| Product Data Section 2: Sheet 6 |
|||
|
COMPACT STRAND |
printer friendly version (PDF) | ||
Okoguard®-Okobond® Type MV-105 5/8kV Okobond Shielded Power Cable One Okopact® (Compact Stranded) Copper Conductor 105°C Rating 5kV-133% or 8kV-100% Insulation Level For Direct Burial & Conduit Use
|
B Strand Screen-Extruded Semiconducting EPR C Insulation-Okoguard EPR D Insulation Screen-Extruded Semiconducting EPR E Shield-6 mil Okobond Copper Tape F Jacket-Okolene
|
|
Shield A 6 mil copper longitudinal corrugated Okobond shield is applied over the extruded semiconducting insulation screen with a sealed overlap to make the cable core impervious to moisture penetration. The tape is copolymer coated to provide a bond at the overlap and to the outer jacket. This construction provides a substantially lower shield resistance compared to a tight helically applied copper tape. The tape shield resistance is also extremely stable for the life of the cable. Jacket Applications
Specifications Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072. Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072. Insulation Screen: Extruded semiconducting EPR insulation screen applied directly over the insulation. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072. Shield: 6 mil longitudinal corrugated, copolymer coated copper shield with a 0.25" overlap. Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 and UL 1072 for polyethylene jackets. UL Listed as Type MV-105, sunlight resistant in accordance with UL 1072. Okoguard-Okobond cables are also available with 5, 25, 35 and 69kV ratings. Product Features
|
| Okoguard Insulation:115 mils(2.91mm), 5kV-133% or 8kV-100% Insulation Level |
|
Minimum Manufacturing Quantity for non-stock items is 5000'
Aluminum Conductors
Ampacities (3) Ampacities are in accordance with Table 310.81 of the NEC for a 5kV insulated single conductor directly buried with a conductor temperature rating of 105°C, ambient earth temperature of 20°C, 100% Load Factor, thermal resistance (RHO) of 90, 7 1/2 inch spacing between conductor center lines, and 24 inch spacing between circuits. Refer to Table 310.81 for 8kV ampacities. (4) Ampacities are in accordance with Table 310.77 of the NEC for 5kV three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90. Refer to Table 310.77 for 8kV ampacities. Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installations requirements. (5) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill. *The jam ratio conduit I.D. to cable O.D. should be checked to avoid possible jamming. |
| D/07110206 | |
| BACK TO DATA SHEET INDEX |