THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 24
Loxarmor® Type MV-90 or MC
2.4kV Okoguard® Nonshielded Power Cable
3 Okopact® (Compact Stranded) Copper Conductors/90°C Rating
100% and 133% Insulation Level
For Cable Tray Use-Sunlight Resistant-For Direct Burial
UL
.

A Uncoated, Okopact (Compact Stranded) Copper Conductors

B Extruded Semiconducting EPR Strand Screen

C Okoguard Insulation

D Okopact (Compact) Copper Grounding Conductor

E Phase Identification Tape

F Fillers and Binder Tape

G Loxarmor

H Jacket -Yellow Okoseal

Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectric. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

Assembly
The Type MV-90 conductors are assembled with fillers and a binder tape overall. One bare stranded copper grounding conductor is placed in one of the outer interstices. The interlocked armor provides good mechanical strength. For direct burial, embedment in concrete or for areas subjected to corrosive atmospheres, the Loxarmor is protected with a yellow Okoseal® (PVC) jacket.

Applications
Loxarmor power cables are recommended as an economical alternate to a wire in conduit system. They are designed specifically for use on feeders and branch circuits in industrial power distribution systems.

Loxarmor power cables may be installed in both exposed and concealed work, wet and dry location, direct burial in the earth, or embedded in concrete. They may be installed on metal racks, troughs, in cable trays or secured to supports not greater than 6 feet apart. Loxarmor power cables are also approved for Classes I and II, Division 2 and Class III, Divisions 1 and 2, hazardous locations - NEC Articles 501, 502 and 503.

Specifications
Conductors: Uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR conductor stress relief meets or exceeds electrical and physical requirements of ICEA S-96-659/NEMA WC71 and UL 1072.

Insulation: Okoguard meets or exceeds electrical and physical requirements of ICEA S-96-659/NEMA WC71 and UL 1072.

Phase Identification: Colored tape over insulation (black, red and blue).

Grounding Conductor: Uncoated copper compact stranded per ASTM B-496 and sized in accordance with UL 1072.

Assembly: Cabled with one ground wire, fillers in the interstices, binder tape overall.

Loxarmor: Galvanized steel or aluminum interlocked tape armor per UL 1072, ICEA S-96-659/NEMA WC71, and UL Listing E-38916.

Jacket: Sunlight resistant, yellow PVC jacket in accordance with UL 1072.

UL Listed as Type MV-90 or MC, sunlight resistant, for use in cable tray, and for direct burial in accordance with UL 1072.

Product Features

  • Tandem extruded all EPR system. 
  • Complete prepackaged, color coded, factory tested wiring system. 
  • Okoguard Loxarmor cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE). 
  • Passes the vertical tray flame test requirements of IEEE 383 and 1202, UL 1072 & ICEA T-29-520 (210,000 BTU/hr). 
  • Complies with NEC Sections 310-7 and 300-50 for direct burial. 
  • Excellent corona resistance. 
  • Exceptional resistance to "treeing". 
  • Stress cones not required. 
  • Resistant to most oils, acids, and alkalies.

Okoguard Insulation: 90 mils (2.29mm) with Yellow Okoseal Jacket
1-Catalog Number(1)
2-Conductor Size - AWG/kcmil
3-Conductor Size - mm2
4-Approx. Diameter over Insulation - Inches

5-Ground Conductor Size - Awg/kcmil
6-Ground Conductor Size - mm2
7-Approx. Core O.D. - Inches
8-Approx. Core O.D. - mm
9-Loxarmor O.D. - In.
10-Jacket Thickness - mils
11-Jacket Thickness - mm

