THE OKONITE COMPANY Product Data
Section 2: Sheet 3
 

COMPACT STRAND
CONSTRUCTION

  printer friendly version (PDF)

Okoguard®-Okoseal® Type MV-105

5/8kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
5kV-133% or 8kV-100% Insulation Level
For Cable Tray Use - Sunlight Resistant
UL
 

A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shielding-CopperTape

F Jacket-Okoseal


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long , problem free service. The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.



Jacket

The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil, acids and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for use as feeder circuits, in electric utility generating stations, for distribution circuits, and for feeders or branch circuits in industrial and commercial installations. Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250.4(A)(5), or messenger supported in industrial establishments and electric utilities. Sizes 1/0 AWG and larger may also be installed in cable tray.


Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen applied directly over the insulation. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.

Shield: 5 mil bare copper tape helically applied with 25% nominal overlap.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.3 and UL 1072 for polyvinyl chloride jackets. UL Listed as Type MV-105 and sunlight resistant, in accordance with UL 1072. CSA C68.3 listed and rated FT4 and -25°C.

Product Features

  • Triple tandem extruded, all EPR system.
  • Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE).
  • 105°C continuous operating temperature.
  • 140°C emergency rating.
  • 250°C short circuit rating.
  • Passes UL and IEEE 383 and 1202 (1/0 AWG and larger) Vertical Tray Flame Test.
  • Excellent corona resistance.
  • Screens are clean stripping.
  • Exceptional resistance to “treeing”.
  • Exceptional resistance to moisture.
  • Resistant to most oils, acids, and alkalies.
  • Sunlight resistant.
  • For Cable Tray Use.
  • CSA FT4, -25°C.
  • Improved Temperature Rating. 

Okoguard Insulation: 115 mils (2.92mm),
5kV—133% or 8kV—100% Insulation Level
1-Catalog Number (1)
2-Conductor Size AWG or kcmil
3-Conductor Size -mm2
4-Approx. Dia. over Insulation (in.)
5-Approx. Dia. over Screen (in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
  9-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000’
11-Approx. Ship Weight lbs./1000’
12-Ampacities Conduit in Air (2)
13-Ampacities Underground Duct (3)
14-Ampacities Cable Tray (4)
15-Conduit Size Inches (5)*
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

114-23-3824
114-23-3826
114-23-3865
114-23-3832

1/0
2/0
3/0
4/0

53.5
67.4
85.0
107.0

0.61
0.65
0.70
0.75

0.67
0.71
0.76
0.81

60
60
80
80

1.52
1.52
2.03
2.03

0.81
0.85
0.95
0.99

20.6
21.6
24.1
25.2

615
720
895
1030

655
775
950
1090

200
225
270
305

210
235
270
310

220
245
290
335

2 1/2
2 1/2
3
3

114-23-3834
114-23-3838
114-23-3846
114-23-3873
114-23-3855

250
350
500
750
1000

127.0
177.0
253.0
380.0
507.0

0.80
0.89
1.01
1.19
1.34

0.86
0.95
1.07
1.26
1.42

80
80
80
80
80

2.03
2.03
2.03
2.03
2.03

1.05
1.14
1.26
1.45
1.61

26.7
29.0
32.0
36.9
40.8

1185
1540
2055
2940
3775

1250
1625
2155
3120
3955

355
430
530
665
770

345
415
505
630
720

 370
460
580
750
900

3
3 1/2
3 1/2
4
4

 
Authorized stock item. Available from our Customer Service Center.

Aluminum Conductors
(1) Aluminum conductors are available on special order.

Ampacities
(2) Ampacities are in accordance with Table 310.73 of the NEC for three single Type MV-105 5kV conductors or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C. Refer to Table 310.73 for 8kV ampacities

(3) Ampacities are in accordance with Table 310.77 of the NEC for three single 5kV conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C and thermal resistance (RHO) of 90. Refer to Table 310.77 for 8kV ampacities.

(4) Ampacities based on single Type MV-105 5kV conductors, or single conductors twisted together (triplexed, quadruplexed, etc.) size 1/0 AWG and larger, installed in uncovered cable tray in accordance with Section 392.13 of the NEC at an ambient temperature of 40°C and a conductor temperature rating of 105°C. In accordance with NEC Section 392.13(B)(1) the ampacities are 75% of the values given in NEC Table 310.69 (copper conductors). Where the cable tray is covered for more than six feet with solid unventilated covers, the ampacities shall not exceed 93% of the values shown above. Refer to Table 10.69 for 8kV ampacities.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(5) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit l.D. to cable O.D. should be checked to avoid possible jamming.

 

D/07110203 
BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS | QUALITY ASSURANCE |

| HOMEPAGE | CONTACT US |