THE OKONITE COMPANY Product Data
Section 3: Sheet 12
Aluminum Loxarmor®
Type MC (XHHW-2)

600V Power Cable-Aluminum Interlocked Armor
Copper Conductors/90°C Wet or Dry Rating
For Cable Tray Use - Sunlight Resistant For Direct Burial
UL
A Bare, Annealed, Stranded Copper Conductor

B X-Olene Insulation - Color Coded for Identification

C Bare, Annealed, Stranded Copper Grounding Conductor

D Non-Hygroscopic Fillers, as necessary

E Binder Tape

F Loxarmor - Aluminum Interlocked Armor

G Black Okoseal Jacket, when specified


Insulation
X-Olene® is Okonite's trade name for its chemically cross-linked polyethylene, with high dielectric strength.

Color Coding
Conductors are color coded using base colors and tracers in accordance with the Conductor Identification Table on the back of this Data Sheet.

Assembly and Coverings
The individual conductors are cabled together with non-hygroscopic fillers as necessary and a binder tape overall. One bare stranded copper grounding conductor is placed in one of the outer interstices. The Loxarmor® is an interlocked aluminum armor with good mechanical strength. For direct burial in the ground, embedment in concrete, or for areas subjected to corrosive atmospheres, the Loxarmor is protected with an Okoseal® (PVC) jacket.

Applications
Loxarmor power and control cables are recommended as an economical alternate to a wire in conduit system. They are designed specifically for use on feeders and branch circuits in power distribution systems. Loxarmor power cables may be installed in both exposed and concealed work, wet and dry locations, direct burial in the earth, or embedded in concrete. They may be installed on metal racks, troughs, in cable trays or secured to supports not greater that 6 feet apart. When used with approved terminators, Loxarmor may be used in Class I and II (Division 2) and Class III (Division 1 and 2) hazardous locations - NEC Articles 501, 502 and 503.

Specifications
Conductors: Bare, copper, per ASTM B-3 Class B stranding per ASTM B-8.

Insulation: X-Olene per ICEA S-95-658 NEMA WC-57 and UL 44. Listed UL Type XHHW-2.

Conductor Identification: Base colors and tracers per ICEA S-95-658 NEMA WC-57. Sizes 4 AWG and larger - print number and color.

Ground Conductor: Bare, copper per ASTM B-3 Class B stranding per ASTM B-8, ICEA S-95-658 NEMA WC-57 and UL 1569.

Assembly: Per UL 1569 with binder tape overall.

Loxarmor: Per ICEA S-95-658 NEMA WC-57, Section 4.5.7 and UL 1569.

Jacket: When specified, black Okoseal (PVC) per UL 1569. UL Listed as Type MC cable.

Product Features
  • Cable complies with UL 1569 for Type MC Metal-Clad Cable.
  • Complete pre-packaged, factory-tested wiring system - color coded.
  • Flame retardant - passes the vertical tray flame test requirements of IEEE 383 and 1202, UL 1569 ICEA T-29-520(210,000 BTU/hr.)
  • Loxarmor cables are quality control inspected to meet or exceed applicable UL standards.
  • 90°C continuous rating in wet or dry locations , 130°C emergency overload rating, 250°C short circuit rating.
  • Lower installed cost compared to wire in conduit or EMT.
  • Excellent compression and impact resistance.
  • Easily re-routed in the event of system changes.
  • UL Listed for cable tray use.
  • UL Listed for direct burial.
  • UL Listed sunlight resistant.

