| . A
Conductor-Stranded Aluminum
B Filled Strand-Semiconducting Material
C Strand Screen-Extruded Semiconducting EPR
D Insulation-Okoguard
E Insulation Screen-Extruded Semiconducting EPR
F Concentric Conductor-Bare Copper Wires
G Encapsulating Jacket-Okolene with Extruded ID
Stripes
Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber
(EPR) based, thermosetting compound, whose optimum balance of electrical and physical
properties is unequalled in other solid dielectrics. Okoguard insulation, with the
distinctive red color and a totally integrated EPR system, provides the optimum balance of
electrical and physical properties for long, problem free service.
The triple tandem extrusion of the screens with the insulation provides optimum
electrical characteristics.
The compressed conductors are filled with Okonite's proprietary semiconducting filler
material. This construction prevents the travel of water through the strands in the event
of a mechanical dig-in followed by external exposure to water.
An insulation screen of ethylene-propylene rubber is extruded over the insulation. The
copper concentric wires are uniformly spaced around the insulation screen. The overall
polyethylene jacket provides protection against mechanical damage and corrosion.
Product identification is provided through the use of three red stripes placed 120°
apart in the black jacket. |