THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 15
Okoguard®-Okolene® Type MV-105
25kV LCS Shielded Power Cable
One Okopact® (Compact Stranded) Aluminum Conductor/105°C Rating
100% Insulation Level
Sunlight Resistant for Direct Burial or Underground Raceway
UL
A Conductor-Okopact (Compact Stranded) Aluminum

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shield-8 Mil LCS Copper Tape

F Jacket-Okolene


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Shield
An 8 mil copper longitudinal corrugated shield (LCS) is applied over the extruded semiconducting insulation screen. This construction provides a substantially lower shield resistance compared with a tight helically applied copper tape. The LCS resistance is also extremely stable during load cycling.

Jacket
The Okolene jacket on this cable is mechanically rugged, chemical, oil and moisture resistant.

Applications
Okoguard shielded Okolene Type MV-105 power cables are recommended for use as feeder circuits, in electric utility distribution circuits.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250-51, or messenger supported in industrial establishments and electric utilities.

Specifications
Conductor: EC Grade aluminum, Class B compact stranded per ASTM B-400.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: 8 mil longitudinal corrugated, copper shield with a 0.25" overlap.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 and UL 1072 for polyethylene jackets.

UL Listed as Type MV-105, sunlight resistant in accordance with UL 1072. CSA Listed to C68.3.

Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating temperature. 140°C emergency rating. 250°C short circuit rating. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Low shield resistance. Moisture resistant. Resistant to most oils, acids and alkalies. Sunlight resistant. Improved Temperature Rating.


1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(1)
13-Ampacities Direct Burial(2)
14-Ampacities Underground Duct(3)
15-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Okoguard Insulation:260 mils(6.60mm), 100% Insulation Level
135-23-6452 1 33.6 0.87 0.93 80 2.03 1.16 29.6 670 815 150 200 145 3 1/2
135-23-6456 1/0 53.5 0.90 0.96 80 2.03 1.20 30.5 715 860 170 230 165 3 1/2
135-23-6462 4/0 107.0 1.04 1.12 80 2.03 1.36 34.5 950 1140 260 340 245 4
135-23-6468 500 253.0 1.31 1.39 80 2.03 1.62 41.2 1440 1725 430 545 400 5
135-23-6472 750 380.0 1.50 1.58 110 2.79 1.88 47.7 1920 2265 540 680 490 6
135-23-6476 1000 507.0 1.65 1.75 110 2.79 2.05 52.1 2330 2800 640 795 565 6
Ampacities

(1) Ampacities are in accordance with Table 310-74 of the NEC for three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C.

(2) Ampacities are in accordance with Table 310-82 of the NEC for an insulated single conductor directly buried with a conductor temperature rating of 105°C, ambient earth temperature of 20°C, 100% load factor, thermal resistance (RHO) of 90, with 7 1/2" spacing between the conductor center lines and 24" spacing between circuits.

(3) Ampacities are in accordance with Table 310-78 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

Refer to the NEC IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(4) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit to cable O.D. should be checked to avoid possible jamming.

B/97020215
BACK TO DATA SHEET INDEX