1-Catalog Number
2-Conductor Size - AWG/kcmil
3-Number of Conductors
4-Insulation Thickness-mils
5-Grounding Conductor AWG *
6-Core O.D. - Inches
7-Core O.D. - mm
8-Loxarmor O.D. - Inches
9-Loxarmor O.D. - mm
10-Jacket Thickness - mils
11-Jacket Thickness - mm
12-Approx. O.D. - Inches
13-Approx. O.D. - mm
14-Cross-Sectional Area(sq in) ¥
15-Approx. Net Weight lbs./1000'
16-Approx. Ship Weight lbs./1000'
17-NEC Ampacity(1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
With PVC Jacket
112-31-5744 8(7X) 3 45 10 0.54 13.6 0.79 20.0 50 12.7 0.88 22.3 0.63 429 484 55
112-31-5745 4 10 0.60 15.2 0.85 21.5 50 1.27 0.97 26.3 0.72 534 589 44
112-31-5746 6(7X) 3 45 8 0.62 15.7 0.87 22.0 50 1.27 0.98 24.8 0.75 591 646 75
112-31-5747 4 8 0.69 17.5 0.94 23.8 50 1.27 1.07 27.2 0.86 714 781 60
112-31-5748 4(7X) 3 45 8 0.72 18.2 0.97 24.5 50 1.27 1.11 28.2 0.91 829 897 95
112-31-5749 4 8 0.80 20.3 1.05 26.7 50 1.27 1.21 30.7 1.06 1013 1103 76
112-31-5750 2(7X) 3 45 6 0.84 21.4 1.09 27.8 50 1.27 1.19 30.2 1.14 1079 1159 130
112-31-5751 4 6 0.94 23.9 1.19 30.3 50 1.27 1.33 33.8 1.33 1374 1464 104
112-31-5752 1(19X) 3 55 6 0.97 24.6 1.22 31.0 50 1.27 1.32 33.5 1.39 1309 1399 150
112-31-5753 4 6 1.08 27.6 1.33 33.9 50 1.27 1.44 36.7 1.64 1639 1755 120
112-31-5754 1/0(19X) 3 55 6 1.06 26.8 1.31 33.2 50 1.27 1.41 35.8 1.58 1559 1675 170
112-31-5755 4 6 1.18 30.0 1.43 36.4 50 1.27 1.53 38.9 1.87 1962 2105 136
112-31-5756 2/0(19X) 3 55 6 1.15 29.3 1.40 35.6 50 1.27 1.50 38.1 1.80 1924 2067 195
112-31-5757 4 6 1.29 32.7 1.54 39.1 60 1.52 1.74 44.2 2.19 2557 2721 156
112-31-5760 4/0(19X) 3 55 4 1.38 35.1 1.63 41.5 60 1.52 1.76 44.7 - 2786 2950 260
112-31-5761 4 4 1.55 39.3 1.83 46.4 60 1.52 1.95 49.5 - 3605 3871 208
112-31-5762 250(37X) 3 65 4 1.53 38.8 1.81 45.9 60 1.52 1.93 49.0 - 3363 3629 290
112-31-5763 4 4 1.71 43.4 1.99 50.5 60 1.52 2.11 53.6 - 4248 4504 232
112-31-5764 350(37X) 3 65 3 1.75 44.5 2.03 51.6 60 1.52 2.16 54.9 - 4480 4765 350
112-31-5765 4 3 1.96 49.8 2.24 56.9 60 1.52 2.40 61.0 - 5758 6317 280
112-31-5766 500(37X) 3 65 2 2.03 51.6 2.31 58.7 75 1.90 2.46 62.5 - 6174 6733 430
112-31-5767 4 2 2.27 57.7 2.55 64.8 75 1.90 2.70 68.6 - 7898 8490 344
112-31-5768 750(61X) 3 80 1 2.48 63.1 2.76 70.2 75 1.90 2.90 73.7 - 9010 9772 535
112-31-5769 4 1 2.78 70.6 3.06 77.8 85 2.16 3.29 83.6 - 11785 12718 428
112-31-5770 1000(61X) 3 80 1/0 2.81 71.3 3.09 78.4 85 2.16 3.32 84.3 - 11835 12768 615
112-31-5771 4 1/0 3.14 79.9 3.42 87.0 85 2.16 3.66 93.0 - 15193 16743 492
* Grounds may be split.

Mimimum Manufacturing Quantity for non-stock items; sizes #8 to #1-5000'; #1/0 to #4/0-3000'; 250-1000 kcmil-1500'.

Length Tolerance: Cut lengths of 1000 feet or longer are subject to a tolerance of ± 10%; less than 1000 feet ± 15%.

¥ Cross-sectional area for calculation of cable try fill in accordance with NEC Section 318-9.

When conductors smaller than #8 AWG are required, C-L-X Type MC is recommended.

Composite power and control cables are available on special order.

(1) Ampacities Ampacities are based on 310-16 of the National Electrical Code for XHHW-2 conductors rated 90°C, in a multi-conductor cable, at an ambient temperature of 30°C (86°F). Derating for more than three current carrying conductors within the cable is in accordance with Note 8 and 10 to NEC Tables 310-16 through 310-19. When installed in Class 1 remote-control or signaling circuits in accordance with NEC Section 725-19, where the conductors do not carry continuous load, no derating is required.

The ampacities shown apply to cables installed in cable tray in accordance with NEC Section 318-11, installation in any approved raceway, or direct buried in the earth.


1-Catalog Number
2-Conductor Size - AWG/kcmil
3-Number of Conductors
4-Insulation Thickness-mils
5-Grounding Conductor AWG *
6-Core O.D. - Inches
7-Core O.D. - mm
8-Loxarmor O.D. - Inches
09-Loxarmor O.D. - mm
10-Approx. O.D. - Inches
11-Approx. O.D. - mm
12-Cross-Sectional Area(sq in) ¥
13-Approx. Net Weight lbs./1000'
14-Approx. Ship Weight lbs./1000'
15-NEC Ampacity(1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Without PVC Jacket
112-31-5644 8(7X) 3 45 10 0.54 13.6 0.79 20.0 0.77 19.6 0.49 340 379 55
112-31-5645 4 10 0.60 15.2 0.85 21.5 0.86 21.8 0.57 435 490 44
112-31-5646 6(7X) 3 45 8 0.62 15.7 0.87 22.0 0.87 22.0 0.59 490 546 75
112-31-5647 4 8 0.69 17.5 0.94 23.8 0.96 24.8 0.69 605 660 60
112-31-5648 4(7X) 3 45 8 0.72 18.2 0.97 24.5 1.00 25.4 0.73 716 780 95
112-31-5649 4 8 0.80 20.3 1.05 26.7 1.10 27.9 0.86 888 955 76
112-31-5650 2(7X) 3 45 6 0.84 21.4 1.09 27.8 1.08 27.4 0.94 957 1024 130
112-31-5651 4 6 0.94 23.9 1.19 30.3 1.22 31.0 1.12 1252 1342 104
112-31-5652 1(19X) 3 55 6 0.97 24.6 1.22 31.0 1.21 30.7 1.17 1172 1262 150
112-31-5653 4 6 1.08 27.6 1.33 33.9 1.33 33.8 1.40 1490 1580 120
112-31-5654 1/0(19X) 3 55 6 1.06 26.8 1.31 33.2 1.30 33.0 1.34 1413 1503 170
112-31-5655 4 6 1.18 30.0 1.43 36.4 1.42 36.0 1.61 1803 1919 136
112-31-5656 2/0(19X) 3 55 6 1.15 29.3 1.40 35.6 1.39 35.3 1.54 1765 1865 195
112-31-5657 4 6 1.29 32.7 1.54 39.1 1.60 40.6 1.86 2333 2476 156
112-31-5660 4/0(19X) 3 55 4 1.38 35.1 1.63 41.5 1.62 41.1 - 2568 2711 260
112-31-5661 4 4 1.55 39.3 1.83 46.4 1.82 46.2 - 3361 3595 208
112-31-5662 250(37X) 3 65 4 1.53 38.8 1.81 45.9 1.80 45.7 - 3122 3356 290
112-31-5663 4 4 1.71 43.4 1.99 50.5 1.98 50.3 - 3983 4239 232
112-31-5664 350(37X) 3 65 3 1.75 44.5 2.03 51.6 2.02 51.3 - 4182 4438 350
112-31-5665 4 3 1.96 49.8 2.24 56.9 2.23 56.6 - 5354 5754 280
112-31-5666 500(37X) 3 65 2 2.03 51.6 2.31 58.7 2.30 58.4 - 5758 6317 430
112-31-5667 4 2 2.27 57.7 2.55 64.8 2.54 64.6 - 7440 7999 344
112-31-5668 750(61X) 3 80 1 2.48 63.1 2.76 70.2 2.75 70.0 - 8515 9225 535
112-31-5669 4 1 2.78 70.6 3.06 77.8 3.11 79.0 - 11038 11800 428
112-31-5670 1000(61X) 3 80 1/0 2.81 71.3 3.09 78.4 3.14 79.8 - 11194 12114 615
112-31-5671 4 1/0 3.14 79.9 3.42 87.0 3.47 88.1 - 14186 15419 492
* Grounds may be split.
Conductor Color Coding Sequence
Conductor Number Base Color Tracer Color
1 Black -
2 Red -
3 Blue -
4 Orange -
5 Yellow -
6 Brown -
7 Red Black
8 Blue Black
9 Orange Black
10 Yellow Black
11 Brown Black
12 Black Red
13 Blue Red
14 Orange Red
15 Yellow Red
16 Brown Red
17 Black Blue
18 Red Blue
19 Orange Blue
20 Yellow Blue
21 Brown Blue
22 Black Orange
23 Red Orange
24 Blue Orange
25 Yellow Orange
26 Brown Orange
27 Black Yellow
28 Red Yellow
29 Blue Yellow
30 Orange Yellow
31 Brown Yellow
32 Black Brown
33 Red Brown
34 Blue Brown
35 Orange Brown
36 Yellow Brown
37 Black -
Color Coding per ICEA Method 1, E-2
Sizes 4 AWG and larger:
Surface Printing of Numbers and color designation per ICEA Method 3
Special Order: Any or all of the following conductors may be added when specifically requested by the customer to meet his specific application requirements. These conductor codings comply with UL and NEC requirements.
Purpose Base Color Tracer Color
Equipment Grounding Unisulated
Green
Green 1 or more continuous yellow stripes
Grounded White
White Black continuous stripe
White Red continuous stripe
White Blue continuous stripe
White Orange continuous stripe
White Brown continuous stripe
White Numeric Printing
B\96060312