THE OKONITE COMPANY Product Data
Section 3: Sheet 2
OkoniteŽ-OkosealŽ
Type RHW-2/PVC
600V Power and Control
Copper Conductor/90°C Wet or Dry
For Cable Tray Use - Sunlight Resistant - For Direct Burial II
UL
A Uncoated, Stranded Copper Conductor

B Insulation - Okonite

C Jacket - Okoseal


Insulation
Okonite is Okonite's trade name for its ethylene propylene based insulation. Okonite insulation is heat resistant, mechanically rugged, and exceptionally moisture resistant. This insulation provides an excellent balance of properties for a low voltage power cable.

Applications
For use in branch circuits up to 600V. Rated 90°C wet or dry for use in conduits, underground ducts and aerial circuits in accordance with the National Electric Code. It is applicable for cable tray use on sizes 4/0 and larger and is sunlight resistant. This construction combines the high dielectric and flexibility characteristics of EPR and PVC to resist the hostile oil environments in refinery use and permits ease of low friction installation. The jacket is UL rated Oil Resistant II.

Specifications
Conductor: Uncoated copper Class B stranded per ASTM B-8. 

Insulation: Okonite (EPR) meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70 and UL Standard 44.

Jacket: Okoseal (PVC) meets or exceeds the requirements of ICEA S-95-658, NEMA WC70 and UL 1581, Class 43 PVC (90°C rated PVC jacket).

Listed by Underwriters Laboratories, Inc. under miscellaneous wire category as RHW-2/PVC. Sizes 4/0 & larger are also marked "for CT-Use".

Product Features
  • Sizes 4/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL 1581 for use in cable tray.
  • Heat resistance; 90°C continuous rating; 130°C emergency overload rating; 250°C short circuit rating
  • Rated 90°C wet or dry.
  • Resistant to deformation at high temperature.
  • Stable electrical properties.
  • Low SIC and power factor.
  • Low moisture absorption.
  • Mechanically rugged.
  • Resistant to weather, most oils, acids and alkalies.
  • More flexible, easier to install and terminate than XLPE insulation.
  • UL Listed.
  • Constructions also available rated 2kV.

1-Catalog Number
2-Copper Conductor Size - AWG/kcmil
3-Insulation Thickness - mils
4-Jacket Thickness - mils
5-Nominal Diameter Over Jacket
06-Approx. Net Weight lbs./1000'
07-Approx. Ship Weight lbs./1000'
08-90°C Wet(1) NEC Ampacity
09-75°C Wet(1) NEC Ampacity
10-ICEA Ampacity(2)
1 2 3 4 5 6 7 8 9 10
112-14-3071 14 45 15 .202 29 34 15 15 24
112-14-3111 12 45 15 .220 39 44 20 20 24
112-14-3151 10 45 15 .244 54 59 30 30 30
112-14-3231 8 60 30 .335 94 105 55 50 55
112-14-3271 6 60 30 .372 130 141 75 65 75
112-14-3311 4 60 30 .418 187 210 95 85 97
112-14-3371 2 60 30 .477 274 297 130 115 130
112-14-3421 1/0 80 45 .632 449 481 170 150 179
112-14-3441 2/0 80 45 .676 545 577 195 175 204
112-14-3481 4/0 80 45 .783 814 853 260 230 272
112-14-3541 350 95 65 1.006 1342 1406 350 310 384
112-14-3581 500 95 65 1.135 1844 1933 430 300 477
112-14-3641 750 110 65 1.345 2706 2806 535 475 598  
Minimum Manufacturing Quantity:#14 Awg Through #9 Awg is 25,000'; #8 Awg through #1 Awg is 15,000'; 1/0 through 4/0 is 10,000'; 250 kcmil through 1000 kcmil - 5,000'
To order a color other than black, change the last digit of the catalog number as follows:
White 2
Red 3
Green 4
Orange 5
Blue 6
Yellow 7
Example: To order #14 - Red, the catalog number would be 112-14-3073.
(1) Ampacities are based on Table 310-16 of the National Electrical Code for these 90°C rated conductors at an ambient temperature of 30°C. The 75°C wet column is provided for additional information.

The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within a raceway is in accordance with Note 8 to NEC Tables 310-16 through 310-19.

(2) Based on three (3) conductors in a single enclosed or exposed conduit. Capacities based on 40°C air ambient using ICEA methods. For 30°C ambient multiply values by 1.10; for 50°C multiply by .90. For other ambients or installation conditions refer to Engineering Data Book EHB-90.

The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 318-11.

B\96060302
BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |