Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber
(EPR) base, thermosetting compound, whose optimum balance of electrical and physical
properties is unequaled in other solid dielectrics. Okoguard insulation, with the
distinctive red color and a totally integrated EPR system, provides the optimum balance of
electrical and physical properties for long, problem free service. Assembly
The Type MV-105 conductors are assembled with fillers, one bare stranded grounding
conductor and a binder tape into a round core. A continuously corrugated welded aluminum
sheath (C-L-X) encases the cable core. The C-L-X sheath is protected with a low
temperature red Okoseal® jacket. The impervious, continuous, corrugated
aluminum C-L-X sheath provides complete protection against moisture, liquids and gases in
addition to its excellent mechanical strength. In addition, the aluminum sheath has
adequate ampacity capability to be used as a grounding conductor in non HL areas. The
Okoseal jacket allows the cable to be direct buried in the ground, embedded in concrete or
areas subjected to corrosive atmospheres.
Applications
C-L-X power cables are recommended as an economical alternate to a wire in conduit system.
They are designed specifically for use as feeders or branch circuits in industrial and
utility power distribution systems. C-L-X power cables may be installed in both exposed
and concealed work, wet and dry locations, direct burial in the earth, or embedded in
concrete. They may be installed on metal racks, troughs, in cable trays or secured to
supports not greater than 6 feet apart.
C-L-X Type MC-HL cables are also approved for Classes I, II, and III, Divisions 1 and 2
and Class I, Zone 1 and 2
hazardous locations - NEC Articles 501, 502, 503 and 505.
Specifications
Conductors: Uncoated copper compact stranded per ASTM B-496.
Strand Screen: Extruded semiconducting EPR strand screen meets or exceeds
electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072.
Insulation: Okoguard meets or exceeds the electrical and physical requirements
of ICEA S-93-639/NEMA WC74 and UL 1072. The insulated conductors are tested in accordance with AEIC
CS8.
Insulation Screen: Extruded semiconducting EPR insulation screen meets or
exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072.
Shield: 5 mil uncoated copper tape with 12.5% nominal overlap.
Phase Identification: Color coded (black, red, blue) polyester ribbon laid
longitudinally under the copper shield.
Grounding Conductor: Uncoated copper in accordance with UL 1072.
Assembly: Cabled with fillers in the interstices, binder tape overall.
Sheath: Close fitting, impervious, continuous, corrugated aluminum C-L-X per UL
1072, and UL listing E-60545; C-L-X is recognized as a grounding conductor by NEC.
Jacket: A low temperature, sunlight resistant, red PVC jacket in accordance with
UL 1072 and CSA C22.2. Other color jackets are available.
UL Listed as type MV-105 or MC-HL, sunlight resistant, for use in cable tray, and for
direct burial in accordance with UL 1072 and 2225. Conforms to applicable requirements of
IEC 502, 540, and 332-3. CSA Listed to C68.3.
Product Features
-
Triple tandem extruded, all EPR system.
- Complete prepackaged, color coded, factory tested
wiring system.
- Okoguard C-L-X cables meet or exceed all recognized industry standards UL,
AEIC, NEMA/ICEA, IEEE.
- Passes the vertical tray flame test requirements of IEEE 383 and
1202, UL 1072, ICEA T-29-520 (210,000 BTU/hr.) and the 210,000 BTU/hr. corner
configuration test.
- Complies with NEC Sections 310.7 and 300.50 for direct burial.
-
Complies with NEC Articles 501, 502, 503 and 505 for hazardous locations.
- Continuous sheath
provides grounding safety.
- Excellent corona resistance.
- Screens are clean stripping.
-
Exceptional resistance to "treeing".
- Installation temperature of -40°C.
-
Improved Temperature Rating.
|