Okoguard®-Okolon® Type MV-105
8kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
100% and 133% Insulation Level
For Cable Tray Use-Sunlight Resistant
|
|
A Uncoated, Okopact (Compact Stranded) Copper Conductor
B Strand Screen-Extruded Semiconducting EPR
C Insulation-Okoguard EPR
D Insulation Screen-Extruded Semiconducting EPR
E Shielding-Coated Copper Tape
F Jacket-Okolon
Insulation
Okoguard is Okonite’s registered trade name for its exclusive
ethylene-propylene rubber (EPR) based, thermosetting compound, whose
optimum balance of electrical and physical properties is unequaled
in other solid dielectrics. Okoguard insulation, with the
distinctive red color and a totally integrated EPR system, provides
the optimum balance of electrical and physical properties for long,
problem free service. The triple tandem extrusion of the screens
with the insulation provides optimum electrical characteristics.
Jacket
The Okolon jacket on this cable is a vulcanized chlorosulfonated
polyethylene base compound which is mechanically rugged, flame,
radiation, and oil resistant. |
|
Applications
Okoguard shielded Okolon Type MV-105 power cables are recommended for use as
feeder circuits in electric utility generating stations, for distribution
circuits, and for feeders or branch circuits in industrial and commercial
installations. Type MV cables may be installed in wet or dry locations,
indoors or outdoors (exposed to sunlight), in any raceway or underground
duct, directly buried if installed in a system with a grounding conductor in
close proximity that conforms with NEC Section 250.4(A)(5), or messenger
supported in industrial establishments and electric utilities. Sizes 1/0 AWG
and larger may also be installed in cable tray.
Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.
Strand Screen: Extruded semiconducting EPR strand screen. Meets or
exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 &
S-97-682, AEIC CS8, CSA C68.3 or UL 1072.
Insulation: Meets or exceeds electrical and physical requirements
of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3, and UL 1072.
Insulation Screen: Extruded semiconducting EPR insulation screen.
Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA
WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.
Shield: 5 mil coated copper tape helically applied with 25%
nominal overlap.
Jacket: Meets or exceeds electrical and physical requirements of
ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.3 and UL 1072 for
chlorosulfonated polyethylene jackets. UL Listed as Type MV-105, sunlight
resistant and for use in cable tray in accordance with UL 1072. CSA C68-3
listed and rated FT4 (1/0 and larger) and -25°C.
Product Features
- Triple tandem extruded, all EPR system.
- Okoguard cables meet or exceed all recognized industry standards
(UL, CSA, AEIC, NEMA/ICEA, IEEE, CSA).
- 105°C continuous operating temperature.
- 140°C emergency rating.
- 250°C short circuit rating.
- Passes UL and IEEE 383 and 1202 (1/0 AWG and larger) Vertical Tray
Flame Test.
- Excellent corona resistance.
- Screens are clean stripping.
- Exceptional resistance to “treeing”.
- Exceptional resistance to moisture.
- Resistant to most oils, acids, and alkalies.
- Sunlight resistant.
- For Cable Tray Use; 1/0 AWG and larger.
- CSA FT4 and -25°C.
- Improved Temperature Rating.
|
1-Catalog
Number (1)
2-Conductor Size AWG or kcmil
3-Conductor Size -mm2
4-Approx. Dia. over Insulation (in.)
