THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 5
Okoguard®-Okolon® Type MV-105
5/8kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
5kV-133% or 8kV-100% Insulation Level
For Cable Tray Use-Sunlight Resistant
UL
A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shielding-Copper Tape

F Jacket-Okolon


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okolon jacket on this cable is a vulcanized chlorosulfonated polyethylene based compound which is mechanically rugged, flame, radiation, and oil resistant.

Applications
Okoguard Shielded-Okolon power cables are recommended for use as feeder circuits in utility generating plants, in distribution applications and for primary circuits.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 310.7, or messenger supported in industrial establishments and electric utilities. Sizes 1/0 AWG and larger may also be installed in cable tray.

Specifications
Conductor: Annealed uncoated copper Compact Stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds the electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen applied directly over the insulation. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: 5 mil coated copper tape helically applied.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-68-516 and UL 1072 for chlorosulfonated polyethylene jackets.

UL Listed as Type MV-105, sunlight resistant and for use in cable tray in accordance with UL 1072. CSA Listed to C68-3.

Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE, CSA). 105°C continuous operating temperature. 140°C emergency rating. 250°C short circuit rating. Passes UL and IEEE 383 and 1202 (1/0 AWG and larger) Vertical Tray Flame Test. Excellent corona resistance. Radiation resistant. Screens are clean stripping. Exceptional resistance to "treeing". Moisture resistant. Resistant to most oils, acids, and alkalies Improved Temperature Rating.


Okoguard Insulation:115 mils(2.92mm),
5kV-133% or 8kV-100% Insulation Level
1-Catalog Number(1)
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(2)
13-Ampacities Underground Duct (3)
14-Ampacities Cable Tray(4)
15-Conduit Size-Inches*(5)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
114-23-2717 6 13.3 0.44 0.50 60 1.52 0.70 17.8 315 365 84 92 - 2
114-23-2719 4 21.2 0.48 0.54 60 1.52 0.75 18.9 390 460 110 120 - 2
114-23-2721 2 33.6 0.54 0.60 60 1.52 0.80 20.4 490 570 145 155 - 2 1/2
114-23-2723 1 42.4 0.57 0.63 60 1.52 0.83 21.2 560 670 175 180 - 2 1/2
114-23-2725 1/0 53.5 0.61 0.67 60 1.52 0.87 22.1 645 755 200 210 220 2 1/2
114-23-2727 2/0 67.4 0.65 0.71 80 2.03 0.93 24.2 795 900 225 235 245 3
114-23-2729 3/0 85.0 0.69 0.75 80 2.03 1.00 25.4 925 1030 270 270 290 3
114-23-2731 4/0 107.0 0.75 0.81 80 2.03 1.05 26.7 1090 1195 305 310 335 3
114-23-2733 250 127.0 0.79 0.85 80 2.03 1.10 27.8 1235 1340 355 345 370 3 1/2
114-23-2737 350 177.0 0.89 0.95 80 2.03 1.20 30.4 1595 1725 430 415 460 3 1/2
114-23-2743 500 253.0 1.01 1.07 80 2.03 1.31 33.4 2120 2270 530 505 580 4
114-23-2749 750 380.0 1.19 1.27 80 2.03 1.51 38.4 3020 3235 665 630 750 5
114-23-2751 1000 507.0 1.35 1.42 80 2.03 1.67 42.4 3880 4285 770 720 900 5
Minimum Manufacturing Quantity for non-stock items is 5000'

Aluminum Okopact Conductors

(1) Aluminum Okopact conductors are available on special order. To order aluminum Okopact conductors, change the first three digits of the catalog number from 114 to 134.

Ampacities

(2) Ampacities are in accordance with Table 310-73 of the NEC for three single Type MV-105 5kV conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C. Refer to Table 310-73 for 8kV ampacities.

(3) Ampacities are in accordance with Table 310-77 of the NEC for three single 5kV conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90. Refer to Table 310-77 for 8kV ampacities

(4) Ampacities based on single Type MV-105 5kV conductors, or single conductors twisted together (triplexed, quadruplexed, etc.), size 1/0 AWG and larger, installed in uncovered cable tray in accordance with Section 318-13 of the NEC at an ambient temperature of 40°C and a conductor temperature rating of 105°C. In accordance with NEC Section 318-13(b) the ampacities are 75% of the values given in NEC Table 310-69 (copper conductors). Where the cable tray is covered for more than six feet with solid unventilated covers, the ampacities shall not exceed 93% of the values shown above. Refer to Table 310-69 for 8kV ampacities.

Refer to the NEC, IEEE/ICEA-S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(5) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possible jamming.

C/96110205
BACK TO DATA SHEET INDEX