THE OKONITE COMPANY Product Data
Section 2: Sheet 8
 

COMPACT STRAND
CONSTRUCTION

  printer friendly version (PDF)

Okoguard®-Okoseal® Type MV-105

15kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
100% and 133% Insulation Level
For Cable Tray Use-Sunlight Resistant
UL SA

 
A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shield-Copper Tape

F Jacket-Okoseal



Insulation

Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service. The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to flame, oil,acids and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for use as feeder circuits, in electric utility generating stations, for distribution circuits, and for feeders or branch circuits in industrial and commercial installations. Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250.4(A)(5), or messenger supported in industrial establishments and electric utilities. Sizes 1/0 AWG and larger may also be installed in cable tray.

Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded EPR semiconducting strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Insulation Screen: Extruded EPR semiconducting insulation screen applied directly over the insulation. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Shield: 5 mil bare copper tape helically applied with 25% nominal overlap.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.3 and UL 1072 for polyvinyl chloride jackets. UL listed as Type MV-105, sunlight resistant and for use in cable tray in accordance with UL 1072. CSA C68.3 listed and rated FT4 and -25°C.

Product Features

  • Triple tandem extruded, all EPR system.
  • Okoguard cables meet or exceed all recognized industry standards (UL, CSA, AEIC, NEMA/ICEA, IEEE).
  • 105°C continuous operating temperature.
  • 140°C emergency rating.
  • 250°C short circuit rating.
  • Passes the Vertical Tray Flame Test requirements of UL 1072 and IEEE 383 and 1202.
  • Excellent corona resistance.
  • Screens are clean stripping.
  • Exceptional resistance to “treeing”.
  • Exceptional resistance to moisture.
  • Resistant to most oils, acids, and alkalies.
  • Sunlight resistant.
  • For Cable Tray Use.
  • CSA FT4 and -25°C.
  • Improved Temperature Rating.

1-Catalog Number (1)
2-Conductor Size AWG or kcmil
3-Conductor Size -mm2
4-Approx. Dia. over Insulation (in.)
5-Approx. Dia. over Screen (in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
  9-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000’
11-Approx. Ship Weight lbs./1000’
12-Ampacities (2) Conduit in Air
13-Ampacities (3) Underground Duct 
14-Ampacities (4) Cable Tray
15-Conduit Size Inches (5)*
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Okoguard Insulation: 175 mils (4.45mm), 100% Insulation Level 

115-23-3064
115-23-3066
115-23-3067

1/0
2/0
3/0

53.5
67.4
85.0

0.74
0.78
0.83

0.80
0.84
0.89

80
80
80

2.03
2.03
2.03

0.98
1.02
1.07

24.8
25.8
27.1

760
870
1005

825
935
1070

215
255
290

215
245
275

220
250
290

3
3
3

115-23-3069
115-23-3074
115-23-3076

4/0
250
350

107.0
127.0
177.0

0.88
0.93
1.03

0.94
0.99
1.10

80
80
80

2.03
2.03
2.03

1.12
1.18
1.29

28.4
30.0
32.8

1160
1315
1700

1240
1395
1800

330
365
440

315
345
415

335
370
460

 3
 3
1/2
 3
1/2

115-23-3090
115-23-3091
115-23-3092

500
750
1000

253.0
380.0
507.0

1.14
1.32
1.47

1.22
1.40
1.55

80
80
80

2.03
2.03
2.03

1.41
1.59
1.73

35.8
40.4
43.9

2230
3115
3970

2275
3290
4200

535
655
755

500
610
690

575
745
890

4
5
5

Okoguard Insulation: 220 mils (5.59mm), 133% Insulation Level 

115-23-3230
115-23-3232
115-23-3234

1/0
2/0
3/0

53.5
67.4
85.0

0.83
0.87
0.92

0.89
0.93
0.98

80
80
80

2.03
2.03
2.03

1.10
1.12
1.16

27.9
28.4
29.4

 850
980
1100

 920
1060
1185

215
255
290

215
245
275

220
250
290

3
3
3
1/2

115-23-3236
115-23-3238
115-23-3240

4/0
250
350

107.0
127.0
177.0

0.97
1.03
1.12

1.03
1.09
1.20

80
80
80

2.03
2.03
2.03

1.22
1.27
1.38

31.0
32.3
35.1

1280
1420
1835

1370
1510
1950

330
365
440

315
345
415

335
370
460

3 1/2
3
1/2
4

115-23-3242
115-23-3243
115-23-3244

500
750
1000

253.0
380.0
507.0

1.24
1.41
1.56

1.31
1.49
1.66

80
80
110

2.03
2.03
2.79

1.50
1.68
1.91

38.1
42.7
48.5

2375
3280
4260

2520
3455
4530

535
655
755

500
610
690

575
745
890

5
5
6

 
Authorized Stock Item. Available from our Customer Service Centers. Minimum Manufacturing Quantity for non-stock items is 5000'.

Aluminum Conductors
(1) Aluminum conductors are available on special order. To order aluminum conductors, change the first three digits of the catalog number from 115 to 135.

Ampacities
(2) Ampacities are in accordance with Table 310.73 of the NEC for three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C.

(3) Ampacities are in accordance with Table 310.77 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin EHB for installation in duct banks, multiple point ground shields, other ambient temperatures, circuit configurations or installation requirements.

(4) Ampacities based on single Type MV-105 conductors, or single conductors twisted together (triplexed, quadruplexed, etc.) size 1/0 AWG and larger, installed in uncovered cable tray in accordance with Section 392.13 of the NEC at an ambient temperature of 40°C and a conductor temperate rating of 105°C. In accordance with NEC Section 392.13(b) (copper conductors), the values are 75% of the values given in table 310.69. Where the cable tray is covered for more than six feet with solid unventilated covers, the ampacities shall not exceed 93% of the values shown above.

(5) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possible jamming.
 

G/07110208
BACK TO DATA SHEET INDEX