COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 16
Okoguard®-Okoseal® Type MV-105
35kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
100% and 133% Insulation Level
UL
A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shield-Copper Tape

F Jacket-Okoseal


Insulation
Okoguard Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service. The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits in industrial and commercial installations.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 310.7, or messenger supported in industrial establishments and electric utilities.

Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: 5 mil bare copper tape helically applied.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 and UL 1072 for polyvinyl chloride jackets.

UL Listed as Type MV-105 and sunlight resistant, in accordance with UL 1072.

A flame retardant construction, size 1/0 AWG and larger, for installation in cable tray is available on special order. This construction is UL labeled "MV-105 FOR CT USE."

Product Features
Triple tandem extruded all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating temperature. 140°C emergency rating. 250°C short circuit rating. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing." Moisture resistant. Resistant to most oils, acids, and alkalies. Sunlight resistant. Improved Temperature Rating


1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(1)
13-Ampacities Direct Burial(2)
14-Ampacities Underground Duct(3)
15-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Okoguard Insulation:345 mils(8.76mm), 100% Insulation Level
115-23-3516 1/0 53.5 1.08 1.15 80 2.03 1.34 34.0 1150 1275 215 295 215 4
115-23-3517 2/0 67.4 1.12 1.19 80 2.03 1.38 35.0 1270 1380 255 335 245 4
115-23-3519 3/0 85.0 1.16 1.24 80 2.03 1.43 36.2 1420 1605 290 380 275 4
115-23-3521 4/0 107.0 1.22 1.30 80 2.03 1.49 37.7 1615 1800 330 435 315 5
115-23-3523 250 127.0 1.26 1.34 80 2.03 1.52 38.7 1770 1950 365 475 345 5
115-23-3527 350 177.0 1.36 1.44 80 2.03 1.62 41.2 2170 2420 440 575 415 5
115-23-3531 500 253.0 1.48 1.56 80 2.03 1.75 44.4 2764 3014 535 700 500 6
115-23-3535 750 380.0 1.66 1.76 110 2.79 2.00 50.9 3840 4240 655 865 610 6
115-23-3537 1000 507.0 1.82 2.16 110 2.79 2.16 54.9 4765 5300 755 1005 690 6
Okoguard Insulation:420 mils(10.7mm), 133% Insulation Level
115-23-3656 1/0 53.5 1.23 1.31 80 2.03 1.50 38.0 1355 1535 215 295 215 5
115-23-3657 2/0 67.4 1.27 1.35 80 2.03 1.54 39.0 1485 1665 255 335 245 5
115-23-3659 3/0 85.0 1.32 1.40 80 2.03 1.58 40.2 1645 1825 290 380 275 5
115-23-3661 4/0 107.0 1.37 1.45 80 2.03 1.64 41.5 1835 2085 330 435 315 5
115-23-3663 250 127.0 1.42 1.49 80 2.03 1.72 43.7 2000 2250 365 475 345 5
115-23-3667 350 177.0 1.52 1.59 110 2.79 1.84 46.7 2520 2770 440 575 415 5
115-23-3671 500 253.0 1.63 1.73 110 2.79 1.98 50.3 3155 3555 535 700 500 6
115-23-3675 750 380.0 1.81 1.91 110 2.79 2.16 54.9 4140 4680 655 865 610 6
115-23-3677 1000 507.0 1.97 2.07 110 2.79 2.32 58.9 5090 5630 755 1005 690 -
Authorized stock item. Available from our Customer Service Centers.

Ampacities

(1) Ampacities are in accordance with Table 310-73 of the NEC for three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C.

(2) Ampacities are in accordance with Table 310-81 of the NEC for an insulated single conductor directly buried with a conductor temperature rating of 105°C, ambient earth temperature of 20°C, 100% Load Factor, thermal resistance (RHO) of 90, 7 1/2 inch spacing between conductor center lines, and 24 inch spacing between circuits.

(3) Ampacities are in accordance with Table 310-77 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(4) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio conduit I.D. to cable O.D. should be checked to avoid possible jamming.

D/04090216