THE OKONITE COMPANY
Product Data
Section 2: Sheet 30
OkoguardŽ URO
15kV Underground Primary Distribution Cable
Aluminum Conductor/105°C Rating
133% Insulation Level
A Conductor-Stranded Aluminum

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard

D Insulation Screen-Extruded Semiconducting EPR

E Concentric Conductor-Annealed Coated Copper Wires


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem-free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

An insulation screen of ethylene-propylene rubber is extruded over the insulation. The annealed coated copper wires are uniformly spaced around the insulation screen.

Applications
Okoguard URO cables provide excellent circuit longevity in underground residential distribution systems. They can be buried direct or installed in underground ducts or conduits.

Specifications
Central Conductor: Aluminum per ASTM B-609, Class B stranded per B-231.

Conductor Screen: Extruded semiconducting ethylene-propylene rubber meets or exceeds the requirements of  ICEA S-94-649/NEMA WC74 & S-97-682 and AEIC CS8.

Insulation: Extruded Okoguard meets or exceeds the requirements of  ICEA S-94-649/NEMA WC74 & S-97-682 for ethylene-propylene rubber and AEIC CS8.

Insulation Screen: Extruded semiconducting ethylene-propylene rubber meets or exceeds the requirements of  ICEA S-94-649/NEMA WC74 & S-97-682 and AEIC CS8.

Concentric Conductor: Annealed coated copper wires.

Product Features  

  • Triple tandem extruded, all EPR system 
  • Okoguard cables meet or exceed NEMA/ICEA standards and REA U-1. 
  • 90°C continuous operating temperatures 
  • 130°C emergency rating 
  • 250°C short circuit rating 
  • Excellent corona resistance. 
  • Low dielectric constant and power factor. 
  • Screens are clean stripping. 
  • Exceptional resistance to "treeing". 
  • Moisture resistant. 
  • Excellent resistance to most chemicals. 
  • Design Options:
  • Additional conductor sizes
  • Filled strand
  • Copper central conductor 
  • Improved Temperature Rating.

 Okoguard insulation system has been tested and qualified for operation at 105°C continuous and 140°C emergency operating temperature.


Okoguard Insulation: 220 mils 133% Insulation Level
1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Nominal Dia. over Insulation
4-Nominal Dia. over Insulation Screen
5-Copper Neutral - No. x AWG
06-Nominal O.D. - Inches
07-Approx. Net Weight - lbs./1000'
08-Approx. Ship Weight - lbs./1000'
09-Ampacity Direct Burial(1)
10-Ampacity Duct(1)
1 2 3 4 5 6 7 8 9 10
FULL NEUTRAL
161-23-3910 2(7x) 0.78 0.85 10 x 14 0.98 481 571 170 120
161-23-3916 1(19x) 0.81 0.89 14 x 14 1.02 555 645 195 135
161-23-3922 1/0(19x) 0.85 0.93 16 x 14 1.06 635 725 220 155
161-23-3925 2/0(19x) 0.90 0.97 14 x 12 1.13 746 836 250 175
161-23-3928 3/0(19x) 0.95 1.02 16 x 12 1.18 867 957 285 200
161-23-3931 4/0(19x) 1.01 1.08 14 x 10 1.28 1035 1135 325 230
161-23-3934 250(37x) 1.06 1.16 16 x 10 1.37 1228 1344 360 255
161-23-3940 350(37x) 1.17 1.27 20 x 10 1.47 1514 1692 425 300
1/3 NEUTRAL
160-23-3910 2(7x) 0.78 0.85 6 x 14 0.98 429 519 160 135
160-23-3916 1(19x) 0.81 0.89 6 x 14 1.02 464 554 180 155
160-23-3922 1/0(19x) 0.85 0.93 6 x 14 1.06 506 596 205 175
160-23-3925 2/0(19x) 0.90 0.97 8 x 14 1.10 568 658 235 200
160-23-3928 3/0(19x) 0.95 1.02 10 x 14 1.15 653 743 270 230
160-23-3931 4/0(19x) 1.01 1.08 12 x 14 1.21 752 852 300 240
160-23-3934 250(37x) 1.06 1.16 14 x 14 1.29 873 973 330 260
160-23-3940 350(37x) 1.17 1.27 18 x 14 1.39 1092 1208 390 320
160-23-3943 500(37x) 1.29 1.39 16 x 12 1.56 1405 1583 470 385
160-23-3946 750(61x) 1.49 1.59 16 x *   1.79 1920 2170 570 470
160-23-3949 1000(61x) 1.64 1.77 18 x *   1.98 2465 2813 665 550
* Special conductor size

(1) Ampacities

Full neutral, single phase ampacities are based on ICEA S-94-649, Appendix F for 90°C conductor temperature, 20°C ambient temperature, 100% load factor and an earth thermal resistivity of RHO 90.

One third neutral, three phase ampacities are based on ICEA P-53-426 triplexed or triangular configuration for the same conditions stated above.

A/93100230