THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 6
Okoguard®-Okobond® Type MV-105
5/8kV Okobond Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor105°C Rating
5kV-133% or 8kV-100% Insulation Level
For Direct Burial & Conduit Use
UL

A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shield-6 mil Okobond Copper Tape

F Jacket-Okolene


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Shield
A 6 mil copper longitudinal corrugated Okobond shield is applied over the extruded semiconducting insulation screen with a sealed overlap to make the cable core impervious to moisture penetration. The tape is copolymer coated to provide a bond at the overlap and to the outer jacket. This construction provides a substantially lower shield resistance compared to a tight helically applied copper tape. The tape shield resistance is also extremely stable for the life of the cable.

Jacket
The Okolene® jacket on this cable is a polyethylene compound which is mechanically rugged; oil and moisture resistant. The outer jacket is firmly bonded to the corrugated copper shield for a moisture barrier.

Applications
Okoguard shielded Okobond Type MV-105 power cables are recommended for use by electric utilities and industrial operations for distribution circuits, and for feeders or branch circuits in industrial and commercial installations.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 310.7, or messenger supported in industrial establishments and electric utilities. Okoguard-Okobond is especially suited for underground applications in duct or direct burial where it is subject to excessive water.

Specifications
Conductor: Uncoated copper, stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen applied directly over the insulation. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: 6 mil longitudinal corrugated, copolymer coated copper shield with a 0.375" overlap.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 and UL 1072 for polyethylene jackets.

UL Listed as Type MV-105, sunlight resistant in accordance with UL 1072. CSA Listed to C68-3.

Product Features

  • Triple tandem extruded, all EPR system.
  • Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE).
  • 105°C continuous operating temperature.
  • 140°C emergency rating.
  • 250°C short circuit rating.
  • Excellent corona resistance.
  • Provides "flat line" corona response.
  • Screens are clean stripping.
  • Exceptional resistance to "treeing."
  • Low shield resistance.
  • Moisture resistant.
  • Resistant to most oils, acids and alkalies.
  • Sunlight resistant.
  • Improved Temperature Rating.

  • Okoguard Insulation:115 mils(2.91mm),
    5kV-133% or 8kV-100% Insulation Level
    1-Catalog Number(1)
    2-Conductor Size - AWG or kcmil
    3-Conductor Size - mm2
    4-Approx. Dia. over Insulation(in.)
    5-Approx. Dia. over Screen(in.)
    6-Jacket Thickness - mils
    7-Jacket Thickness - mm
    8-Approx. O.D. - Inches
    09-Approx. O.D. - mm
    10-Approx. Net Weight lbs./1000'
    11-Approx. Ship Weight lbs./1000'
    12-Ampacities Conduit in Air(2)
    13-Ampacities Direct Burial(3)
    14-Ampacities Underground Duct(4)
    15-Conduit Size-Inches*(5)

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
    114-23-6860 6 13.3 0.44 0.50 60 1.52 .71 17.9 315 380 84 150 92 2
    114-23-6861 4 21.2 0.48 0.54 60 1.52 .75 19.0 385 465 110 195 120 2
    114-23-6862 2 33.6 0.54 0.60 60 1.52 .81 20.4 490 585 145 250 155 2 1/2
    114-23-6865 2/0 67.4 0.65 0.71 80 2.03 .96 24.3 775 925 225 365 235 3
    114-23-6867 4/0 107.0 0.75 0.81 80 2.03 1.11 26.8 1070 1220 305 465 310 3
    114-23-6869 350 177.0 0.89 0.95 80 2.03 1.20 30.5 1570 1800 430 615 415 3 1/2
    114-23-6872 500 253.0 1.01 1.07 80 2.03 1.32 33.5 2090 2380 530 745 505 4
    114-23-6875 750 380.0 1.19 1.27 80 2.03 1.52 38.5 2985 3305 665 910 630 5
    114-23-6878 1000 507.0 1.35 1.43 80 2.03 1.67 42.4 3830 4220 770 1055 720 5

    Minimum Manufacturing Quantity for non-stock items is 5000'

    Aluminum Okopact Conductors

    (1) Aluminum Okopact conductors are available on special order. To order aluminum Okopact conductors, change the first three digits of the catalog number from 114 to 134.

    Ampacities

    (2) Ampacities are in accordance with Table 310-73 of the NEC for 5kV three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C. Refer to Table 310-73 for 8kV ampacities

    (3) Ampacities are in accordance with Table 310-81 of the NEC for a 5kV insulated single conductor directly buried with a conductor temperature rating of 105°C, ambient earth temperature of 20°C, 100% Load Factor, thermal resistance (RHO) of 90, 7 1/2 inch spacing between conductor center lines, and 24 inch spacing between circuits. Refer to Table 310-81 for 8kV ampacities.

    (4) Ampacities are in accordance with Table 310-77 of the NEC for 5kV three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90. Refer to Table 310-77 for 8kV ampaciies.

    Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installations requirements.

    (5) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

    *The jam ratio conduit I.D. to cable O.D. should be checked to avoid possible jamming.

    C/97010206
    BACK TO DATA SHEET INDEX