THE OKONITE COMPANY
Product Data
Section 2: Sheet 37
Okoguard® CIC
URO-J Cable-In-Conduit
15 to 35kV Primary Underground Distribution Cable-Full Neutral
One Aluminum Conductor/105°C Rating
100% and 133% Insulation Level
A Conductor-Stranded Aluminum

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Concentric Wires-Bare Copper

F Encapsulating Jacket-Okolene

G Conduit-Flexible Polyethylene


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Okonite URO cables are factory installed within a polyethylene conduit. This URO-CIC (Cable-in-Conduit) has many of the advantages of a jacketed cable provided the ends of the conduit are sealed.

The annealed copper concentric wires are uniformly spaced around the insulation screen and are sufficient in number to supply full conductivity of the power conductor. The flexible polyethylene conduit provides an economical factory assembled cable-in-conduit with mechanical protection against accidental dig-in, and easier installation.

Applications
CIC cable with a full neutral provides reliable circuit security in underground distribution systems. They provide greater mechanical protection against accidental dig-in than the direct burial UD cables normally installed. The Okolene® duct protects the cable in adverse soil conditions (stone, coarse backfill, corrosive soil conditions, etc.).

The Okoguard CIC cable is commonly installed where the ground above the cable will be finished with asphalt paving, landscaping, structures, etc.

URO-CIC is particularly advantageous when used in landscaped residential areas since system expansions may be accomplished without disturbing the lawn and shrubbery.

Specifications
Central Conductor: Aluminum per ASTM B-609 Class B stranded per B-231.

Conductor Screen: Extruded semiconducting ethylene-propylene rubber meets or exceeds the requirements of ICEA S-94-649/NEMA WC74 and AEIC CS8.

Insulation: Extruded Okoguard meets or exceeds the requirements of ICEA S-94-649/NEMA WC74 and AEIC CS8.

Insulation Screen: Extruded semiconducting ethylene-propylene rubber meets or exceeds the requirements of ICEA S-94-649/NEMA WC74 and AEIC CS8.

Concentric Conductor: Bare copper wires per ICEA S-94-649/NEMA WC74. Conductivity equal to central conductor.

Jacket: Black Okolene with red extruded stripes meets or exceeds the requirements of ICEA S-94-649/NEMA WC74 for polyethylene jackets.

Conduit: Extruded high density polyethylene Schedule 40 pipe per ASTM D2104 and NEMA TC7.

Product Features  

  • Triple tandem extruded, all EPR cable. 
  • Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE).
  • Listed by UL as MV90
  • Listed by CSA as C68.3 
  • 90°C continuous operating temperature 
  • 130°C emergency rating 
  • 250°C short circuit rating 
  • Excellent corona resistance. 
  • Screens are clean stripping. 
  • Exceptional resistance to "treeing". 
  • Outstanding impact strength and abrasion resistance. 
  • Additional protection against dig-in. 
  • Meets or exceeds requirements of applicable industry standards. 
  • Very low moisture absorption. 
  • Excellent resistance to weather and most chemicals. 
  • Easy to splice and terminate. 
  • Design Options: 
  • Filled strand
  • Copper central conductor 
  • Improved Temperature Rating.

Okoguard insulation system has been tested and qualified for operation at 105°C continuous and 140°C emergency operating temperature.


