THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 17
Okoguard®-Okoseal® Type MV-105
35kV Shielded Power Cable
One Okopact® (Compact Stranded) Aluminum Conductor/105°C Rating
100% and 133% Insulation Level
UL
A Conductor-Okopact (Compact Stranded) Aluminum

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shield-Copper Tape

F Jacket-Okoseal


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits in industrial and commercial installations.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 310.7, or messenger supported in industrial establishments and electric utilities.

Specifications
Conductor: Class B compact stranded aluminum per ASTM B-400.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: Uncoated 5 mil copper tape helically applied.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 and UL 1072 for polyvinyl chloride jackets.

UL Listed as Type MV-105 and sunlight resistant, in accordance with UL 1072. CSA Listed to C68.3.

A flame retardant construction, size 1/0 AWG and larger, for installation in cable tray is available on special order. This construction is UL labeled "MV-105 FOR CT USE."

Product Features
Triple tandem extruded all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE, CSA). 105°C continuous operating temperature. 140°C emergency rating. 250°C short circuit rating. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Moisture resistant. Resistant to most oils, acids, and alkalies Sunlight resistant. Improved Temperature Rating.


1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(1)
13-Ampacities Direct Burial(2)
14-Ampacities Underground Duct(3)
15-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Okoguard Insulation:345 mils(8.76mm), 100% Insulation Level
135-23-3516 1/0 53.5 1.07 1.15 80 2.03 1.34 33.9 925 1065 170 230 165 4
135-23-3517 2/0 67.4 1.12 1.19 80 2.03 1.38 35.0 990 1130 200 260 190 4
135-23-3519 3/0 85.0 1.16 1.24 80 2.03 1.43 36.2 1070 1265 225 295 215 4
135-23-3521 4/0 107.0 1.22 1.29 80 2.03 1.48 37.6 1160 1360 260 340 245 5
135-23-3523 250 127.0 1.27 1.35 80 2.03 1.53 38.9 1250 1450 290 370 270 5
135-23-3527 350 177.0 1.37 1.44 80 2.03 1.63 41.4 1440 1710 350 450 330 5
135-23-3531 500 253.0 1.49 1.57 110 2.79 1.81 46.0 1805 2070 430 545 400 5
135-23-3535 750 380.0 1.67 1.77 110 2.79 2.02 51.3 2280 2705 540 680 490 6
135-23-3537 1000 507.0 1.83 1.93 110 2.79 2.17 55.2 2680 3240 640 795 565 6
Okoguard Insulation:420 mils(10.7mm), 133% Insulation Level
135-23-3656 1/0 53.5 1.23 1.31 80 2.03 1.49 37.9 1130 1330 170 230 165 5
135-23-3657 2/0 67.4 1.27 1.35 80 2.03 1.54 39.0 1205 1400 200 260 190 5
135-23-3659 3/0 85.0 1.32 1.41 80 2.03 1.58 40.2 1290 1485 225 295 215 5
135-23-3661 4/0 107.0 1.37 1.45 80 2.03 1.64 41.5 1390 1660 260 340 245 5
135-23-3663 250 127.0 1.43 1.50 110 2.79 1.75 44.5 1590 1850 290 370 270 5
135-23-3667 350 177.0 1.52 1.60 110 2.79 1.85 46.9 1800 2065 350 450 330 6
135-23-3671 500 253.0 1.64 1.74 110 2.79 1.99 50.5 2120 2540 430 545 400 6
135-23-3675 750 380.0 1.83 1.93 110 2.79 2.18 55.2 2580 3150 540 680 490 6
135-23-3677 1000 507.0 1.98 2.08 110 2.79 2.33 59.1 3000 3340 640 795 565 -
Ampacities

(1) Ampacities are in accordance with Table 310-74 of the NEC for three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C.

(2) Ampacities are in accordance with Table 310-82 of the NEC for an insulated single conductor directly buried with a conductor temperature rating of 105°C, ambient earth temperature of 20°C, 100% Load Factor, thermal resistance (RHO) of 90, 7 1/2 inch spacing between conductor center lines and 24 inch spacing between circuits.

(3) Ampacities are in accordance with Table 310-78 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(4) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio conduit I.D. to cable O.D. should be checked to avoid possible jamming.

C/97020217
BACK TO DATA SHEET INDEX