A Bare, Annealed, Stranded Copper Power Conductors B Stranded Control Conductors
C X-Olene Insulation-Color Coded for Identification
D Non-Hygroscopic Fillers, as necessary
E Binder Tape
F Impervious, Continuous, Welded Corrugated,
Aluminum Sheath
G Black Okoseal Jacket
Insulation
X-Olene® is Okonite's trade name for its chemically cross-linked polyethylene,
with high dielectric strength.
Color Coding
Conductors 6 AWG and smaller are color coded black, red, blue, orange. Power conductors #4
AWG and larger are printed number coded. Control conductors are color coded black, red,
blue, yellow. When the control conductors are within one standard AWG size of the power
conductors, the control conductors have an additional tracer to facilitate identification.
Assembly and Coverings
The individual conductors are cabled together with non-hygroscopic fillers, bare copper
equipment grounding conductor, where indicated, and a binder tape overall. The C-L-X
sheath exceeds the grounding conductor requirements of Table 250.122 of the NEC and UL
1569. The impervious, continuous, welded, corrugated aluminum C-L-X sheath provides
complete protection against moisture, liquids and gases and has excellent mechanical
strength. For direct burial in the ground, embedment in concrete, or for areas subjected
to corrosive atmospheres, the C-L-X sheath is protected with a low temperature black Okoseal® (PVC) jacket.
Applications
C-L-X Type MC cables with the impervious, continuous, corrugated aluminum sheath are
recommended as an economical alternate to a wire in conduit system.
They are authorized for use on feeders and branch circuits for power, lighting, control
and signaling circuits in accordance with Article 330 and 725 of the NEC.
C-L-X Type MC cables may be installed indoors or outdoors, in wet or dry locations, as
open runs of cable secured to supports spaced not more than six feet apart, in cable tray,
as aerial cable on a messenger, in any approved raceway, direct burial, or encased in
concrete. C-L-X type MC cables are also approved for use in Class I & II,
Division 2, Class III, Division 1 and 2 and Class I, Zones 1 & 2 hazardous
locations - NEC Articles 501, 502, 503 and 505.
Specifications
Conductors: Bare soft annealed copper, Class "B" stranding per ASTM B-8.
#2 AWG - compact copper per ASTM B-496.
Insulation: X-Olene per ICEA S-95-658/ NEMA WC-70, ICEA S-73-532/NEMA
WC57, and UL 44, Listed UL Type
XHHW-2.
Conductor Identification: Base color and tracer or printed numbers & color.
Grounding Conductor: Where indicated, bare soft annealed copper, Class B
stranded in accordance with UL 1581. Meets or exceeds requirements of NEC Table 250.122.
Assembly: Per UL 1569 with binder tape overall
Sheath: Close fitting, impervious, continuous, welded, corrugated aluminum C-L-X
per UL 1569. Exceeds grounding conductor requirements of NEC Table 250-95.
Jacket: Black Okoseal (PVC) per UL 1569. |