1-Catalog Number
2-Conductor Size - AWG or kcmil/Number of Strands
3-Nominal O.D. Over Insulation
4-Nominal O.D. Over Insulation Screen
5-Copper Neutral Wires - No. x AWG
6-Nominal O.D. Over Concentric Wires
07-Okelene Conduit Nominal Size
08-Okelene Conduit(O.D. (in.)
09-Approx. Net Weight - lbs./1000'
10-Approx. Ship Weight - lbs./1000'
11-Ampacity(1)
12-Minimum Bending Radius(in.)
1 2 3 4 5 6 7 8 9 10 11 12
Okoguard Insulation:175 mils(4.45mm), 100% Insulation Level-15kV
161-23-2110 2(7x) 0.68 0.76 10 x 14 1.00 1 1/4 1.66 751 1041 120 18
161-23-2116 1(19x) 0.72 0.80 14 x 14 1.03 1 1/2 1.90 890 1280 135 21
161-23-2122 1/0(19x) 0.76 0.84 16 x 14 1.07 1 1/2 1.90 970 1360 155 21
161-23-2125 2/0(19x) 0.81 0.88 14 x 12 1.15 1 1/2 1.90 1100 1490 175 21
161-23-2128 3/0(19x) 0.86 0.93 16 x 12 1.20 2 2.38 1380 1940 200 26
161-23-2131 4/0(19x) 0.91 0.99 14 x 10 1.30 2 2.38 1575 2265 230 26
161-23-2134 250(37x) 0.97 1.04 16 x 10 1.36 2 2.38 1740 2430 255 26
161-23-2140 350(37x) 1.07 1.17 20 x 10 1.58 2 2.38 2170 2860 300 26
Okoguard Insulation:220 mils(5.59mm), 133% Insulation Level-15kV
161-23-3110 2(7x) 0.78 0.85 10 x 14 1.09 1 1/2 1.90 897 1287 120 21
161-23-3116 1(19x) 0.81 0.89 14 x 14 1.13 1 1/2 1.90 973 1363 135 21
161-23-3122 1/0(19x) 0.85 0.93 16 x 14 1.17 1 1/2 1.90 1053 1445 155 21
161-23-3125 2/0(19x) 0.90 0.97 14 x 12 1.24 2 2.38 1351 2041 175 26
161-23-3128 3/0(19x) 0.95 1.02 16 x 12 1.29 2 2.38 1475 2165 200 26
161-23-3131 4/0(19x) 1.01 1.08 14 x 10 1.39 2 2.38 1678 2368 230 26
161-23-3134 250(37x) 1.06 1.16 16 x 10 1.48 2 2.38 1877 2567 255 26
161-23-3140 350(37x) 1.17 1.27 20 x 10 1.58 2 1/2 2.88 2462 3362 300 32
Okoguard Insulation:260 mils(6.60mm), 100% Insulation Level-25kV
161-23-4116 1(19x) 0.90 0.97 14 x 14 1.21 2 2.38 1212 1902 135 26
161-23-4122 1/0(19x) 0.94 1.01 16 x 14 1.25 2 2.38 1298 1985 150 26
161-23-4125 2/0(19x) 0.98 1.05 14 x 12 1.33 2 2.38 1439 2129 175 26
161-23-4128 3/0(19x) 1.03 1.13 16 x 12 1.40 2 2.38 1595 2285 200 26
161-23-4131 4/0(19x) 1.09 1.19 14 x 10 1.50 2 2.38 1806 2496 225 26
161-23-4134 250(37x) 1.14 1.24 16 x 10 1.56 2 1/2 2.88 1980 2670 250 32
161-23-4140 350(37x) 1.25 1.35 20 x 10 1.73 2 1/2 2.88 2637 3537 300 32
Okoguard Insulation:320 mils(8.76mm), 133% Insulation Level-25kV
161-23-5116 1(19x) 1.02 1.12 14 x 14 1.36 2 2.38 1370 2060 135 26
161-23-5122 1/0(19x) 1.06 1.16 16 x 14 1.40 2 2.38 1461 2151 150 26
161-23-5125 2/0(19x) 1.10 1.20 14 x 12 1.47 2 2.38 1611 2301 175 26
161-23-5128 3/0(19x) 1.15 1.25 16 x 12 1.52 2 1/2 2.88 2036 3226 200 32
161-23-5131 4/0(19x) 1.21 1.31 14 x 10 1.62 2 1/2 2.88 2257 3447 225 32
161-23-5134 250(37x) 1.27 1.37 16 x 10 1.74 2 1/2 2.88 3387 4577 250 32
161-23-5140 350(37x) 1.37 1.47 20 x 10 1.85 2 1/2 2.88 2818 4008 300 32
Okoguard Insulation:345 mils(8.76mm), 100% Insulation Level-35kV
161-23-6122 1/0(19x) 1.11 1.21 16 x 14 1.45 2 2.38 1521 1951 150 26
161-23-6125 2/0(19x) 1.15 1.25 14 x 12 1.52 2 1/2 2.88 1966 3156 170 32
161-23-6128 3/0(19x) 1.20 1.30 16 x 12 1.57 2 1/2 2.88 2101 3291 200 32
161-23-6131 4/0(19x) 1.26 1.36 14 x 10 1.74 2 1/2 2.88 2391 3581 225 32
161-23-6134 250(37x) 1.32 1.42 16 x 10 1.79 2 1/2 2.88 2575 3765 245 32
Okoguard Insulation:420 mils(10.7mm), 133% Insulation Level-35kV
161-23-7122 1/0(19x) 1.26 1.36 16 x 14 1.60 2 1/2 2.88 2013 3203 150 32
161-23-7125 2/0(19x) 1.31 1.41 14 x 12 1.74 2 1/2 2.88 2241 3431 170 32
161-23-7128 3/0(19x) 1.36 1.46 16 x 12 1.79 2 1/2 2.88 2386 3576 200 32
Minimum Manufacturing Quantity is 10,000 ft.

Standard Package - 1,500 ft. N.R. Reel

(1) Ampacities

Ampacities for a full neutral single phase system based on conductor operating temperature of 90°C, direct buried 36" deep, 20°C ambient temperature, thermal resistivity RHO-90, 100% load factor .

A/93100237