THE OKONITE COMPANY Product Data
Section 3: Sheet 13
Galvanized Steel Loxarmor®
Type MC (XHHW-2)
600V Power Cable-Galvanized Steel Interlocked Armor
Copper Conductor/90°C wet or Dry Rating
For Cable Tray Use-Sunlight Resistant-For Direct Burial
UL
A Bare, Annealed, Stranded Copper Conductors

B X-Olene Insulation - Color Coded for Identification

C Bare, Annealed, Stranded Copper Grounding Conductor

D Non-Hygroscopic Fillers, as necessary

E Binder Tape

F Loxarmor - Galvanized Steel Interlocked Armor

G Black Okoseal Jacket, when specified


Insulation
X-Olene® is Okonite's trade name for its chemically cross-linked polyethylene, with high dielectric strength.

Color Coding
Conductors are color coded using base colors and tracers in accordance with the Conductor Identification Table on the back of this Data Sheet.

Assembly and Coverings
The individual conductors are cabled together with non-hygroscopic fillers as necessary and a binder tape overall. One bare stranded copper grounding conductor is placed in one of the outer interstices. The Loxarmor is an interlocked galvanized steel armor with outstanding mechanical strength. For direct burial in the ground, embedment in concrete, or for areas subjected to corrosive atmospheres, the Loxarmor is protected with a black Okoseal® (PVC) jacket.

Applications
Loxarmor power and control cables are recommended as an economical alternate to a wire in conduit system. They are designed specifically for use on feeders and branch circuits in power distribution systems. Loxarmor power cables may be installed in both exposed and concealed work, wet and dry locations, direct burial in the earth, or embedded in concrete. They may be installed on metal racks, troughs, in cable trays or secured to supports not greater than 6 feet apart. When used with approved terminators, Loxarmor may be used in Class I and II (Division 2) and Class III (Division 1 and 2) hazardous locations - NEC Articles 501, 502 and 503.

Specifications
Conductors: Bare, copper, per ASTM B-3, Class B stranding per ASTM B-8.

Insulation: X-Olene per ICEA S-95-658 NEMA WC57 and UL 44. Listed UL Type XHHW-2.

Conductor Identification: Base colors and tracers per ICEA S-95-658 NEMA WC57. Sizes 4 AWG & larger - print number and color.

Ground Conductor: Bare, copper per ASTM B-3, Class B stranding per ASTM B-8, ICEA S-95-658 / WC57and UL 1569.

Assembly: Per UL 1569 with binder tape overall.

Loxarmor: Per ICEA S-95-658 NEMA WC57, Section 4.5.7 and UL 1569.

Jacket: When specified, black Okoseal (PVC) per UL 1569.

UL Listed as Type MC cable.

Product Features
  • Cable complies with UL 1569 for Type MC Metal-Clad Cable..
  • Complete pre-packaged, factory-tested wiring system - color coded.
  • Flame retardant - passes the vertical tray flame test requirements of IEEE 383 and 1202, UL 1569, ICEA T-29-520(210,000 BTU/hr.)
  • Loxarmor cables are quality control inspected to meet or exceed applicable UL standards.
  • 90°C continuous rating in wet or dry locations; 130°C emergency overload rating; 250°C short circuit rating
  • Lower installed cost compared to wire in conduit or EMT.
  • Excellent compression and impact resistance.
  • Easily re-routed in the event of system changes.
  • UL Listed for cable tray use.
  • UL Listed for direct burial.
  • UL Listed sunlight resistant.

