Specifications: NEMA HP100
Conductors: Bare copper per ASTM B-3, Class B stranded per ASTM B-8. Insulation:
Flame-retardant, radiation-resistant Okozel, a modified ETFE fluoropolymer, per NEMA HP
100.2.
Conductor Identification: Base colors with tracers in accordance with NEMA
HP100.
Assembly: Conductors cabled together in accordance with NEMA HP100 with
fiberglass fillers as required; and a high temperature nylon/polyester tape overall.
Jacket: Flame-retardant, radiation, oil, fuel and chemical-resistant Okozel.
Cable meets or exceeds the requirements of IEEE Std. 383, Type Test of Class IE
Electric Cables for Nuclear Power Generating Stations and is rated "nonburning"
under ASTM D635.
Applications
Okozel control cables are recommended for use in either nuclear powered or fossil fueled
generating stations where continuity of service in critical control circuits is of primary
importance. These cables which are rated 150°C in dry locations (90°C wet as Class 1E),
offer reduced cable diameters through higher ampacities and thinner insulation walls than
comparable XLPE or rubber constructions.
Okozel control cables are also recommended for high ambient temperature areas up to
150°C (302°F) in industrial applications or for cold weather installations in excess of
-65°C (-85°F).
Product Features
Low surface friction provides easier installation. Smaller diameter and lighter weight
permits more cables per tray. 150°C continuous operating temperature, 90°C in
containment area. Cold installation temperature in excess of -65°C. Exceptional abrasion
resistance will not cut or tear. Passes IEEE 383 & 1202 and UL vertical tray flame
tests (70,000 BTU/hr). Passes the ICEA T-29-520 210,000 BTU/hr vertical tray flame test.
Low smoke emission. Chemically inert-unaffected by typical acids, bases, solvents and
cleaning agents, fuels and hydraulic fluids. High dielectric strength. Low dielectric
constant. Qualified for nuclear generating stations. |