THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 22
C-L-X® Type MV-105 or MC-HL
15kV Okoguard® Shielded Power Cable-Aluminum Sheath
3 Okopact® (Compact Stranded) Copper Conductors/105°C Rating
133% Insulation Level
For Cable Tray Use-Sunlight Resistant-For Direct Burial
UL SA
A Uncoated Okopact (Compact Stranded) Copper Conductors

B Extruded Semiconducting EPR Strand Screen

C Okoguard Insulation (EPR)

D Phase Identification Tape

E Extruded Semiconducting EPR Insulation Screen

F Copper Grounding Conductor

G Uncoated Copper Shield

H Fillers and Binder Tape

J Impervious, Continuous, Corrugated Aluminum C-L-X Sheath

K Jacket-Red Low Temperature Okoseal

Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) base, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

Assembly
The Type MV-105 conductors are assembled with fillers, one bare stranded grounding conductor and a binder tape into a round core. A continuously corrugated welded aluminum sheath (C-L-X) encases the cable core. The C-L-X sheath is protected with a low temperature red Okoseal® jacket. The impervious, continuous, corrugated aluminum C-L-X sheath provides complete protection against moisture, liquids and gases in addition to its excellent mechanical strength. In addition, the aluminum sheath has adequate ampacity capability to be used as a grounding conductor in non HL areas. The Okoseal jacket allows the cable to be direct buried in the ground, embedded in concrete or areas subjected to corrosive atmospheres.

Applications
C-L-X power cables are recommended as an economical alternate to a wire in conduit system. They are designed specifically for use as feeders or branch circuits in industrial and utility power distribution systems. C-L-X power cables may be installed in both exposed and concealed work, wet and dry locations, direct burial in the earth, or embedded in concrete. They may be installed on metal racks, troughs, in cable trays or secured to supports not greater than 6 feet apart.

C-L-X Type MC-HL cables are also approved for Classes I, II, and III, Divisions 1 and 2 and Class I, Zone 1 and 2  hazardous locations - NEC Articles 501, 502, 503 and 505.

Specifications
Conductors: Uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072.

Insulation: Okoguard meets or exceeds the electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072. The insulated conductors are tested in accordance with AEIC CS8.

Insulation Screen: Extruded semiconducting EPR insulation screen meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072.

Shield: 5 mil uncoated copper tape with 12.5% nominal overlap.

Phase Identification: Color coded (black, red, blue) polyester ribbon laid longitudinally under the copper shield.

Grounding Conductor: Uncoated copper in accordance with UL 1072.

Assembly: Cabled with fillers in the interstices, binder tape overall.

Sheath: Close fitting, impervious, continuous, corrugated aluminum C-L-X per UL 1072, and UL listing E-60545; C-L-X is recognized as a grounding conductor by NEC.

Jacket: A low temperature, sunlight resistant, red PVC jacket in accordance with UL 1072 and CSA C22.2. Other color jackets are available.

UL Listed as type MV-105 or MC-HL, sunlight resistant, for use in cable tray, and for direct burial in accordance with UL 1072 and 2225. Conforms to applicable requirements of IEC 502, 540, and 332-3. CSA Listed to C68.3.

Product Features

  • Triple tandem extruded, all EPR system. 
  • Complete prepackaged, color coded, factory tested wiring system. 
  • Okoguard C-L-X cables meet or exceed all recognized industry standards UL, AEIC, NEMA/ICEA, IEEE. 
  • Passes the vertical tray flame test requirements of IEEE 383 and 1202, UL 1072, ICEA T-29-520 (210,000 BTU/hr.) and the 210,000 BTU/hr. corner configuration test.
  • Complies with NEC Sections 310.7 and 300.50 for direct burial. 
  • Complies with NEC Articles 501, 502, 503 and 505 for hazardous locations. 
  • Continuous sheath provides grounding safety. 
  • Excellent corona resistance. 
  • Screens are clean stripping. 
  • Exceptional resistance to "treeing". 
  • Installation temperature of -40°C. 
  • Improved Temperature Rating.

Okoguard Insulation:220 mils(5.59mm)
1-Catalog Number(1)
2-Conductor Size - AWG/kcmil
3-Conductor Size - mm2
4-Approx. Diameter over Insulation - Inches

5-Ground Conductor Size - Awg or kcmil
6-Approx. Core O.D. - Inches
7-Approx. Core O.D. - mm
8-C-L-X O.D. - Inches
9-Jacket Thickness - mils
10-Jacket Thickness - mm
11-Approx. O.D. - Inches
12-Approx. O.D. - mm
13-Approx. Net Weight lbs./1000'
14-Approx. Ship Weight lbs./1000'
15-Ampacities in Air(2)
16-Ampacities Cable Tray(3)
17-Ampacities Direct Burial(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
With Red Okoseal Jacket
571-23-3504 2 33.6 0.75 6 1.82 46.2 2.15 60 1.52 2.24 56.9 2468 3147 185 165 200
571-23-3508 1 42.4 0.78 4 1.88 47.8 2.23 60 1.52 2.36 59.9 2806 3404 210 185 225
571-23-3512 1/0 53.5 0.82 4 1.96 49.8 2.32 75 1.91 2.48 63.0 3185 3674 240 215 255
571-23-3516 2/0 67.4 0.86 4 2.07 52.6 2.40 75 1.91 2.56 65.0 3625 4219 275 245 290
571-23-3524 4/0 107.0 0.96 3 2.27 57.7 2.62 75 1.91 2.78 70.6 4430 5385 360 320 345
571-23-3528 250 127.0 1.01 3 2.36 59.9 2.75 75 1.91 2.92 74.2 5081 5845 400 350 410
571-23-3536 350 177.0 1.11 2 2.60 66.0 3.03 85 2.16 3.21 81.5 6440 7305 490 430 495
571-23-3544 500 253.0 1.22 1 2.84 72.9 3.32 85 2.16 3.50 92.5 8371 9946 600 525 590
571-23-3548 750 380.0 1.40 1/0 3.23 82.0 3.80 85 2.16 4.00 101.6 11426 13087 745 635 720
Authorized stock item. Available from our Customer Service Centers.

Length Tolerance

Cut lengths subject to ±10% variation in length for lengths 1,000' or longer and ± 15% for lengths less than 1,000'.

Jackets:  Optional jacket types available - consult local sales office

Copper or bronze C-L-X and non-jacketed C-L-X are available on special order.

Aluminum Okopact Conductors

(1) Aluminum conductors are available on special order. To order aluminum Okopact conductors, change the first three digits of the catalog number from 571 to 521.

Ampacities

(2) Ampacities are in accordance with Table 310.71 of the NEC for an insulated three conductor cable, isolated in air, with a conductor operating temperature of 105°C and an ambient air temperature of 40°C.

(3) Ampacities are in accordance with Table 310.75 of the NEC for a three conductor Type MV-105 or MC cable installed in uncovered cable tray in accordance with Section 392.13 of the NEC with a conductor operating temperature of 105°C and ambient air temperature of 40°C. Where the cable tray is covered for more than six feet with solid unventilated covers, the ampacities shall not be more than 95% of the values shown above.

(4) Ampacities are in accordance with Table 310.83 of the NEC for an insulated three conductor cable directly buried in the earth with a conductor operating temperature of 105°C, ambient earth temperature of 20°C, 100% load factor, thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, other ambient temperatures, circuit configurations or installation requirements.

C-L-X® The Okonite Company

C/04050222
BACK TO DATA SHEET INDEX