THE OKONITE COMPANY Product Data
Section 3: Sheet 1
Okoguard-Okolon®
Type RHH or RHW-2 or USE-2, VW-1
600V Power and Control
Copper Conductor/90°C Wet or Dry
For Cable Tray Use-Sunlight Resistant-For Direct Burial
UL SA
A Uncoated, Stranded Copper Conductor

B Composite Okoguard-Okolon Insulation


Composite Insulation
Okoguard-Okolon is Okonite's trade name for its ethylene propylene-chlorosulfonated polyethylene composite insulation. The combination of the two materials provides a dielectric which requires no outer covering and which has excellent resistance to heat, mechanical abuse, flame, weathering, most oils, acids and alkalies.

The advantages of Okoguard EPR, with a proven track record of over 30 years as a medium voltage insulation, are now offered in low voltage cables.

Applications
Okoguard-Okolon 600 Volt Power and Control Cables are recommended for use in all low voltage circuits where continuity of service is the prime consideration. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, directly buried in the earth, or lashed to a messenger for aerial installation. These cables may also be installed in cable tray (size 1/0 AWG and larger per NEC 392.2).

Specifications
Conductor: Uncoated copper solid per ASTM-B-3, compress stranded per ASTM B-8, or compact per ASTM B-496.

Insulation: Meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70 and UL Standards 44 and 854.

Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2 or USE-2, VW-1. Sizes 1/0 AWG and larger are also marked "sunlight resistant, for use in cable tray".

Listed by CSA as RW-90, -25C, FT1 (1/0 and larger FT4), outdoor.

Product Features
  • Sizes 1/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL 1581 for use in cable tray.
  • Passes the IEEE 383-1974 Vertical Tray Flame Test.
  • Passes the IEEE 1202-1991 Vertical Tray Flame Test. (sizes 1/0 AWG & larger).
  • Extreme heat resistance; 90°C continuous rating, wet or dry 110°C hot spot rating 130°C emergency overload rating 250°C short circuit rating
  • Exceptional resistance to deformation at high temperature.
  • Stable electrical properties.
  • Low SIC and power factor.
  • Low moisture absorption.
  • Mechanically rugged.
  • Resistant to weather, most oils, acids and alkalies.
  • More flexible, easier to install and terminate than XLPE insulation.
  • UL and CSA Listed.
Composite Insulation
Thickness (mils)
Conductor
(AWG/kcmil)
Okoguard Okolon
14-9 30 15
8 45 15
6-2 45 30
1-4/0 55 45
250-500 65 65
750-1000 80 65
*CSA Rated RW-90 available

1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Number of Strands
4-Composite Insulation - Thickness-mils
5-Composite Insulation - Thickness-mm
6-Approx. O.D. - Inches
07-Approx. O.D. - mm
08-Approx. Net Weight lbs./1000'
09-Approx. Ship Weight lbs./1000'
10-90°C Wet(1) NEC Ampacity
11-75°C Wet(1) NEC Ampacity
12-ICEA Ampacity(2)
1 2 3 4 5 6 7 8 9 10 11 12
112-24-2061 14 1 45 1.14 .16 4.06 23 28 15 15 24
112-24-2071 14 7 45 1.14 .17 4.57 25 30 15 15 24
112-24-2091 12 1 45 1.14 .18 4.57 32 37 20 20 30
112-24-2101 12 7 45 1.14 .19 4.83 34 39 20 20 30
112-24-2121 10 1 45 1.14 .20 5.08 46 51 30 30 42
112-24-2131 10 7 45 1.14 .21 5.33 48 54 30 30 42
112-24-2171 9 19 45 1.14 .23 5.84 58 63 30 30 48
112-24-2191 8 7 60 1.52 .27 6.86 77 82 55 50 55
112-24-2221 6 7 75 1.91 .34 8.64 123 133 75 65 75
112-24-2251 4 7 75 1.91 .38 9.75 176 200 95 85 97
112-24-2311 2 7 75 1.91 .43 11.00 257 280 130 115 130
112-24-2331 1 19 100 2.54 .52 13.16 349 364 150 130 156
112-24-2351 1/0 19 100 2.54 .56 14.10 413 446 170 150 179
112-24-2371 2/0 19 100 2.54 .60 15.14 509 539 195 175 204
112-24-2391 3/0 19 100 2.54 .64 16.33 622 654 225 200 242
112-24-2411 4/0 19 100 2.54 .70 17.68 766 805 260 230 278
112-24-2431 250 37 130 3.30 .81 20.57 944 1002 290 255 317
112-24-2471 350 37 130 3.30 .91 23.04 1273 1332 350 310 384
112-24-2531 500 37 130 3.30 1.03 26.19 1764 1847 430 380 477
112-24-2591 750 61 145 3.68 1.28 32.51 2625 2717 535 475 598
112-24-2651 1000 61 145 3.68 1.44 36.58 3443 3590 615 545 689
Authorized stock item. Available from our Customer Service Centers.

Minimum Manufacturing Quantity:#14 Awg Through #9 Awg is 25,000'; #8 Awg through #1 Awg is 15,000'; 1/0 through 4/0 is 10,000'; 250 kcmil through 1000 kcmil - 5,000'

To order a color other than black, change the last digit of the catalog number as follows:
White 2
Red 3
Green 4
Orange 5
Blue 6
Yellow 7
Example: To order #14/Sol - Red, the catalog number would be 112-24-2063.
(1) Ampacities are based on Table 310.16 of the National Electrical Code for these 90°C rated conductors at an ambient temperature of 30°C. The 75°C wet column is provided for additional information.

The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within a raceway is in accordance with Note 8 to NEC Tables 310.16 through 310.19.

(2) Based on three (3) conductors in a single enclosed or exposed conduit. Capacities based on 40°C air ambient using ICEA methods. For 30°C ambient multiply values by 1.10; for 50°C multiply by .90. For other ambients or installation conditions refer to Engineering Data Book EHB-90.

The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.11.

C/04050301