COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 18B
Okoguard® Okoseal® Type MV-105
15kV Okoguard Shielded Power Cable
3 Okopact® (Compact Stranded) Copper Conductors/105°C Rating
100% & 133% Insulation Level
For Cable Tray Use-Sunlight Resistant-For Direct Burial
UL SA *
A Uncoated Okopact (Compact Stranded) Copper Conductors

B Extruded Semiconducting EPR Strand Screen

C Okoguard Insulation (EPR)

D Extruded Semiconducting EPR Insulation Screen

E Phase Identification Tape

F Okopact Copper Grounding Conductor, where indicated

G Uncoated Copper Shield

H Fillers and Binder Tape

J Jacket-Black Okoseal


Insulation
Okoguard Is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) base, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

Assembly
The Type MV-105 conductors are assembled with fillers and a binder tape overall. One bare stranded copper ground conductor is placed in one of the outer interstices.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil and most chemicals.

Applications
Okoguard shielded three conductor Okoseal Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits in industrial and utility power distribution systems. Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried, cable tray, or messenger supported in industrial establishments and electric utilities.

Specifications
Conductors: Uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072.

Insulation: Okoguard meets or exceeds the electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072. The insulated conductors are tested in accordance with AEIC CS8.

Insulation Screen: Extruded semiconducting EPR insulation screen per ICEA S-93-639/NEMA WC74, AEIC CS8 and UL 1072.

Shield: 5 mil uncoated copper tape with 12.5% nominal overlap.

Phase Identification: Color coded (black, red, blue) polyester ribbon laid longitudinally under the copper shield.

Grounding Conductor: Uncoated copper compact stranded per ASTM B-496 and sized in accordance with UL 1072.

Assembly: Cabled with fillers in the interstices, binder tape overall.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072 for polyvinyl chloride jackets.

UL Listed as Type MV-105, sunlight resistant for use in cable tray, and for direct burial in accordance with UL 1072.

*CSA Listing to C68.3 requires special order.

Product Features

Triple tandem extruded, all EPR system. Complete prepackaged, color coded, factory tested wiring system. Passes the UL 1072 & IEEE 383 vertical tray flame test requirements. Complies with NEC Sections 310-7 and 710-4(b) for direct burial. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Improved Temperature Rating.


1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation - Inches

5-Ground Conductor Size - Awg or kcmil
6-Ground Conductor Size - mm2
7-Approx. Core O.D. - Inches
8-Approx. Core O.D. - mm
9-Jacket Thickness - mils
10-Jacket Thickness - mm
11-Approx. Cable O.D. - Inches
12-Approx. Cable O.D. - mm
13-Approx. Net Weight lbs./1000'
14-Approx. Ship Weight lbs./1000'
15-Ampacities in Air(1)
16-Ampacities Cable Trays(2)
17-Ampacities Direct Burial(3)
  2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Okoguard Insulation: 175 mils(4.45mm), 100% Insulation Level
115-23-3766 2 33.6 0.66 6 13.3 1.63 41.4 110 2.79 1.86 47.2 2039 2226 185 165 200
115-23-3768 1/0 53.5 0.73 4 21.2 1.76 44.7 110 2.79 1.99 50.5 2582 2838 240 215 255
115-23-3770 2/0 67.4 0.77 4 21.2 1.85 47.0 110 2.79 2.09 53.1 2958 3214 275 245 290
115-23-3772 4/0 107.0 0.87 3 26.7 2.07 52.6 110 2.79 2.30 58.4 3987 4322 360 320 375
115-23-3774 250 127.0 0.91 3 26.7 2.17 55.1 110 2.79 2.41 61.2 4420 4755 400 350 410
115-23-3776 350 177.0 1.01 2 33.6 2.37 60.2 110 2.79 2.61 66.3 5648 6275 490 430 495
115-23-3778 500 253.0 1.13 1 42.4 2.66 67.6 140 3.56 2.96 75.2 7589 8351 600 525 590
115-23-3780 750 380.0 1.31 1/0 53.5 3.05 77.5 140 3.56 3.35 85.1 10378 11400 745 635 720
Okoguard Insulation: 220 mils(5.59mm), 133% Insulation Level
115-23-3802 2 33.6 0.75 6 13.3 1.82 46.2 110 2.79 2.06 52.3 2352 2608 185 165 200
115-23-3804 1/0 53.5 0.82 4 21.2 1.96 49.8 110 2.79 2.19 55.6 2917 3209 240 215 255
115-23-3806 2/0 67.4 0.86 4 21.2 2.05 52.1 110 2.79 2.29 58.2 3329 3664 275 245 290
115-23-3808 4/0 107.0 0.96 3 26.7 2.27 57.7 110 2.79 2.50 63.5 4326 4661 360 320 375
115-23-3810 250 127.0 1.01 3 26.7 2.37 60.2 110 2.79 2.61 66.3 4836 5463 400 350 410
115-23-3812 350 177.0 1.11 2 33.6 2.61 66.3 140 3.56 2.90 73.7 6255 7175 490 430 495
115-23-3814 500 253.0 1.22 1 42.4 2.89 73.4 140 3.56 3.16 80.3 7939 8869 600 525 590
115-23-3816 750 380.0 1.40 1/0 53.5 3.25 82.6 140 3.56 3.55 90.2 11021 12220 745 635 720
Authorized stock item. Available from our Customer Service Centers.

Length Tolerance:
Cut lengths subject to ± 10% variation in length for lengths 1,000' or longer and ± 15% for lengths less than 1,000'.

Ampacities

(1) Ampacities are in accordance with Table 310-71 of the NEC for an insulated three conductor cable, isolated in air, with a conductor operating temperature of 105°C and an ambient air temperature of 40°C.

(2) Ampacities are in accordance with Table 310-75 of the NEC for a three conductor Type MV-105 cable installed in uncovered cable tray in accordance with Section 318-13 of the NEC with a conductor operating temperature of 105°C and ambient air temperature of 40°C. Where the cable tray is covered for more than six feet with solid unventilated covers, the ampacities shall not be more than 95% of the values shown above.

(3) Ampacities are in accordance with Table 310-83 of the NEC for an insulated three conductor cable directly buried in the earth with conductor operating temperature of 105°C, ambient earth temperature of 20°C, 100% load factor, thermal resistance (RHO) of 90.

Refer to the NEC, lEEE/lCEA S-135 Power Cable Ampacities or the Okonite Engineering Data Bulletin for installation in duct banks, other ambient temperatures, circuit configurations or installation requirements.

A/97050221