1-Catalog Number
2-Conductor Size - AWG/kcmil
3-Number of Conductors
4-Insulation Thickness-mils
5-Grounding Conductor AWG *
6-Core O.D. - Inches
7-Core O.D. - mm
8-Loxarmor O.D. - Inches
9-Loxarmor O.D. - mm
10-Jacket Thickness - mils
11-Jacket Thickness - mm
12-Approx. O.D. - Inches
13-Approx. O.D. - mm
14-Cross-Sectional Area(sq in) ¥
15-Approx. Net Weight lbs./1000'
16-Approx. Ship Weight lbs./1000'
17-NEC Ampacity(1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
112-31-5244 8(7X) 3 45 10 0.54 13.6 0.78 19.7 50 1.27 0.87 22.0 0.62 522 577 55
112-31-5316 4 10 0.60 15.2 0.84 21.3 50 1.27 0.96 24.4 0.71 639 694 44
112-31-5317 6(7X) 3 45 8 0.62 15.7 0.86 21.7 50 1.27 0.97 24.6 0.73 699 754 75
112-31-5318 4 8 0.69 17.5 0.93 23.6 50 1.27 1.05 26.7 0.85 840 907 60
112-31-5248 4(7X) 3 45 8 0.72 18.2 0.96 24.3 50 1.27 1.10 27.9 0.89 955 1022 95
112-31-5319 4 8 0.80 20.3 1.04 26.4 50 1.27 1.20 30.5 1.04 1164 1244 76
112-31-5251 2(7X) 3 45 6 0.84 21.4 1.08 27.5 50 1.27 1.18 30.0 1.12 1227 1307 130
112-31-5320 4 6 0.94 23.9 1.18 30.0 50 1.27 1.31 33.2 1.31 1532 1632 104
112-31-5321 1(19X) 3 55 6 0.97 24.6 1.21 30.7 50 1.27 1.31 33.2 1.37 1480 1570 150
112-31-5322 4 6 1.08 27.6 1.32 33.6 50 1.27 1.43 36.3 1.62 1830 1946 120
112-31-5258 1/0(19X) 3 55 6 1.06 26.8 1.30 32.9 50 1.27 1.40 35.6 1.55 1744 1860 170
112-31-5323 4 6 1.18 30.0 1.42 36.1 50 1.27 1.52 38.6 1.84 2169 2312 136
112-31-5324 2/0(19X) 3 55 6 1.15 29.3 1.39 35.4 50 1.27 1.49 37.8 1.77 2126 2269 195
112-31-5325 4 6 1.29 32.7 1.53 38.8 60 1.52 1.73 43.9 2.16 2762 2926 156
112-31-5328 4/0(19X) 3 55 4 1.38 35.1 1.62 41.2 60 1.52 1.75 44.5 - 3027 3261 260
112-31-5329 4 4 1.55 39.3 1.80 45.6 60 1.52 1.94 49.3 - 3957 4223 208
112-31-5331 250(37X) 3 65 4 1.53 38.8 1.78 45.2 60 1.52 1.92 48.8 - 3711 3977 290
112-31-5332 4 4 1.71 43.4 1.96 49.8 60 1.52 2.10 53.3 - 4636 4983 232
112-31-5344 350(37X) 3 65 3 1.75 44.5 2.00 50.9 60 1.52 2.15 54.6 - 4877 5224 350
112-31-5345 4 3 1.96 49.8 2.21 56.2 60 1.52 2.36 59.9 - 6125 6684 280
112-31-5349 500(37X) 3 65 2 2.03 51.6 2.28 57.9 75 1.90 2.45 62.2 - 6632 7191 430
112-31-5352 4 2 2.27 57.7 2.52 64.1 75 1.90 2.69 68.3 - 8410 9120 344
112-31-5353 750(61X) 3 80 1 2.48 63.1 2.73 69.5 75 1.90 2.90 73.7 - 9568 10330 535
112-31-5354 4 1 2.78 70.6 3.03 77.0 85 2.16 3.22 81.8 - 12215 13148 428
112-31-5356 1000(61X) 3 80 1/0 2.81 71.3 3.06 77.7 85 2.16 3.25 82.6 - 12269 13202 615
112-31-5357 4 1/0 3.14 79.9 3.39 86.2 85 2.16 3.59 91.2 - 15681 17231 492
* Grounds may be split.
Minimum Manufacturing Quantity for non-stock items; sizes #8 to #1 - 5000'; #1/0 to #4/0 - 3000'; 250-1000 kcmil-1500'.

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ± 15%.

¥ Cross-sectional area for calculation of cable try fill in accordance with NEC Section 318-9.

When conductors smaller than #8 AWG are required, C-L-X Type MC is recommended.

Composite power and control cables are available on special order.

(1) Ampacities

Ampacities are based on 310-16 of the National Electrical Code for XHHW-2 conductors rated 90°C, in a multi-conductor cable, at an ambient temperature of 30°C (86°F). Derating for more than three current carrying conductors within the cable is in accordance with Note 8 and 10 to NEC Tables 310-16 through 310-19. When installed in Class 1 remote-control or signaling circuits in accordance with NEC Section 725-19, where the conductors do not carry continuous load, no derating is required.

The ampacities shown apply to cables installed in cable tray in accordance with NEC Section 318-11, installation in any approved raceway, or direct buried in the earth.