12-Approx. O.D. - Inches
13-Approx. O.D. - mm
14-Approx. Net Weight lbs./1000'
15-Approx. Ship Weight lbs./1000'
16-Ampacities in Air(2)
17-Ampacities Cable Tray(3)
18-Ampacities Direct Burial(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Galvanized Steel Loxarmor
114-24-5341 8 8.4 0.36 8 8.4 0.84 21.3 1.06 50 1.27 1.17 29.7 815 895 59 52 85
114-24-5342 6 13.3 0.39 6 13.3 0.92 23.3 1.14 50 1.27 1.25 31.7 985 1075 79 69 105
114-24-5343 4 21.2 0.44 6 13.3 1.01 25.7 1.23 50 1.27 1.34 34.1 1209 1299 105 91 135
114-24-5344 2 33.6 0.50 6 13.3 1.15 29.3 1.37 50 1.27 1.48 37.6 1567 1710 140 125 180
114-24-5345 1 42.4 0.52 4 21.2 1.21 30.7 1.43 50 1.27 1.54 39.0 1820 1963 160 140 200
114-24-5346 1/0 53.5 0.56 4 21.2 1.28 32.6 1.50 60 1.52 1.61 41.0 2073 2216 185 165 230
114-24-5347 2/0 67.4 0.60 4 21.2 1.38 35.0 1.60 60 1.52 1.73 43.9 2435 2599 215 190 260
114-24-5348 4/0 107.0 0.70 3 26.7 1.59 40.5 1.84 60 1.52 1.98 50.2 3523 3779 285 255 335
114-24-5349 250 127.0 0.75 3 26.7 1.70 43.3 1.95 60 1.52 2.08 52.9 4038 4294 320 280 365
114-24-5350 350 177.0 0.85 2 33.6 1.90 48.2 2.15 60 1.52 2.28 57.9 5234 5793 395 350 440
114-24-5351 500 253.0 0.96 1 42.4 2.14 54.4 2.39 75 1.91 2.56 64.9 6965 7524 485 425 530
114-24-5352 750 380.0 1.14 1/0 53.5 2.53 64.4 2.78 75 1.91 2.95 74.8 9818 10580 615 525 650
114-24-5353 1000 507.0 1.29 1/0 53.5 3.12 79.3 3.12 85 2.16 3.31 84.1 12567 13645 705 590 730
Aluminum Loxarmor
114-24-5800 8 8.4 0.36 8 8.4 0.84 21.3 1.07 50 1.27 1.18 30.0 667 747 59 52 85
114-24-5802 6 13.3 0.39 6 13.3 0.92 23.3 1.15 50 1.27 1.26 32.0 825 915 79 69 105
114-24-5804 4 21.2 0.44 6 13.3 1.01 25.7 1.24 50 1.27 1.35 34.4 1033 1123 105 91 135
114-24-5806 2 33.6 0.50 6 13.3 1.15 29.3 1.38 50 1.27 1.49 37.9 1367 1510 140 125 180
114-24-5808 1 42.4 0.52 4 21.2 1.21 30.7 1.44 50 1.27 1.55 39.3 1611 1754 160 140 200
114-24-5810 1/0 53.5 0.56 4 21.2 1.28 32.6 1.51 50 1.27 1.62 41.2 1851 1994 185 165 230
114-24-5812 2/0 67.4 0.60 4 21.2 1.38 35.0 1.61 60 1.52 1.74 44.2 2197 2361 215 190 260
114-24-5816 4/0 107.0 0.70 3 26.7 1.59 40.5 1.85 60 1.52 1.99 50.4 3163 3419 285 255 335
114-24-5818 250 127.0 0.75 3 26.7 1.70 43.2 1.96 60 1.52 2.09 53.1 3655 3911 320 280 365
114-24-5820 350 177.0 0.85 2 33.6 1.90 48.2 2.16 60 1.52 2.29 58.1 4807 5366 395 350 440
114-24-5822 500 253.0 0.96 1 42.4 2.14 54.4 2.40 75 1.91 2.57 65.2 6484 7043 485 425 530
114-24-5824 750 380.0 1.14 1/0 53.5 2.53 64.4 2.85 85 2.16 3.02 76.6 9427 10189 615 525 650
114-24-5826 1000 507.0 1.29 1/0 53.5 3.12 79.3 3.19 85 2.16 3.38 85.8 12124 13202 705 590 730

Length Tolerance: Cut lengths of 1,000 feet or longer are subject to a tolerance of ±10%; less than 1,000 feet, ±15%.

Non-jacketed Loxarmor available on special order.

Aluminum Okopact Conductors

(1) Aluminum Okopact conductors are available on special order. To order aluminum Okopact conductors, change the first three digits of the catalog number from 114 to 134.

Ampacities

(2) Ampacities are in accordance with Table 310-71 of the NEC for an insulated three conductor cable, isolated In air, with a conductor operating temperature of 90°C and an ambient air temperature of 40°C.

(3) Ampacities are in accordance with Table 310-75 of the NEC for a three conductor Type MV-90 or MC cable installed in uncovered cable tray in accordance with Section 318-13 of the NEC with a conductor operating temperature of 90°C and ambient air temperature of 40°C. Where the cable tray is covered for more than six feet with solid unventilated covers, the ampacities shall not be more than 95% of the values shown above.

(4) Ampacities are in accordance with Table 310-83 of the NEC for an insulated three conductor cable directly buried in the earth with a conductor operating temperature of 90°C, ambient earth temperature of 20°C, 100% load factor, thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, other ambient temperatures, circuit configurations or installation requirements.

B/97050224