THE OKONITE COMPANY
Product Data
Section 2: Sheet 36
Okoguard® CIC
URO Cable-In-Conduit
15 to 35kV Primary Underground Distribution Cable-Full Neutral
One Aluminum Conductor/90°C Rating
100% and 133% Insulation Level
.

A Conductor-Stranded Aluminum

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Concentric Wires-Bare Copper

F Conduit-Flexible Polyethylene


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Okonite URO cables are factory installed within a polyethylene conduit. This URO-CIC (Cable-in-Conduit) has many of the advantages of a jacketed cable provided the ends of the conduit are sealed.

The annealed copper concentric wires are uniformly spaced around the insulation screen and are sufficient in number to supply full conductivity of the power conductor. The flexible polyethylene conduit provides an economical factory assembled cable-in-conduit with mechanical protection against accidental dig-in, and easier installation.

Applications
CIC cable with a full neutral provides reliable circuit security in underground distribution systems. They provide greater mechanical protection against accidental dig-in than the direct burial UD cables normally installed. The Okolene® duct protects the cable in adverse soil conditions (stone, coarse backfill, corrosive soil conditions, etc.).

The Okoguard CIC cable is commonly installed where the ground above the cable will be finished with asphalt paving, landscaping, structures, etc.

URO-CIC is particularly advantageous when used in landscaped residential areas since system expansions may be accomplished without disturbing the lawn and shrubbery.

Specifications
Central Conductor: Aluminum per ASTM B-609 Class B stranded per B-231.

Conductor Screen: Extruded semiconducting ethylene-propylene rubber meets or exceeds the requirements of ICEA S-68-516 and AEIC CS6.

Insulation: Extruded Okoguard meets or exceeds the requirements of ICEA S-68-516 and AEIC CS6.

Insulation Screen: Extruded semiconducting ethylene-propylene rubber meets or exceeds the requirements of ICEA S-68-516 and AEIC CS6.

Concentric Conductor: Bare copper wires per ICEA S-68-516. Conductivity equal to central conductor.

Conduit: Extruded high density polyethylene Schedule 40 pipe per ASTM D2104 and NEMA TC7-1990.

Product Features Triple tandem extruded, all EPR cable. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE). 90°C continuous operating temperature 130°C emergency rating 250°C short circuit rating Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Outstanding impact strength and abrasion resistance. Additional protection against dig-in. Meets or exceeds requirements of applicable industry standards. Very low moisture absorption. Excellent resistance to weather and most chemicals. Easy to splice and terminate. Design Options: Filled strand Copper central conductor Improved Temperature Rating.

Okoguard insulation system has been tested and qualified for operation at 105°C continuous and 140°C emergency operating temperature.