1-Catalog Number
2-Conductor Size - AWG/kcmil
3-Number of Conductors
4-Insulation Thickness-mils
5-Grounding Conductor AWG *
6-Core O.D. - Inches
7-Core O.D. - mm
8-Loxarmor O.D. - Inches
09-Loxarmor O.D. - mm
10-Approx. O.D. - Inches
11-Approx. O.D. - mm
12-Cross-Sectional Area(sq in) ¥
13-Approx. Net Weight lbs./1000'
14-Approx. Ship Weight lbs./1000'
15-NEC Ampacity(1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Without PVC Jacket
112-31-5206 8(7X) 3 45 10 0.54 13.6 0.78 19.7 0.76 19.3 0.47 435 474 55
112-31-5207 4 10 0.60 15.2 0.84 21.3 0.85 21.6 0.55 542 597 44
112-31-5208 6(7X) 3 45 8 0.62 15.7 0.86 21.7 0.86 21.8 0.58 600 655 75
112-31-5209 4 8 0.69 17.5 0.93 23.6 0.94 23.8 0.68 733 788 60
112-31-5210 4(7X) 3 45 8 0.72 18.2 0.96 24.3 0.97 24.6 0.72 843 898 96
112-31-5211 4 8 0.80 20.3 1.04 26.4 1.09 27.7 1.85 1041 1108 76
112-31-5212 2(7X) 3 45 6 0.84 21.4 1.08 27.5 1.07 27.2 0.92 1106 1178 130
112-31-5213 4 6 0.94 23.9 1.18 30.0 1.21 30.7 1.10 1410 1500 104
112-31-5201 1(19X) 3 55 6 0.97 24.6 1.21 30.7 1.20 30.5 1.15 1344 1424 150
112-31-5202 4 6 1.08 27.6 1.32 33.6 1.32 33.5 1.38 1682 1782 120
112-31-5214 1/0(19X) 3 55 6 1.06 26.8 1.30 32.9 1.29 32.8 1.32 1600 1700 170
112-31-5215 4 6 1.18 30.0 1.42 36.1 1.41 35.8 1.59 2011 2127 136
112-31-5216 2/0(19X) 3 55 6 1.15 29.3 1.39 35.4 1.38 35.0 1.52 1971 2071 195
112-31-5203 4 6 1.29 32.7 1.53 38.8 1.60 40.6 1.83 2548 2691 156
112-31-5218 4/0(19X) 3 55 4 1.38 35.1 1.62 41.2 1.61 41.0 - 2810 2953 260
112-31-5219 4 4 1.55 39.3 1.80 45.6 1.84 46.7 - 3798 4064 208
112-31-5220 250(37X) 3 65 4 1.53 38.8 1.78 45.2 1.79 45.2 - 3471 3705 290
112-31-5221 4 4 1.71 43.4 1.96 49.8 2.01 51.1 - 4465 4721 232
112-31-5222 350(37X) 3 65 3 1.75 44.5 2.00 50.9 2.01 51.1 - 4581 4928 350
112-31-5223 4 3 1.96 49.8 2.21 56.2 2.22 56.4 - 5799 6199 280
112-31-5224 500(37X) 3 65 2 2.03 51.6 2.28 57.9 2.29 58.2 - 6218 6777 430
112-31-5225 4 2 2.27 57.7 2.52 64.1 2.53 64.3 - 7953 8512 344
112-31-5226 750(61X) 3 80 1 2.48 63.1 2.73 69.5 2.74 69.6 - 9075 9785 535
112-31-5227 4 1 2.78 70.6 3.03 77.0 3.04 77.2 - 11594 12356 428
112-31-5228 1000(61X) 3 80 1/0 2.81 71.3 3.06 77.7 3.07 78.0 - 11642 12404 615
112-31-5229 4 1/0 3.14 79.9 3.39 86.2 3.40 86.3 - 14988 15921 492
* Grounds may be split.
Conductor Color Coding Sequence
Conductor Number Base Color Tracer Color
1 Black -
2 Red -
3 Blue -
4 Orange -
5 Yellow -
6 Brown -
7 Red Black
8 Blue Black
9 Orange Black
10 Yellow Black
11 Brown Black
12 Black Red
13 Blue Red
14 Orange Red
15 Yellow Red
16 Brown Red
17 Black Blue
18 Red Blue
19 Orange Blue
20 Yellow Blue
21 Brown Blue
22 Black Orange
23 Red Orange
24 Blue Orange
25 Yellow Orange
26 Brown Orange
27 Black Yellow
28 Red Yellow
29 Blue Yellow
30 Orange Yellow
31 Brown Yellow
32 Black Brown
33 Red Brown
34 Blue Brown
35 Orange Brown
36 Yellow Brown
37 Black -
Color Coding per ICEA Method 1, E-2
Sizes 4 AWG and larger:
Surface Printing of Numbers and color designation per ICEA Method 3
Special Order: Any or all of the following conductors may be added when specifically requested by the customer to meet his specific application requirements. These conductor codings comply with UL and NEC requirements.
Purpose Base Color Tracer Color
Equipment Grounding Unisulated
Green
Green 1 or more continuous yellow stripes
Grounded White
White Black continuous stripe
White Red continuous stripe
White Blue continuous stripe
White Orange continuous stripe
White Brown continuous stripe
White Numeric Printing
LOXARMOR® The Okonite Co.

B/96070313

BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |