Specifications
Conductors: Bare copper per ASTM B-3, Class B stranded per ASTM B-8. Insulation:
Flame-retardant, radiation-resistant Okozel, a modified ETFE fluoropolymer.
Conductor Identification: Base colors with tracers in accordance with ICEA
S-73-532, NEMA WC57 Method 1.
Assembly: Conductors cabled together in accordance with ICEA
S-73-532, NEMA WC57 Section 5.1; with non-hygroscopic fillers as required; and a binder tape overall.
Sheath: Close fitting, impervious, continuous, welded, corrugated aluminum C-L-X
in accordance with UL 1569. The sheath exceeds the grounding conductor requirements of
Table 250-95 of the NEC. Copper C-L-X sheathed cable meets or exceeds the requirements of
IEEE Std. 383, Type Test for Class 1E Electric Cables for Nuclear Power Generating
Stations. All C-L-X cables are rated "nonburning" under ASTM D635.
Applications
C-L-X Okozel control cables are recommended for use in either nuclear powered or fossil
fueled generating stations where continuity of service in critical circuits is of primary
importance. These cables, which are rated 150°C in dry locations (90°C as Class 1E),
offer reduced cable diameters through higher ampacities and thinner insulation walls than
comparable XLPE or rubber constructions. C-L-X Okozel control cables are also recommended
for high ambient temperature areas up to 150°C (302°F) in industrial applications or for
cold weather installations to -65°C (-85°F).
Product Features
Factory assembled "cable in conduit". 150°C continuous operating temperature.
Cold installation temperature in excess of -65°C. Flame retardant - passes the vertical
tray flame test requirements of IEEE 383 and 1202, UL 1569, ICEA T-29-520(210,000 BTU/hr.)
and the 210,000 BTU/hr. corner configuration test. Lower smoke emission. Chemically inert
insulation-unaffected by typical acids, bases, solvents and cleaning agents, fuels and
hydraulic fluids. High dielectric strength. Low dielectric constant. Qualified for nuclear
generating stations. Smaller diameter and lighter weight permits more cables per tray.
C-L-X enclosure permits installation in cable tray containing other voltages within a
barrier separator. C-L-X sheath exceeds equipment grounding conductor requirements of
Section 250-95 of the NEC. Provides excellent grounding safety. Excellent compression and
impact resistance. No limit to number of bends in run. Lower installed system cost than
conduit or EMT systems. UL Listed for cable tray use, and sunlight resistant. May be
installed in ducts, plenums and other environmental air-handling spaces per NEC Articles
300-22 (b) and (c). |