5-Approx. Dia. over Screen (in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches |
9-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000’
11-Approx. Ship Weight lbs./1000’
12-Ampacities (2) Conduit in Air
13-Ampacities (3)
Underground Duct
14-Ampacities (4) Cable Tray
15-Conduit Size Inches
(5)* |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
15 |
|
Okoguard Insulation: 115 mils (2.92mm), 100% Insulation Level
|
|
114-23-2717
114-23-2719
114-23-2721
114-23-2723
|
6
4
2
1 |
13.3
21.2
33.6
42.4 |
0.44
0.48
0.54
0.58 |
0.50
0.54
0.60
0.64 |
60
60
60
60 |
1.52
1.52
1.52
1.52 |
0.66
0.71
0.76
0.80 |
16.8
18.0
19.3
20.3 |
305
375
480
550 |
335
405
515
590 |
93
120
165
190 |
97
125
165
185 |
|
2
2
2 1/2
2 1/2 |
|
114-23-2725
114-23-2727
114-23-2729
|
1/0
2/0
3/0
|
53.5
67.4
85.0
|
0.61
0.65
0.70
|
0.67
0.71
0.76
|
60
60
80
|
1.52
1.52
2.03
|
0.83
0.87
0.97
|
21.1
22.1
24.6
|
630
735
915
|
670
790
975
|
215
255
290
|
215
245
275
|
215
250
290
|
2
1/2
2 1/2
3
|
|
114-23-2731
114-23-2733
114-23-2737
|
4/0
250
350
|
107.0
127.0
177.0
|
0.75
0.80
0.89
|
0.81
0.86
0.95
|
80
80
80
|
2.03
2.03
2.03
|
1.02
1.07
1.16
|
25.9
27.2
29.5
|
1070
1215
1575
|
1135
1285
1660
|
330
365
440
|
315
345
415
|
335
370
460
|
3
3
3 1/2
|
|
114-23-2743
114-23-2749
114-23-2751
|
500
750
1000
|
253.0
380.0
507.0
|
1.03
1.19
1.34
|
1.07
1.26
1.42
|
80
80
80
|
2.03
2.03
2.03
|
1.28
1.47
1.63
|
32.5
37.3
41.4
|
2095
2980
3860
|
2195
3160
4035
|
535
655
755
|
500
610
690
|
575
745
890
|
3 1/2
4
5
|
|
Okoguard Insulation: 140 mils (3.56mm), 133% Insulation Level
|
115-23-2917
115-23-2919
115-23-2921
115-23-2923 |
6
4
2
1
|
13.3
21.2
33.6
42.4
|
0.50
0.54
0.60
0.63
|
0.56
0.60
0.66
0.69
|
60
60
60
60
|
1.52
1.52
1.52
1.52
|
0.72
0.77
0.82
0.85
|
18.3
19.6
20.8
21.6
|
345
420
525
595
|
385
460
565
650
|
93
120
165
190
|
97
125
165
185
|
|
2
2 1/2
2 1/2
2 1/2
|
115-23-2925
115-23-2927
115-23-2929 |
1/0
2/0
3/0
|
53.5
67.4
85.0
|
0.67
0.71
0.75
|
0.73
0.77
0.81
|
60
80
80
|
1.52
2.03
2.03
|
0.89
0.97
1.02
|
22.6
24.6
25.9
|
680
830
965
|
735
885
1020
|
215
255
290
|
215
245
275
|
215
250
290
|
2 1/2
3
3
|
115-23-2931
115-23-2933
115-23-2937 |
4/0
250
350
|
107.0
127.0
177.0
|
0.81
0.86
0.95
|
0.87
0.92
1.01
|
80
80
80
|
2.03
2.03
2.03
|
1.07
1.13
1.22
|
27.2
28.7
31.0
|
1130
1285
1645
|
1195
1365
1745
|
330
365
440
|
315
345
415
|
335
370
460
|
3
3 1/2
3 1/2
|
115-23-2943
115-23-2949
115-23-2951 |
500
750
1000
|
253.0
380.0
507.0
|
1.07
1.25
1.40
|
1.15
1.33
1.47
|
80
80
80
|
2.03
2.03
2.03
|
1.36
1.54
1.68
|
34.5
39.1
42.7
|
2195
3075
3925
|
2295
3250
4100
|
535
655
755
|
500
610
690
|
575
745
890
|
4
5
5
|
|
Aluminum
Conductors
(1) Aluminum conductors are available on special order. To order aluminum
conductors, change the first three digits of the catalog number from 114 to
134 and 115 to 135, respectively.Ampacities
(2) Ampacities are in accordance with Table 310.73 of the NEC for three
single Type MV-105 conductors, or single conductors twisted together (triplexed)
and installed in an isolated conduit in air at an ambient temperature of
40°C and a conductor temperature of 105°C.
(3) Ampacities are in accordance with Table 310.77 of the NEC for three
single conductors or triplexed cable in one underground raceway, three feet
deep with a conductor temperature of 105°C, 100% Load Factor, an ambient
earth temperature of 20°C, and thermal resistance (RHO) of 90.
(4) Ampacities based on single Type MV-105 conductors, or single
conductors twisted together (triplexed, quadruplexed, etc.), size1/0 AWG and
larger, installed in uncovered cable tray in accordance with Section 392.13
of the NEC at an ambient temperature of 40°C and a conductor temperature
rating of 105°C. In accordance with NEC Section 392.13(b), the ampacities
are 75% of the values given in NEC Table 310.69 (copper conductors). Where
the cable tray is covered for more than six feet with solid unventilated
covers, the ampacities shall not exceed 93% of the values shown above.
Refer to the NEC, IEEE/ICEA-S-135 Power Cable Ampacities, or the Okonite
Engineering Data Bulletin for installation in duct banks, multiple point
grounded shields, other ambient temperatures, circuit configurations or
installation requirements.
(5) Recommended size of rigid or nonmetallic conduit for three conductors
based on 40% maximum fill.
*The jam ratio conduit l.D. to cable O.D. should be checked to avoid possible jamming.
|
|