 1/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL 1581 for use in cable tray.
  • Passes the ICEA T-29-520 210,000 Btu/hr. vertical tray flame test (sizes 6 AWG and larger).
  • Passes the IEEE 383-1974 Vertical Tray Flame Test.
  • Passes the IEEE 1202-1991 Vertical Tray Flame Test. (sizes 1/0 AWG and larger).
  • Extreme heat resistance 90°C continuous rating; 130°C emergency overload rating; 250°C short circuit rating.
  • Rated 90°C wet or dry.
  • Exceptional resistance to deformation at high temperatures.
  • Stable electrical properties.
  • Low SIC and power factor.
  • Low moisture absorption.
  • Mechanically rugged.
  • Resistant to weather.
  • Smaller diameter.
  • More flexible, easier to install, terminate, or splice than XLPE insulation.
  • Flame retardant.
  • UL Listed, UL Rated VW-1.

1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Number of Strands
4-Insulation Thickness - mils
5-Insulation Thickness - mm
6-Approx.O.D. - Inches
07-Approx.O.D. - mm
08-Approx. Net Weight lbs./1000'
09-Approx. Ship Weight lbs./1000'
10-90°C Wet(1) NEC Ampacity
11-75°C Wet(1) NEC Ampacity
12-ICEA Ampacity(2)
1 2 3 4 5 6 7 8 9 10 11 12
112-09-1061 14 1 45 1.14 .16 4.06 22 27 15 15 24
112-09-1071 14 7 45 1.14 .17 4.83 26 31 15 15 24
112-09-1091 12 1 45 1.14 .18 4.57 31 36 20 20 30
112-09-1101 12 7 45 1.14 .19 4.83 33 38 20 20 30
112-09-1121 10 1 45 1.14 .20 5.08 44 49 30 30 42
112-09-1131 10 7 45 1.14 .21 5.33 47 52 30 30 42
112-09-1191 8 7 60 1.52 .27 6.86 75 80 55 30 55
112-09-1221 6 7 60 1.52 .31 7.87 109 120 75 65 75
112-09-1251 4 7 60 1.52 .35 8.89 163 174 95 85 97
112-09-1311 2 7 60 1.52 .41 10.41 247 270 130 115 130
112-09-1331 1 19 80 2.03 .49 12.45 321 344 150 130 156
112-09-1351 1/0 19 80 2.03 .53 13.46 395 427 170 150 179
112-09-1371 2/0 19 80 2.03 .58 14.73 487 519 195 175 204
112-09-1391 3/0 19 80 2.03 .63 16.00 601 633 225 200 342
112-09-1411 4/0 19 80 2.03 .68 17.27 745 784 260 230 278
112-09-1431 250 37 95 2.41 .76 19.56 891 930 290 255 317
112-09-1471 350 37 95 2.41 .86 22.10 1217 1272 350 310 384
112-09-1531 500 37 95 2.41 .99 25.40 1702 1766 430 380 477
112-09-1591 750 61 110 2.79 1.20 31.00 2536 2636 535 475 598
112-09-1651 1000 61 110 2.79 1.35 34.80 3335 3451 615 545 689
Minimum Manufacturing Quantity:#14 Awg Through #10 Awg is 25,000'; #8 Awg through #2 Awg is 15,000'; #1 through 4/0 is 10,000'; 250 kcmil through 1000 kcmil - 5,000'
To order a color other than black, change the last digit of the catalog number as follows:
White 2
Red 3
Green 4
Orange 5
Blue 6
Yellow 7
Example: To order #14/SOL - Red, the catalog number would be 112-09-1063.
Ampacities

(1) Ampacities are based on Table 310-16 of the National Electrical Code for these 90°C rated conductors at an ambient temperature of 30°C. The 75°C wet column is provided for additional information.

The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within a raceway is in accordance with Note 8 to NEC Tables 310-16 through 310-19.

(2) Based on three (3) conductors in a single enclosed or exposed conduit. Capacities based on 40°C air ambient using ICEA methods. For 30°C ambient multiply values by 1.10; for 50°C multiply by .90. For other ambients or installation conditions refer to Engineering Data Book EHB-90.

The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 318-11.

B\96060303