Okoguard®-Okoseal® Type MV-105
5/8kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C
Rating
5kV-133% or 8kV-100% Insulation Level
For Cable Tray Use - Sunlight Resistant

|
|
A Uncoated, Okopact (Compact
Stranded) Copper Conductor
B Strand Screen-Extruded
Semiconducting EPR
C Insulation-Okoguard EPR
D Insulation Screen-Extruded
Semiconducting EPR
E Shielding-CopperTape
F Jacket-Okoseal
Insulation
Okoguard is Okonite's registered trade name for its exclusive
ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum
balance of electrical and physical properties is unequaled in other solid
dielectrics. Okoguard insulation, with the distinctive red color and a
totally integrated EPR system, provides the optimum balance of electrical
and physical properties for long , problem free service. The triple tandem
extrusion of the screens with the insulation provides optimum electrical
characteristics.
Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and
has excellent resistance to oil, acids and most chemicals.
Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for use
as feeder circuits, in electric utility generating stations, for
distribution circuits, and for feeders or branch circuits in industrial and
commercial installations. Type MV cables may be installed in wet or dry
locations, indoors or outdoors (exposed to sunlight), in any raceway or
underground duct, directly buried if installed in a system with a grounding
conductor in close proximity that conforms with NEC Section 250.4(A)(5), or
messenger supported in industrial establishments and electric utilities.
Sizes 1/0 AWG and larger may also be installed in cable tray. |
|
Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.
Strand Screen: Extruded semiconducting EPR strand screen. Meets or
exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 &
S-97-682, AEIC CS8, CSA C68.3 and UL 1072.
Insulation: Meets or exceeds electrical and physical requirements
of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.
Insulation Screen: Extruded semiconducting EPR insulation screen
applied directly over the insulation. Meets or exceeds electrical and
physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA
C68.3 and UL 1072.
Shield: 5 mil bare copper tape helically applied with 25% nominal
overlap.
Jacket: Meets or exceeds electrical and physical requirements of
ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.3 and UL 1072 for polyvinyl
chloride jackets. UL Listed as Type MV-105 and sunlight resistant, in
accordance with UL 1072. CSA C68.3 listed and rated FT4 and -25°C.
Product Features
- Triple tandem extruded, all EPR system.
- Okoguard cables meet or exceed all recognized industry standards
(UL, AEIC, NEMA/ICEA, IEEE).
- 105°C continuous operating temperature.
- 140°C emergency rating.
- 250°C short circuit rating.
- Passes UL and IEEE 383 and 1202 (1/0 AWG and larger) Vertical Tray
Flame Test.
- Excellent corona resistance.
- Screens are clean stripping.
- Exceptional resistance to “treeing”.
- Exceptional resistance to moisture.
- Resistant to most oils, acids, and alkalies.
- Sunlight resistant.
- For Cable Tray Use.
- CSA FT4, -25°C.
- Improved Temperature Rating.
|
Okoguard Insulation: 115 mils (2.92mm),
5kV—133% or 8kV—100% Insulation Level |
1-Catalog Number
(1)
2-Conductor Size AWG or kcmil
3-Conductor Size -mm2
4-Approx. Dia. over Insulation (in.)
5-Approx. Dia. over Screen (in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches |
9-Approx.
O.D. - mm
10-Approx. Net Weight lbs./1000’
11-Approx. Ship Weight lbs./1000’
12-Ampacities Conduit in Air (2)
13-Ampacities Underground Duct (3)
14-Ampacities Cable Tray (4)
15-Conduit Size Inches (5)*
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
15 |
|
114-23-3824
114-23-3826
114-23-3865
114-23-3832
|
1/0
2/0
3/0
4/0
|
53.5
67.4
85.0
107.0
|
0.61
0.65
0.70
0.75
|
0.67
0.71
0.76
0.81
|
60
60
80
80
|
1.52
1.52
2.03
2.03
|
0.81
0.85
0.95
0.99
|
20.6
21.6
24.1
25.2
|
615
720
895
1030
|
655
775
950
1090
|
200
225
270
305
|
210
235
270
310
|
220
245
290
335
|
2
1/2
2
1/2
3
3
|
|
114-23-3834
114-23-3838
114-23-3846
114-23-3873
114-23-3855
|
250
350
500
750
1000
|
127.0
177.0
253.0
380.0
507.0
|
0.80
0.89
1.01
1.19
1.34
|
0.86
0.95
1.07
1.26
1.42
|
80
80
80
80
80
|
2.03
2.03
2.03
2.03
2.03
|
1.05
1.14
1.26
1.45
1.61
|
26.7
29.0
32.0
36.9
40.8
|
1185
1540
2055
2940
3775
|
1250
1625
2155
3120
3955
|
355
430
530
665
770
|
345
415
505
630
720
|
370
460
580
750
900
|
3
3
1/2
3
1/2
4
4
|
|
Authorized stock item.
Available from our Customer Service Center. Aluminum
Conductors
(1) Aluminum conductors are available on special order.
Ampacities
(2) Ampacities are in accordance with Table 310.73 of
the NEC for three single Type MV-105 5kV conductors or single conductors
twisted together (triplexed) and installed in an isolated conduit in air at
an ambient temperature of 40°C and a conductor temperature of 105°C. Refer
to Table 310.73 for 8kV ampacities
(3) Ampacities are in accordance with Table 310.77 of
the NEC for three single 5kV conductors or triplexed cable in one
underground raceway, three feet deep with a conductor temperature of 105°C,
100% Load Factor, an ambient earth temperature of 20°C and thermal
resistance (RHO) of 90. Refer to Table 310.77 for 8kV ampacities.
(4) Ampacities based on single Type MV-105 5kV
conductors, or single conductors twisted together (triplexed, quadruplexed,
etc.) size 1/0 AWG and larger, installed in uncovered cable tray in
accordance with Section 392.13 of the NEC at an ambient temperature of 40°C
and a conductor temperature rating of 105°C. In accordance with NEC Section
392.13(B)(1) the ampacities are 75% of the values given in NEC Table 310.69
(copper conductors). Where the cable tray is covered for more than six feet
with solid unventilated covers, the ampacities shall not exceed 93% of the
values shown above. Refer to Table 10.69 for 8kV ampacities.
Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite
Engineering Data Bulletin for installation in duct banks, multiple point
grounded shields, other ambient temperatures, circuit configurations or
installation requirements.
(5) Recommended size of rigid or nonmetallic conduit
for three conductors based on 40% maximum fill.
*The jam ratio, conduit l.D. to cable O.D. should be checked to avoid
possible jamming.
|
|