THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 4
Okoguard®-Okoseal® Type MV-105
5/8kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
5kV-133% or 8kV-100% Insulation Level
UL SA *
A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shielding-Copper Tape

F Jacket-Okoseal


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil, acids and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 310.7, or messenger supported in industrial establishments and electric utilities.

Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen applied directly over the insulation. Meets or exceeds electrical and physical requirements of ICEA S93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: 5 mil bare copper tape helically applied.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-68-516, and UL 1072 for polyvinyl chloride jackets.

UL Listed as Type MV-105 and sunlight resistant, in accordance with UL 1072.

A flame retardant construction, size 1/0 AWG and larger, for installation in cable tray is also  available. This construction is UL labeled "MV-105 FOR CT USE." The "For CT Use" items, Sizes 4/0 AWG and larger also meet the IEEE 1202-1991 vertical tray flame test.

Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating temperature. 140°C emergency rating. 250°C short circuit rating. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Exeptional resistance to moisture. Resistant to most oils, acids, and alkalies. Sunlight resistant. Improved Temperature Rating.

* Cables listed for cable tray use are also CSA listed & meet the requirements of C68.3.


Okoguard Insulation:115 mils(2.92mm),
5kV-133% or 8kV-100% Insulation Level
1-Catalog Number(1)
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
08-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(2)
13-Ampacities Underground Duct(3)
14-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14
114-23-3817 6 13.3 0.44 0.50 60 1.52 0.64 16.3 285 320 84 92 2
114-23-3819 4 21.2 0.48 0.54 60 1.52 0.68 17.4 355 395 110 120 2
114-23-3821 2 33.6 0.54 0.60 60 1.52 0.74 18.8 455 515 145 155 2 1/2
114-23-3823 1 42.4 0.57 0.63 60 1.52 0.77 19.6 525 585 175 180 2 1/2
114-23-3825 1/0 53.5 0.61 0.67 60 1.52 0.81 20.6 610 670 200 210 2 1/2
114-23-3827 2/0 67.4 0.65 0.71 60 1.52 0.85 21.6 711 771 225 235 3
114-23-3829 3/0 85.0 0.69 0.75 80 2.03 0.94 23.9 875 965 270 270 3
114-23-3831 4/0 107.0 0.75 0.81 80 2.03 1.00 25.3 1045 1135 305 310 3
114-23-3833 250 127.0 0.79 0.85 80 2.03 1.03 26.3 1180 1270 355 345 3
114-23-3837 350 177.0 0.89 0.95 80 2.03 1.13 28.8 1535 1630 430 415 3 1/2
114-23-3843 500 253.0 1.01 1.07 80 2.03 1.25 31.8 2055 2190 530 505 3 1/2
114-23-3849 750 380.0 1.19 1.27 80 2.03 1.45 36.9 2945 3140 665 630 4
114-23-3851 1000 507.0 1.35 1.42 80 2.03 1.61 40.8 3795 4060 770 720 5

Cables listed for Cable Tray Use - meet the vertical tray flame test requirements of UL 1072, IEEE 383, IEEE 1202 and CSA FT4

114-23-3866 4/0 107.0 0.75 0.81 80 2.03 1.00 25.3 1045 1135 305 310 3
114-23-3846 500 253.0 1.01 1.07 80 2.03 1.25 31.8 2055 2190 530 505 3 1/2
114-23-3873 750 380.0 1.19 1.27 80 2.03 1.45 36.9 2945 3140 665 630 4
114-23-3855 1000 507.0 1.35 1.42 80 2.03 1.61 40.8 3795 4060 770 720 5
Authorized stock item. Available from our Customer Service Centers.

Minimum Manufacturing Quantity for non-stock items is 5000'

Aluminum Okopact Conductors

(1) Aluminum Okopact conductors are available on special order. To order aluminum Okopact conductors change the first three digits of the catalog number from 114 to 134.

Ampacities

(2) Ampacities are in accordance with Table 310-73 of the NEC for three single Type MV-105 5kV conductors or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C. Refer to Table 310-73 for 8kV ampacities

(3) Ampacities are in accordance with Table 310-77 of the NEC for three single 5kV conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C and thermal resistance (RHO) of 90. Refer to Table 310-77 for 8kV ampacities.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(4) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit l.D. to cable O.D. should be checked to avoid possible jamming.

F/06080204