1-Catalog Number
2-Conductor Size - AWG or kcmil/Number of Strands
3-Nominal O.D. Over Insulation
4-Nominal O.D. Over Insulation Screen
5-Copper Neutral Wires - No. x AWG
6-Nominal O.D. Over Concentric Wires
07-Okelene Conduit Nominal Size
08-Okelene Conduit(O.D. (in.)
09-Approx. Net Weight - lbs./1000'
10-Approx. Ship Weight - lbs./1000'
11-Ampacity(1)
12-Minimum Bending Radius(in.)
1 2 3 4 5 6 7 8 9 10 11 12
Okoguard Insulation:175 mils(4.45mm), 100% Insulation Level-15kV
161-23-2960 2(7x) 0.68 0.76 10 x 14 0.89 1 1/4 1.66 637 858 120 18
161-23-2966 1(19x) 0.72 0.80 13 x 14 0.92 1 1/4 1.66 708 927 135 18
161-23-2972 1/0(19x) 0.76 0.84 16 x 14 0.96 1 1/4 1.66 785 1004 155 18
161-23-2975 2/0(19x) 0.81 0.88 13 x 12 1.04 1 1/4 1.66 892 1111 175 18
161-23-2978 3/0(19x) 0.86 0.93 16 x 12 1.09 1 1/2 1.90 1071 1321 200 21
161-23-2981 4/0(19x) 0.91 0.99 13 x 10 1.19 1 1/2 1.90 1239 1489 230 21
161-23-2984 250(37x) 0.97 1.04 16 x 10 1.25 2 2.38 2088 2594 255 26
161-23-2990 350(37x) 1.07 1.17 20 x 10 1.38 2 2.38 2597 3103 300 26
Okoguard Insulation:220 mils(5.59mm), 133% Insulation Level-15kV
161-23-3960 2(7x) 0.78 0.85 10 x 14 0.98 1 1/4 1.66 703 922 120 18
161-23-3966 1(19x) 0.81 0.89 13 x 14 1.02 1 1/4 1.66 777 998 135 18
161-23-3972 1/0(19x) 0.85 0.93 16 x 14 1.06 1 1/2 1.90 924 1174 155 21
161-23-3975 2/0(19x) 0.90 0.97 13 x 12 1.13 1 1/2 1.90 1037 1287 175 21
161-23-3978 3/0(19x) 0.95 1.02 16 x 12 1.18 1 1/2 1.90 1156 1406 200 21
161-23-3981 4/0(19x) 1.01 1.08 13 x 10 1.28 2 2.38 1484 1980 230 26
161-23-3984 250(37x) 1.06 1.16 16 x 10 1.37 2 2.38 1677 2183 255 26
161-23-3990 350(37x) 1.17 1.27 20 x 10 1.47 2 2.38 1962 2488 300 26
Okoguard Insulation:260 mils(6.60mm), 100% Insulation Level-25kV
161-23-4966 1(19x) 0.90 0.97 13 x 14 1.10 1 1/2 1.90 912 1182 135 21
161-23-4972 1/0(19x) 0.94 1.01 16 x 14 1.14 1 1/2 1.90 995 1245 150 21
161-23-4975 2/0(19x) 0.98 1.05 13 x 12 1.22 2 2.38 1268 1774 175 26
161-23-4978 3/0(19x) 1.03 1.13 16 x 12 1.29 2 2.38 1418 1924 200 26
161-23-4981 4/0(19x) 1.09 1.19 13 x 10 1.39 2 2.38 1592 2098 225 26
161-23-4984 250(37x) 1.14 1.24 16 x 10 1.45 2 2.38 1765 2271 250 26
161-23-4990 350(37x) 1.25 1.35 20 x 10 1.55 2 1/2 2.88 2348 3044 300 32
Okoguard Insulation:320 mils(8.76mm), 133% Insulation Level-25kV
161-23-5966 1(19x) 1.02 1.12 13 x 14 1.25 2 2.38 1208 1714 135 26
161-23-5972 1/0(19x) 1.06 1.16 16 x 14 1.29 2 2.38 1296 1802 150 26
161-23-5975 2/0(19x) 1.10 1.20 13 x 12 1.36 2 2.38 1416 1922 175 26
161-23-5978 3/0(19x) 1.15 1.25 16 x 12 1.41 2 2.38 1548 2054 200 26
161-23-5981 4/0(19x) 1.21 1.31 13 x 10 1.51 2 2.38 1728 2234 225 26
161-23-5984 250(37x) 1.27 1.37 16 x 10 1.57 2 1/2 2.88 2197 2893 250 32
161-23-5990 350(37x) 1.37 1.47 20 x 10 1.67 2 1/2 2.88 2502 3198 300 32
Okoguard Insulation:345 mils(8.76mm), 100% Insulation Level-35kV
161-23-6972 1/0(19x) 1.11 1.21 16 x 14 1.34 2 2.38 1349 1855 150 26
161-23-6975 2/0(19x) 1.15 1.25 13 x 12 1.41 2 2.38 1471 1977 170 26
161-23-6978 3/0(19x) 1.20 1.30 16 x 12 1.46 2 2.38 1604 2110 200 26
161-23-6981 4/0(19x) 1.26 1.36 13 x 10 1.56 2 1/2 2.88 2078 2774 225 32
161-23-6984 250(37x) 1.32 1.42 16 x 10 1.62 2 1/2 2.88 2259 2955 245 32
161-23-6990 350(37x) 1.42 1.52 20 x 10 1.72 2 1/2 2.88 2568 3264 295 32
Okoguard Insulation:420 mils(10.7mm), 133% Insulation Level-35kV
161-23-7972 1/0(19x) 1.26 1.36 16 x 14 1.49 2 2.38 1528 2034 150 26
161-23-7975 2/0(19x) 1.31 1.41 13 x 12 1.57 2 1/2 2.88 1946 2642 170 32
161-23-7078 3/0(19x) 1.36 1.46 16 x 12 1.62 2 1/2 2.88 2087 2783 200 32
161-23-7981 4/0(19x) 1.42 1.52 13 x 10 1.72 2 1/2 2.88 2277 2973 225 32
161-23-7984 250(37x) 1.47 1.57 16 x 10 1.78 2 1/2 2.88 2992 3688 245 32
Minimum Manufacturing Quantity is 10,000 ft.

Standard Package - 1,500 ft. N.R. Reel

(1) Ampacities

Ampacities for a full neutral single phase system based on conductor operating temperature of 90°C, direct buried 36" deep, 20°C ambient temperature, thermal resistivity RHO-90, 100% load factor in accordance with ICEA S-68-516 Appendix F.

A/93100236
BACK TO DATA SHEET INDEX