THE OKONITE COMPANY Product Data
Section 3: Sheet 27

Okotherm® CIC Fire Resistant Cable
600V Power & Control Cable
Multiple Nickel Coated Copper Conductors 90°C Rating



A
  Nickel or Tin Coated Copper Conductors

B
  Okotherm (Silicone) Thermoset Insulation

C
  Fiberglass Braid - Coded per ICEA

D
  Fiberglass Fillers

E
  Flame Retardant Binder Tape

F
  Black Okoclear TP (TPPO) Jacket
 

Cable Description
Nickel or Tin Coated Copper conductors, Okotherm CIC fire resistant thermoset silicone insulation, color or number coded fiberglass braid, cabled conductors, optional grounding conductor, fire resistant binder tape, Okoclear TP (TPPO) jacket.
Conductors: Nickel or Tin Coated Copper
Insulation: Okotherm Thermoset Silicone
Color Code: ICEA
Braid: Fiberglass Braid
Outer Jacket: Black Okoclear TP (TPPO)



Applicable Industry Standards:

UL 1277, ICEA S-73-532 (NEMA WC 57), ASTM B-33 & B-355

Flame Tests:
IEC 60331, UL 1277

Applications
Okotherm CIC 600 volt power & control cables are used in systems where, in the event of a fire, circuit integrity is required in order to maintain a process or to safely shut down the process. Fire resistance is determined by compliance to the IEC 60331 circuit integrity fire test. Okotherm CIC cables maintain circuit integrity based on qualification to the IEC standard 60331 for all temperatures and times up to and including 2000°F for three hours. When exposed to the fire source, the Okotherm CIC insulation becomes an electrically insulating ceramic-like ash that is capable of maintaining the operating voltage. Okotherm CIC power & control cables may be installed in dry locations, as open runs of cable secured to supports not more than six feet apart, as an aerial cable on a messenger, or in any approved raceway.

Product Features

  • For cable tray use.
  • For direct burial.
  • Sunlight resistant.
  • Flame Retardant - passes the vertical tray flame test requirements of UL 1277.
  • 90°C continuous rating.
  • 130°C emergency overload rating.
  • 250°C short circuit rating.
  • Quality control inspected to meet or exceed applicable industry standards.
  • Jacket resistant to moisture and most chemical atmospheres.
  • Thermal stability at elevated temperatures.
  • Easy to install and terminate.
  • Mechanically rugged.
  • Fire Resistant - qualified to 2000°F per IEC 60331.

1-Catalog Number
2-Conductor Size AWG
3-Number of Conductors
4-Insulation Thickness - mils
5-Jacket Thickness - mils
6-Approx. O.D. - Inches
  7-Cross-Sectional Area (sq. in.)
  8-Approx. Net Weight lbs./1000’
  9-Approx. Ship Weight lbs./1000’
10-90°C NEC Ampacity
11-75°C NEC Ampacity

 NICKEL COPPER

1 2 3 4 5 6 7 8 9 10 11

202-17-3452
202-17-3553
202-17-3454
202-17-3455

14 (7X)
14 (7X)
14 (7X)
14 (7X)

 2
3
4
5

45

45
45
60
60

0.48 
0.51
0.59
0.64

0.18
0.20
0.27
0.32

124
142
202
238

147
165
226
277

15
15
15
15

15
15
15
15

202-17-3457
202-17-3459
202-17-3462
202-17-3469
202-17-3487

14 (7X)
14 (7X)
14 (7X)
14 (7X)
14 (7X)

7
9
12
19
37

45

60
60
80
80
80

0.70
0.81
0.95
1.10
1.46

0.39
0.52
0.71
0.95
1.67

297
345
497
696
1256 

336
384
561
776
1399

15
15
12
12
10

14
14
10
10
8

202-17-3552
202-17-3553
202-17-3554
202-17-3555

12 (7X)
12 (7X)
12 (7X)
12 (7X)

2
3
4
5

45

45
60
60
60

0.52
0.59
0.64
0.69

0.21
0.27
0.32
0.37

154
205
254
301

177
229
293
340

20
20
20
20

20
20
20
20

202-17-3557
202-17-3559
202-17-3562
202-17-3569
202-17-3587

12 (7X)
12 (7X)
12 (7X)
12 (7X)
12 (7X)

7
9
12
19
37 

45

60
80
80
80
80

0.75
0.92
1.03
1.20
1.60

0.44
0.67
0.83
1.13
2.01

380
479
636
905
1655 

419
543
716
985
1798

20
20
15
15
12

17
17
12
12
10

202-17-3652 202-17-3653
202-17-3654 202-17-3655

10 (7X)
10 (7X)
10 (7X)
10 (7X)

2
3
4
5

45

60
60
60
60

0.60
0.63
0.69
0.75

0.28
0.31
0.37
0.44

211
261
327
389

235
300
366
428

30
30
30
30

30
30
28
28

202-17-3657
202-17-3659
202-17-3662

10 (7X)
10 (7X)
10 (7X)

7
9
12

45

60
80
80

0.82
1.00
1.12

0.53
0.79
0.99

499
627
836

563
691
916

28
28
28

24
24
17

1-Catalog Number
2-Conductor Size AWG
3-Insulation Thickness - mils
4-Grounding Conductors-AWG(1)
5-Jacket Thickness - mils
6-Approx. O.D. - Inches
  7-Cross-Sectional Area (sq. in.)
  8-Approx. Net Weight lbs./1000’
  9-Approx. Ship Weight lbs./1000’
10-90°C NEC Ampacity
11-75°C NEC Ampacity

 NICKEL COPPER - 3 INSULATED CONDUCTORS

1 2 3 4 5 6 7 8 9 10 11

202-17-3403
202-17-3503
202-17-3603

14 (7X)
12 (7X)
10 (7X)

 45

14
12
10

60
60
60

0.58
0.62
0.66

0.26
0.30
0.34

206
254
322

230
278
361

15
20
30

15
20
30

 TINNED COPPER  - 3 INSULATED CONDUCTORS

1 2 3 4 5 6 7 8 9 10 11

112-16-3503
112-16-3603
112-16-3703
112-16-3803

8 (7X)
6 (7X)
4 (7X)
2 (7X)

60

10
8
8
6

60
80
80
80

0.78
0.89
0.97
1.10

0.48
0.62
0.74
0.95

447
625
783
1110

486
689
847
1190

55
75
95
130

50
65
85
115

112-16-3903
112-16-3913
112-16-3923
112-16-3943

   1 (19X)
1/0 (19X)
2/0 (19X)
4/0 (19X)

80

6
6
6
4

80
80
80
80

1.27
1.36
1.45
1.67

1.27
1.45
1.65
2.19

1415
1681
2006
2949

1521
1797
2149
3126

150
170
195
260

130
150
175
230

112-16-3953
112-16-3963
112-16-3973

250 (37X)
350 (37X)
500 (37X)

95

4
3
2

110
110
110

1.93
2.15
2.43

2.93
3.63
4.64

3609
4782
6497

3875
5182
7056

390
350
430

255
310
380

112-16-3983

750 (61X)

110

1

140

2.92

6.70

9608

10370

535

475


(1) - Uninsulated 

Length Tolerance - Cut lengths of 1000 feet or longer are subject to a tolerance of 10%, less than 1000 feet,
± 15%.

Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 392.9.

Ampacities are based on 310.16 of the National Electrical Code for conductors rated 90°C, in a multi-conductor cable, at an ambient temperature of 30°C (86F). The 75°C column is provided for additional information.
The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within the cable is in accordance with Note 8 to NEC Section 310.16 through 310.8.
The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.11.

 

A/06060327   