THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 9
Okoguard®-Okoseal® Type MV-105
15kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
100% and 133% Insulation Level
UL
A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded semiconducting EPR

E Shield-Copper Tape

F Jacket Okoseal


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil, acids and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250-51, or messenger supported in industrial establishments and electric utilities.

Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen . Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: 5 mil bare copper tape helically applied.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 and UL 1072 for polyvinyl chloride jackets.

UL Listed as Type MV-105 and sunlight resistant in accordance with UL 1072 .

Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating temperature. 140°C emergency rating. 250°C short circuit rating. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Moisture resistant. Resistant to most oils, acids, and alkalies. Sunlight resistant. Improved Temperature Rating.


1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(1)
13-Ampacities Direct Burial(2)
14-Ampacities Underground Duct(3)
15-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Okoguard Insulation:175 mils(4.45mm), 100% Insulation Level
115-23-3011 2 33.6 0.66 0.72 80 2.03 0.91 23.0 585 655 165 225 165 3
115-23-3013 1 42.4 0.69 0.75 80 2.03 0.94 23.8 660 755 190 260 185 3
115-23-3015 1/0 53.5 0.73 0.79 80 2.03 0.98 24.8 750 845 215 295 215 3
115-23-3017 2/0 67.4 0.77 0.83 80 2.03 1.02 25.8 860 955 255 335 245 3
115-23-3019 3/0 85.0 0.82 0.88 80 2.03 1.06 27.0 995 1090 290 380 275 3
115-23-3021 4/0 107.0 0.87 0.93 80 2.03 1.12 28.3 1160 1260 330 435 315 3
115-23-3023 250 127.0 0.91 0.97 80 2.03 1.16 29.4 1310 1425 365 475 345 3 1/2
115-23-3027 350 177.0 1.01 1.07 80 2.03 1.26 32.0 1675 1815 440 575 415 3 1/2
115-23-3031 500 253.0 1.13 1.21 80 2.03 1.39 35.4 2230 2425 535 700 500 4
115-23-3035 750 380.0 1.31 1.39 80 2.03 1.58 40.0 3300 3565 655 865 610 5
115-23-3037 1000 507.0 1.47 1.55 110 2.79 1.79 45.6 4095 4365 755 1005 690 5
Okoguard Insulation:220 mils(5.59mm), 133% Insulation Level
115-23-3111 2 33.6 0.75 0.81 80 2.03 1.00 25.3 670 765 165 225 165 3
115-23-3113 1 42.4 0.78 0.84 80 2.03 1.03 26.1 745 840 190 260 185 3
115-23-3115 1/0 53.5 0.82 0.88 80 2.03 1.07 27.1 840 915 215 295 215 3
115-23-3117 2/0 67.4 0.86 0.92 80 2.03 1.11 28.1 955 1050 255 335 245 3
115-23-3119 3/0 85.0 0.91 0.97 80 2.03 1.16 29.3 1090 1190 290 380 275 3 1/2
115-23-3121 4/0 107.0 0.96 1.02 80 2.03 1.21 30.7 1265 1375 330 435 315 3 1/2
115-23-3123 250 127.0 1.01 1.07 80 2.03 1.25 31.8 1415 1550 365 475 345 3 1/2
115-23-3127 350 177.0 1.11 1.18 80 2.03 1.37 34.7 1810 1950 440 575 415 4
115-23-3131 500 253.0 1.22 1.30 80 2.03 1.49 37.7 2355 2555 535 700 500 5
115-23-3135 750 380.0 1.40 1.48 80 2.03 1.66 42.2 3246 3511 655 865 610 5
115-23-3139 1000 507.0 1.56 1.66 110 2.79 1.91 48.5 4290 4705 755 1005 690 6
Authorized Stock Item. Available from our Customer Service Centers.

Minimum Manufacturing Quantity for non-stock items is 5000'.

Ampacities

(1) Ampacities are in accordance with Table 310-73 of the NEC for three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C.

(2) Ampacities are in accordance with Table 310-81 of the NEC for an insulated single conductor directly buried with a conductor temperature rating of 105°C, ambient earth temperature of 20°C, 100% Load Factor, thermal resistance (RHO) of 90, 7 1/2 inch spacing between conductor center lines, and 24 inch spacing between circuits.

(3) Ampacities are in accordance with Table 310-77 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(4) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit l.D. to cable O.D. should be checked to avoid possible jamming.

D/04090209