THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 8
Okoguard®-Okoseal® Type MV-105
15kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
100% and 133% Insulation Level
For Cable Tray Use-Sunlight Resistant
UL SA
A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shield-Copper Tape

F Jacket-Okoseal


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to flame, oil, acids and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for use as feeder circuits, in electric utility generating stations, for distribution circuits, and for feeders or branch circuits in industrial and commercial installations.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 310.7, or messenger supported in industrial establishments and electric utilities. Sizes 1/0 AWG and larger may also be installed in cable tray.

Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded EPR semiconducting strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Insulation Screen: Extruded EPR semiconducting insulation screen applied directly over the insulation. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Shield: 5 mil bare copper tape helically applied with 25% nominal overlap.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.3 and UL 1072 for polyvinyl chloride jackets.

UL Listed as Type MV-105, sunlight resistant and for use in cable tray in accordance with UL 1072.

CSA listed meeting the requirements of C68.3 and rated FT4 sizes 4/0 and larger are rated -40°C.

Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, CSA, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating temperature. 140°C emergency rating. 250°C short circuit rating. Passes the Vertical Tray Flame Test requirements of UL 1072 and IEEE 383. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Moisture resistant. Resistant to most oils, acids, and alkalies. Sunlight resistant. For Cable Tray Use. Improved Temperature Rating.


1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(1)
13-Ampacities Underground Duct(2)
14-Ampacities Cable Tray(3)
15-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Okoguard Insulation:175 mils(4.45mm), 100% Insulation Level
115-23-3064 1/0 53.5 0.73 0.79 80 2.03 0.98 24.8 760 850 215 215 220 3
115-23-3066 2/0 67.4 0.77 0.83 80 2.03 1.02 25.8 875 970 255 245 250 3
115-23-3067 3/0 85.0 0.82 0.88 80 2.03 1.07 27.1 1010 1075 290 275 290 3
115-23-3069 4/0 107.0 0.87 0.93 80 2.03 1.12 28.4 1175 1270 330 315 335 3
115-23-3074 250 127.0 0.91 0.97 80 2.03 1.16 29.5 1375 1435 365 345 370 3 1/2
115-23-3076 350 177.0 1.01 1.07 80 2.03 1.26 32.0 1695 1830 440 415 460 3 1/2
115-23-3090 500 253.0 1.13 1.21 80 2.03 1.40 35.5 2250 2445 535 500 575 4
115-23-3091 750 380.0 1.31 1.39 80 2.03 1.58 40.1 3145 3405 655 610 745 5
115-23-3092 1000 507.0 1.47 1.55 110 2.79 1.80 45.6 4120 4385 755 690 890 5
Okoguard Insulation:220 mils(5.59mm), 133% Insulation Level
115-23-3230 1/0 53.5 0.82 0.88 80 2.03 1.07 27.2 855 945 215 215 220 3
115-23-3232 2/0 67.4 0.86 0.92 80 2.03 1.11 28.2 965 1060 255 245 250 3
115-23-3234 3/0 85.0 0.91 0.97 80 2.03 1.16 29.4 1110 1155 290 275 290 3 1/2
115-23-3236 4/0 107.0 0.96 1.02 80 2.03 1.21 30.7 1280 1390 330 315 335 3 1/2
115-23-3238 250 127.0 1.01 1.07 80 2.03 1.25 31.8 1430 1565 365 345 370 3 1/2
115-23-3240 350 177.0 1.11 1.18 80 2.03 1.37 34.7 1815 1950 440 415 460 4
115-23-3242 500 253.0 1.22 1.30 80 2.03 1.49 37.8 2375 2570 535 500 575 5
115-23-3243 750 380.0 1.40 1.48 80 2.03 1.66 42.2 3252 3517 655 610 745 5
115-23-3244 1000 507.0 1.56 1.66 110 2.79 1.91 48.5 4315 4730 755 690 890 6
Authorized Stock Item. Available from our Customer Service Centers.

Minimum Manufacturing Quantity for non-stock items is 5000'.

Ampacities

(1) Ampacities are in accordance with Table 310-73 of the NEC for three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C.

(2) Ampacities are in accordance with Table 310-77 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin EHB for installation in duct banks, multiple point ground shields, other ambient temperatures, circuit configurations or installation requirements.

(3) Ampacities based on single Type MV-105 conductors, or single conductors twisted together (triplexed, quadruplexed, etc.) size 1/0 AWG and larger, installed in uncovered cable tray in accordance with Section 318-13 of the NEC at an ambient temperature of 40°C and a conductor temperate rating of 105°C. In accordance with NEC Section 318-13(b) (copper conductors), the values are 75% of the values given in table 310-69. Where the cable tray is covered for more than six feet with solid unventilated covers, the ampacities shall not exceed 93% of the values shown above.

(4) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possible jamming.

F/06080208